System information

ATS2000/3000/4000/4500 Programming manual
134
Macro Logic Numbe
r
Macro No:
M 1 Disabled
*-Change, 0-Exit
35. PROGRAM MACRO LOGIC
Macro logic provides a powerful tool for activating zones or event flags under specific
conditions. These conditions are macro inputs being triggered, logic equations combining the
macro inputs and output conditions.
Up to four macro inputs can be included in the logic equation. A macro input is an event flag
or an output. Each macro input in the logic equation can be programmed as an AND or an
OR function and can be programmed to invert the logic.
Programming options are provided so that the macro result will trigger a macro output as a
pulse, time, on delay, off delay or latch when activated.
Figure 3. Overview of macro logic
!
CAUTION!
It is very important to plan the Macro Logic carefully on paper, noting all details, and
the origin of every zone and/or event flags, before attempting to program.
See also Event Flags (page 151) and Event to output (page 104).
35.1. Program number
Enter the number of the Macro logic program. There are 24 programs available.
35.1.1 Macro output function
The result of a macro, the macro output, will trigger an event flag or a zone. The macro
output can have some timing functions.
Option Function
Disabled
This macro logic program is disabled.
Non Timed
Follows the result of the logic equation only. If an event flag or output
for this macro changes, the logic equation will be calculated again.
Event flag/output 1
Macro logic
equation
“1 AND 2 OR 3”
Macro output
timing
£ >> ¥
Event flag
or Zone
Event flag/output 2
Event flag/output 3
Event flag/output 4