System information

ATS 2000/3000/4000/4500 Programming manual 121
No
Enable Remote Control
*-Change 0 - Skip
No
Remote Control if any Area Armed
*-Change 0 - Skip
Y
es Use Modem Inti. String
Change 0 - Skip
Specifies if connecting via dialler to a remote computer is possible if any area is armed.
If set to NO and a remote connection is established, the panel will be disconnected when
the user arms the system.
YES A remote connection is possible if an area is armed.
NO A remote connection is not possible if any area is armed.
Press 0 to go directly to Menu 29.8
29.3. Enable Remote Control
Menus 29.1 must be set to YES to use this option.
Specifies if arming areas, controlling outputs and door control is allowed from a remote
computer via dialler.
YES Remote arming of areas, controlling outputs and door control is allowed, when
disarmed.
NO Remote arming of areas, controlling outputs and door control is not allowed,
when disarmed.
Press 0 to go directly to Menu 29.8
This option will only disable remote control function and not status requests, and
will only operate if 29.1 is set to YES, and also depends on option 29.2 and the
status of the Areas.
29.4. Remote control if any area armed
Menu 29.1 and 29.2 must be set to YES to use this option..
Specifies if disarming and arming areas, controlling outputs and door control is allowed
from a remote computer via dialler.
YES Remote disarming and arming of areas, controlling outputs and door control is
allowed.
NO Remote disarming and arming of areas, controlling outputs and door control is
not allowed.
Press 0 to go directly to Menu 29.8
29.5. Use modem Init. String
Menu 29.1 must be set to YES to use this option.
Refer to options (29.1, 29.2, 29.3, 29.4) only for incoming calls or call-backs,
Events sent via modem depend on options 29.6, 29.7 and the computer phone
number.