System information

ATS 2000/3000/4000/4500 Programming manual 113
NO
Shunt Zone When Disarmed
*-Change 0 - Skip
NO
Shunt Zone When Armed
*-Change 0 - Skip
NO
Cancel Door Event Flag
*-Change 0 - Skip
NO
Zone Holds Event Flag for 2 Sec.
*-Change 0 - Skip
21.1.8. Shunt zone when disarmed
Specify if the zone will be shunted when one or more of the areas assigned to the
shunted zone are disarmed.
Press 0 to end programming this shunt timer and to select a new shunt
timer.
!
Set either Shunt zone when disarmed or Shunt zone when armed to YES. Otherwise
the shunt procedure will not operate.
21.1.9. Shunt zone when armed
It records whether the door shunt procedure operates when all the areas assigned to the
shunted zone are secure.
Press 0 to end programming this shunt timer and to select a new shunt
timer.
!
Set either Shunt zone when disarmed or Shunt zone when armed to YES. Otherwise
the shunt procedure will not operate.
21.1.10. Cancel door event flag
Define that closing the zone cancels the shunt time.
YES As soon as the shunted zone switches to normal state, the door unlock event
and the shunt timer are cancelled.
NO The door unlock event and the shunt timer are not cancelled if the zone
switches to normal state.
Press 0 to end programming this shunt timer and to select a new shunt
timer.
21.1.11. Zone holds event flag for 2 seconds
Delay cancelling of the door event flag. It is used for doors with magnetic locks and drop
bolts.
YES In order to allow time for a door to be properly closed, there is a 2-second delay
after the zone switches to normal and before it cancels the door event and
shunt timer.
NO There is no delay.
Press 0 to end programming this shunt timer and to select a new shunt
timer.