System information
ATS2000/3000/4000/4500 Programming manual
104
Event To Ouput
Output No:
Output 3 Mapped To Event Flag 123
Event Flag:
Event flag
Timezone
Output logic
Valid
Invalid
Output
normal/Inverted
Physical
out
p
ut
16. EVENT TO OUTPUT
Programming section to link events to outputs. Outputs are available as relay cards
(ATS1810, ATS1811) or open collector outputs (ATS1820).
Before an event flag actually will activate an output, a number of conditions have to be
met:
• The timezone has to be invalid (if programmed).
• The output logic defines how the output behaves when the timezone is valid.
• The output behaviour can be set to normal or inverted.
Only for a correct combination of conditions, the output will activate. See figure 2 for an
overview.
Figure 2. Basic functionality for outputs.
16.1. Output number
This is the physical number of the output. Each output has a specific number that will
identify the output to the control panel. The output number is determined by the address
of the device the relay card is connected to.
See the ATS2000/3000/4000/4500 Installation guide for more information on
output numbers on devices.
16.1.1. Event flag number
An event flag or a timezone activates an output. Enter the event flag number here.
The output follows the event flags during a valid timezone. If event number 0 is
programmed, the output does not follow any event flag.
Defaults:
The only events activating an output by default are:
Output 2 (strobe O/P) is linked to Event Flag 2.
Output 16 (Panel Siren O/P) is linked to Event Flag 1.