Programming instructions
19
60. Number of Attempt Before Lockout
61. Set the Attempts Lockout Time
• Number of attempts before lockout must be 1-9 attempts.
• The number of attempts is reduced by half every time the keypad is locked out without a
successful code entry (default is 6 attempts).
• The attempt count is reset each time a valid code is entered.
• Lockout Time must be 1-60 seconds.
How long the keypad is locked out after a series of unsuccessful attempts (default is 15
4
4
LOCKOUT
; 6 4 :
64. Disable Remote Input
• Wire a Normally Open Contact to Terminals 3 & 4. Momentarily close to allow person to
pass through door.
• Enter the functions below to Disable/Enable the Remote Input.
NOTE: The Remote Input is enabled as part of the default program.
Remote Input Disable/Enable
; 6 5 :
65. Enable Remote Input
; 6 6 ; [ _ _ ] :
(Ambush Code)
66. Ambush Code
• Ambush code must be 2 digits.
• An error will sound if the ambush code matches the 1st two digits of any user code. See
Using Ambush Function on page 5.
2
3
REMOTE INPUT
AMBUSH
; 6 0 ; [ _ ] :
(Number of Attempts)
; 6 1 ; [ _ _ ] :
(Lockout Time)
62-63. Reserved
59. AL-DTM Door Number
• Door Number must be between 1- 48.
For use with Alarm Lock’s AL-DTM Data Transfer Module. Using the AL-DTM up to 48
locks can be Downloaded/Uploaded and History LOGs can be retrieved. Enter a door
number for each lock. After configuring the AL-DTM, using Alarm Lock's DL-WINDOWS
Software, any of the following data transfers can be initiated by plugging the AL-DTM into
the lock and simply entering User Code 299 at the lock.
• Upload Lock Program
• Upload History LOG
• Download Lock Program
4
AL-DTM
; 5 9 ; [ _ _ ] :
Door Number)