500-ULAC Series Standby Battery Selection Chart
1. Select Power Supply:
505-ULAC, 510-ULAC or
515 Series
2. Determine current load
of draw in amps
3. Determine voltage to be
used
4. Read across to select
standby time in hours
desired
5. Reference “what to
order” by matching amp
load row to standby
hours column. Read
down to select “what to
order”
505-ULAC SERIES STANDBY TIME IN HOURS
Current Draw 12 VDC System 24 VDC System
of Load in Amps
HRS. HRS. HRS. HRS.
1.0 6 12 3 6
0.50 12 24 6 12
0.33 24 48 12 24
0.22 36 72 18 36
0.16 48 96 24 48
No. of SBP2’s
121 2
Required
510-ULAC SERIES STANDBY TIME IN HOURS
Current Draw 12 VDC System 24 VDC System
of Load in Amps
HRS. HRS. HRS. HRS. HRS. HRS. HRS. HRS.
3.0 2 4 6 8 -- -- -- --
2.0 3 6 9 12 1.5 3 4.5 6
1.0 6 12 18 24 3 6 9 12
0.50 12 24 36 48 6 12 18 24
0.33 24 48 72 96 12 24 36 48
0.22 36 72 108 144 18 36 54 72
0.16 48 96 144 192 24 48 72 96
No. of SBP2’s
1234123 4
Required
No. of SBE’s
0111011 1
Required
515 SERIES STANDBY TIME IN HOURS
Current Draw 12 VDC System 24 VDC System
of Load in Amps
HRS. HRS. HRS. HRS. HRS. HRS. HRS. HRS.
10.0 .20 .40 .60 .80 -- -- -- --
8.0 .44 .88 1.3 1.8 -- -- -- --
5.0 .84 1.7 2.6 3.4 .42 .84 1.3 1.7
4.0 1.2 2.4 3.6 4.8 .6 1.2 1.8 2.4
2.0 3 6 9 12 1.5 3 4.5 6
1.0 6 12 18 24 3 6 9 12
0.50 12 24 36 48 6 12 18 24
0.25 36 72 108 144 18 36 54 72
No. of SBP2’s
1234123 4
Required
No. of SBE’s
1111111 1
Required
Standby Battery Pack
(SBP2)
Standby Battery Enclosure
(SBE)