Specifications
7 
Part 3  Installation
Regulator outlet pressure is fixed ex-factory for the 
gas type that the regulator is converted to and it is 
NOT to be adjusted. 
The regulator connections are 
3
/
4
” BSP female. 
The connection to the appliance is 
3
/
4
” BSP male. 
(Refer to the 'Specifications' Section for the gas  
supply location dimensions). 
NOTE: 
A Manual Isolation Valve must be fitted to the  
individual appliance supply line. 
4.  Correctly locate the appliance into its final 
operating position and using a spirit level, adjust 
the legs so that the appliance is level and at the 
correct height. 
5.  Connect the gas supply to the appliance. A 
suitable joining compound which resists the 
breakdown action of LPG must be used on 
every gas line connection, unless compression 
fittings are used. 
6.  Check all gas connections for leakages using 
soapy water or other gas detecting equipment. 
7.  Check that the gas supply pressure is as shown in 
the ‘Specifications’ section, ‘Gas Supply 
Requirements’. 
NOTE: 
The supply pressure to be measured at the  
manifold test point and with 2 burners operating at 
the ‘High Flame’ setting. 
8.  Light the Main Burners. Refer to the 'Operations’ 
Section', ‘Open Burners’. 
9.  Verify that the supply pressure is still correct. 
10. Check that the Main Burner is alight and adjust 
the low fire adjustment screw on the open 
burner gas control valves to obtain the desired 
flame size. 
11. Check / adjust the main burner aeration gap. 
This gap should be set to the dimensions shown 
in the 'Gas Specification Tables' in ‘Part 6 - Gas 
Conversion’. 
NOTE: 
This appliance is fitted with adjustable feet to enable 
the appliance to be positioned securely and level.  
This should be carried out on completion of the gas 
connection. 
Assembly 
This model is delivered completely assembled. 
Ensure that legs and rollers are securely attached. 
NOTE: 
This appliance is fitted with adjustable feet to enable 
the appliance to be positioned securely and level.  
This should be carried out on completion of the gas 
connection. Refer to the 'Gas Connection' section. 
Gas Connection 
NOTE: 
ALL GAS FITTING MUST ONLY BE CARRIED OUT BY A 
QUALIFIED SERVICE PERSON. 
1.  Cobra Oven Ranges do not require an electrical 
connection, they function totally on the gas 
supply only. 
2.  It is essential that the gas supply is correct for the 
appliance to be installed and that adequate 
supply pressure and volume are available. The 
following checks should therefore be made 
before installation:- 
a.  The Gas Type the appliance has been  
supplied for is shown on coloured stickers 
located above the gas entry point and next 
to the rating plate. Check that this is correct 
for the gas supply the appliance is being 
installed for. The gas conversion procedure is 
detailed in the Gas Conversion Instruction 
Sheet for this appliance. 
b.  Supply Pressure required for this appliance is 
shown in the 'Specifications' section of this 
manual. Check the gas supply to ensure that 
adequate supply pressure exists. 
c.  Input Rate of this appliance is also stated on 
the Rating Plate rating plate located on the 
front lower corner of the R/H side panel, and 
in the 'Specifications' section of this manual. 
The input rate should be checked against the 
available gas supply line capacity. Particular 
note should be taken if the appliance is 
being added to an existing installation.
NOTE: 
It is important that adequately sized piping runs 
directly to the connection joint on the appliance, 
with as few tees and elbows as possible to give 
maximum supply volume. 
3.  Fit the gas regulator supplied, into the gas supply 
line as close to the appliance as possible. 
NOTE: 
Gas pressure regulator provided with this appliance 
is convertible between Natural Gas and LPG as per 
the ‘Gas Conversion Section’ in this manual. 
Ensure the regulator is converted to the correct gas 
type that the appliance will operate on. 
WARNING: 
DO NOT USE A NAKED FLAME TO CHECK FOR GAS LEAKAGES. 










