Specifications
17 
Part 6  Gas Conversion
Low Fire Adjustment 
1.  To change the thermostat ‘Low Fire’ screw for 
the gas type required, remove the following:- 
 Gas control knobs. 
 Control Panel. 
 Unscrew ‘Low Fire’ screw from gasvalve. 
  and fully screw in the new ‘Low Fire’ 
screw for the new gas type. (Refer to the 
‘Gas Specifications’ table at the rear of 
this section for the correct low fire screw 
sizes). 
2.  Refit the control panel. 
3.  Refit the gas control knobs. 
Gas Regulator 
- NAT Gas / LPG / Butane Only. 
NOTE: 
The regulator supplied is convertible between  
Natural Gas and LP Gas, but it’s outlet pressure is 
fixed ex-factory and is NOT to be adjusted. 
1.  Ensure that the gas supply is turned 'Off' at the 
mains. 
2.  Unscrew the hexagonal cap (23mm A/F) from 
the regulator. 
3.  Un-clip the plastic pin from the cap, reverse the 
pin and re-fit it back to the cap the correct way 
for the gas type to be used. (Either ‘LP’ or ‘NAT’ 
should be visible on the flank of the pin once 
re-fitted to the cap). 
4.  Screw the cap back into the regulator hand 
tight only. 
Low Fire Screw 
- Town Gas Only. 
1.  Unscrew and remove slotted cap from regulator. 
2.  Turn ‘On’ gas supply and appliance. 
3. Adjust pressure adjusting nut to achieve correct 
burner operating pressure. 
NOTE: 
Operating pressure is to be measured at the  
manifold test point and with both burners operating 
at ‘High Flame’ setting. 
4.  Verify operating pressure remains correct 
(Re-adjust the regulator if required). 
5.  Screw cap nut back onto regulator. 
Gas Type Identification Label 
On completion of gas conversion, replace gas type 
identification label located at:- 
- Rear of appliance, above gas connection. 
- Beside the rating plate. 
Commissioning 
Before leaving the converted installation; 
1.  Check all gas connections for leakages using 
soapy water or other gas detecting equipment. 
2.  Check the following functions in accordance 
with operating instructions specified in the 
'Operation' section of this manual. 
 Light Main Burners. 
 Check Low Fire burner operation. 
 Check High Fire burner operation. 
 Check Griddle Burner operation (If fitted). 
 Ensure that all controls operate correctly. 
 Ensure that operating pressure remains 
correct. 
3.  Ensure any adjustments done to components 
that have adjustments / settings sealed (e.g. 
paint sealed), these are re-sealed. 
NOTE: 
If it is not possible to get the appliance to operate 
correctly, shut ‘Off’ the gas supply and contact the 
supplier of this appliance. 
NOTE, Pin rotated 
for Natural Gas 
NOTE, Pin rotated 
for LPG 
Pressure Adjusting 
Screw 
Cap Nut 
WARNING: 
D
O NOT USE A NAKED FLAME TO CHECK FOR GAS LEAKAGES. 










