Manual

INSTALLATION INSTRUCTIONS FOR
CMP CABLE GLAND TYPE “E”
FOR TERMINATION OF CABLES WITH WIRE BRAID, TAPE ARMOUR (STA/DSTA), STRIP ARMOUR &
SINGLE WIRE ARMOUR (SWA) (WITH LEAD INNER SHEATH ON “E2” VARIANT). FOR USE IN
HAZARDOUS LOCATIONS.
INCORPORATING EC DECLARATION OF CONFORMITY TO DIRECTIVE 94/9/EC
CMP Document No. FI407 Issue 5 01/13
0518
Glasshouse Street St. Peters Newcastle upon Tyne NE6 1BS
Tel: +44 191 265 7411 Fax: +44 191 265 0581
E-Mail: cmp@cmp-products.co.uk Web: www.cmp-products.com
Notified Body: Sira Certification Service, Rake Lane, Chester CH4 9JN, England.
I, the undersigned, hereby declare that the equipment referred to herein conforms to the requirements of the ATEX Directive 94/9/EC and the following
standards:-
EN60079-0:2009, EN60079-1:2007, EN60079-7:2007, BS 6121:1989, EN50262:1998 (Amd 2001), EN61241:0-2004, EN61241-1:2004
Dr Geof Mood - Technical Director - (Authorised Person)
DUBAI HOUSTON NEWCASTLE SINGAPORE SHANGHAI PUSAN PERTH
www.cmp-products.com
Cable Gland Selection Table
Logo’s shown for illustration purposes only. Please check certification for details
CABLE GLAND TYPES
CABLE GLAND TYPES
E1FW, E2FW, E1FX,
E1FW, E2FW, E1FX,
E2FX, E1FU & E2FU
E2FX, E1FU & E2FU
Order codes shown are for E1FU glands
For e.g. E1FW glands substitue E1FW for E1FU - e.g. 20E1FW1RA
* Please note that the overall maximum cable bedding diameter for “E2” variants should be reduced by 1mm to allow for the inner lead sheath.
E1FW - SWA Armour
E2FW - SWA Armour for lead
sheathed cable
E1FX - Braid, Tape, etc Armour
E2FX - Braid, Tape, etc Armour for
lead sheathed cable
E1FU - Universal Gland for all
Armour Types
E2FU - Universal Gland for all
Armour Types with lead
sheathed cable
Cable
Gland
Size
Available Entry Threads
Thread
L
ength
metric
C
able Beding
Diameter
O
verall Cable
Diameter
Armour Wire Diameter
A
cross
Flats
A
cross
Corners
Protrusion
L
ength
Ordering
Reference
(Brass Metric)
PVC
Shroud
Ref
Standard Option Grooved Cone Stepped Cone
M
etric
N
PT
N
PT
M
in
M
ax
M
in
M
ax *
M
in
M
ax
M
in
M
ax
M
ax
M
ax
20S/16 M20 1/2” 3/4” 15.0 3.1 8.6 6.1 11.5 0.15 0.5 0.9 1.0 24.0 25.9 58.5 20S16E1FU1RA PVC04
20S M20 1/2” 3/4” 15.0 6.1 11.6 9.5 15.9 0.15 0.5 0.9 1.25 24.0 25.9 58.5 20SE1FU1RA PVC04
20 M20 1/2” 3/4” 15.0 6.5 13.9 12.5 20.9 0.2 0.5 0.9 1.25 30.5 32.9 60.5 20E1FU1RA PVC06
25S M25 3/4” 1” 15.0 11.1 19.9 14.0 22.0 0.2 0.6 1.25 1.6 37.5 40.5 67.5 25SE1FU1RA PVC09
25 M25 3/4” 1” 15.0 11.1 19.9 18.2 26.2 0.2 0.6 1.25 1.6 37.5 40.5 67.5 25E1FU1RA PVC09
32 M32 1” 1-1/4” 15.0 17.0 26.2 23.7 33.9 0.2 0.6 1.6 2.0 46.0 49.7 69.5 32E1FU1RA PVC11
40 M40 1-1/4” 1-1/2” 15.0 22.0 32.1 27.9 40.4 0.2 0.8 1.6 2.0 55.0 59.4 78.0 40E1FU1RA PVC15
50S M50 1-1/2” 2” 15.0 29.5 38.1 35.2 46.7 0.2 0.8 2.0 2.5 60.0 64.8 75.5 50SE1FU1RA PVC18
50 M50 2” 2-1/2” 15.0 35.6 44.0 40.4 53.1 0.3 0.8 2.0 2.5 70.0 75.6 80.5 50E1FU1RA PVC21
63S M63 2” 2-1/2” 15.0 40.1 49.9 45.6 59.4 0.3 0.8 2.0 2.5 75.0 81.0 91.5 63SE1FU1RA PVC23
63 M63 2-1/2” 3” 15.0 47.2 55.9 54.6 65.9 0.3 0.8 2.0 2.5 80.0 86.4 92.0 63E1FU1RA PVC25
75S M75 2-1/2” 3” 15.0 52.8 61.9 59.0 72.1 0.3 0.8 2.0 2.5 89.0 96.1 99.0 75SE1FU1RA PVC28
75 M75 3” 3-1/2” 15.0 59.1 67.9 66.7 78.5 0.3 0.8 2.5 3.0 99.0 106.9 102.0 75E1FU1RA PVC30
90 M90 3” 3-1/2” 24.0 66.6 79.9 76.2 90.4 0.4 0.8 3.0 3.5 114.0 123.1 120.0 90E1FU1RA PVC32
100 M100 - - 24.0 76.0 90.9 86.1 101.5 0.4 0.8 3.15 4.0 123.0 132.8 148.0 100E1FU1RA LSF33
115 M115 - - 24.0 86.0 97.9 101.5 110.3 0.4 0.8 3.15 4.0 133.4 144.1 169.0 115E1FU1RA LSF34
130 M130 - - 24.0 97.0 114.9 114.2 123.3 0.4 0.8 3.15 4.0 146.0 157.8 183.0 130E1FU1RA LSF35
Dimensions are displayed in millimeters unless otherwise stated
TECHNICAL DATA
CABLE GLAND TYPE : E** Family of Glands
INGRESS PROTECTION : IP66, IP67, IP68
PROCESS CONTROL SYSTEM : BS EN ISO 9001
: ISO / IEC 80079-34:2011
HAZARDOUS AREA CLASSIFICATION
ATEX CERTIFICATION No : SIRA 06ATEX1097X & SIRA 07ATEX4326X
ATEX CERTIFICATION CODE : II 2 GD Ex d IIC / Ex e IIC / Ex nR II / Ex tD A21 IP66
IEC Ex CERTIFICATION No : IEC Ex SIR.06.0043X
IEC Ex CERTIFICATION CODE : Ex d IIC / Ex e IIC / Ex nR II / Ex tD A21 IP66
CSA CERTIFICATION No : 02.1310517
CSA CERTIFICATION CODE : Ex d IIC / Ex e II
INSTALLATION INSTRUCTIONS
Installation should only be performed by a competent person using the correct tools. Spanners should be used for tightening. Read all instructions
before beginning installation.
SPECIAL CONDITIONS FOR SAFE USE
For ATEX & IEC Ex certification:
1. The E type glands shall only be used where temperatures at the point of entry is between -60°C and +130°C.
2. E type glands used for terminating braided cables are only suitable for fixed installations. Cables must be clamped to prevent pulling or twisting.
3. An entry thread seal may be need to maintain the IP rating of the enclosure to which the E type gland is attached.
FOR CSA Certification:
1. These glands are not suitable for use with flameproof enclosures installed in Group IIC atmospheres which have a volume greater than 2000 cc (2
Litre).
2. These glands are for use with Certified Marine Shipboard metal braided cables constructed in according to CSA Std. 245 and
IEEE45/IEC600092-353 Standards, or Certified equivalent), for use on Shipboards and Offshore Rigs/Platfords only
ACCESSORIES
The following accessories are available from CMP Products, as optional extras, to assist with fixing, sealing and earthing :-
Locknut | Earth Tag | Serrated Washer | Entry Thread (I.P.) Sealing Washer | Shroud

Summary of content (2 pages)