Cable Gland Selection Table
CABLE GLAND
CABLE GLAND
TYPES
TYPES
CWe & CXe
CWe & CXe
Cable
Gland
S
ize
Entry
T
hread
Min
Thread
L
ength
Cable
Bedding
D
iameter
Overall
Cable
D
iameter
CWe
A
rmour
Wire
Diameter
CXe Braid
Wire
D
iameter
A
cross
Flats
A
cross
Corners
Protrusion
L
ength
CWe Ordering
Reference
(
Brass Metric)
CXe Ordering
Reference
(
Brass Metric)
PVC
Shroud
R
ef*
C
able
Gland
W
eight
(Kgs)
M
ax
M
in
M
ax
M
in
M
ax
M
in
M
ax
M
ax
M
ax
20S/16 M20 10.0 8.7 6.1 11.5 0.9 1.0 0.15 0.5 24.0 25.9 43.0 20S16CWe1RA 20S16CXe1RA PVC04 0.118
20S M20 10.0 11.7 9.5 15.9 0.9 1.25 0.15 0.5 24.0 25.9 43.0 20SCWe1RA 20SCXe1RA PVC04 0.118
20 M20 10.0 14.0 12.5 20.9 0.9 1.25 0.2 0.5 30.5 32.9 50.0 20CWe1RA 20CXe1RA PVC06 0.159
25S M25 10.0 20.0 14.0 22.0 1.25 1.6 0.2 0.6 36.0 38.9 55.0 25SCWe1RA 25SCXe1RA PVC09 0.228
25 M25 10.0 20.0 18.2 26.2 1.25 1.6 0.2 0.6 36.0 38.9 55.0 25CWe1RA 25CXe1RA PVC09 0.228
32 M32 10.0 26.3 23.7 33.9 1.6 2.0 0.2 0.6 46.0 49.7 58.0 32CWe1RA 32CXe1RA PVC11 0.362
40 M40 15.0 32.2 27.9 40.4 1.6 2.0 0.2 0.8 55.0 59.4 55.0 40CWe1RA 40CXe1RA PVC15 0.520
50S M50 15.0 38.2 35.2 46.7 2.0 2.5 0.2 0.8 60.0 64.8 56.0 50SCWe1RA 50SCXe1RA PVC18 0.579
50 M50 15.0 44.1 40.4 53.1 2.0 2.5 0.3 0.8 70.1 75.7 70.0 50CWe1RA 50CXe1RA PVC21 0.601
63S M63 15.0 50.0 45.6 59.4 2.0 2.5 0.3 0.8 75.0 81.0 70.0 63SCWe1RA 63SCXe1RA PVC23 1.054
63 M63 15.0 56.0 54.6 65.9 2.0 2.5 0.3 0.8 80.0 86.4 80.0 63CWe1RA 63CXe1RA PVC25 1.200
75S M75 15.0 62.0 59.0 72.1 2.0 2.5 0.3 0.8 90.0 97.2 81.1 75SCWe1RA 75SCXe1RA PVC28 1.779
75 M75 15.0 68.0 66.7 78.5 2.5 3.0 0.3 0.8 100.0 108.0 96.0 75CWe1RA 75CXe1RA PVC30 2.370
90 M90 15.0 8.0. 76.2 90.4 3.0 3.5 0.4 0.8 114.0 123.1 120.0 90CWe1RA 90CXe1RA PVC32 3.515
100 M100 15.0 91.0 86.1 101.5 3.15 4.0 0.4 0.8 123.0 132.8 140.0 100CWe1RA 100CXe1RA 150/50HST 4.100
115 M115 15.0 98.0 101.5 110.3 3.15 4.0 0.4 0.8 133.4 144.1 160.0 115CWe1RA 115CXe1RA 180/60HST 4.600
130 M130 15.0 115.0 114.2 123.3 3.15 4.0 0.4 0.8 146.1 157.8 169.0 130CWe1RA 130CXe1RA 180/60HST 5.200
Dimensions are displayed in millimetres unless otherwise stated
CWe = SWA armour
CXe = Braid, Tape, etc armour
NOTE: *CMP SOLO LSF Halogen Free Shrouds also available on request. + Alternative armour clamping range available for non-standard armour sizes. Marine Approvals
including Lloyds & ABS are also available from CMP Products.
Logo’s shown for illustration purposes only. Please check certification for details
0518
Notified Body: Sira Certification Service, Rake Lane, Chester CH4 9JN, England.
I, the undersigned, hereby declare that the equipment referred to herein conforms to the requirements of the ATEXT Directive 94/9/EC and the
following standards:-
EN60079-0:2006, EN60079-1:2007, EN60079-7:2007, BS 6121:1989, EN50262:1998 (Amd 2001), EN61241-0:2004, EN61241-1:2004
Dr Geof Mood - Technical Director - (Authorised Person)
TECHNICAL DATA
CABLE GLAND TYPE : CWe, CXe
INGRESS PROTECTION : IP66, IP67
DESIGN STANDARDS : BS6121:1989, EN50262
PROCESS CONTROL SYSTEM : BS EN ISO 9001
: ISO/IEC 80079-34:2011
HAZARDOUS AREA CLASSIFICATION
ATEX CERTIFICATION No : SIRA 06ATEX1097X
ATEX CERTIFICATION CODE : II 2 GD, Ex tD A21 IP66
IEC Ex CERTIFICATION No : IECEx SIR 06.0042X
IEC Ex CERTIFICATION CODE : Ex e II, Ex tD A21 IP66
INSTALLATION INSTRUCTIONS
Installation should only be performed by a competent person using the correct tools. Spanners should be used for tightening. Read all instructions
before beginning installation.
SPECIAL CONDITIONS FOR SAFE USE
1. The CWe / CXe cable glands shall only be used on enclosures where the temperature, at the point of mounting, is in the range -60°C to +130°C.
2. The entry component threads may need additional sealing to maintain the ingress protection rating applicable to the equipment to which it is
attached.
3. Cables must be clamped to prevent pulling or twisting.
ACCESSORIES
The following accessories are available from CMP Products, as optional extras, to assist with fixing, sealing and earthing :-
Locknut | Earth Tag | Serrated Washer | Entry Thread (I.P.) Sealing Washer | Shroud *