User guide
ASSEMBLY FITTING INSTRUCTIONS
FOR INSTALLATION FOR A2 CABLE
GLAND
CABLE GLAND FOR USE WITH UNARMOURED AND BRAID ARMOURED CABLES
CMP Document No. FI436 Issue 1 07/11
Registered Office: Glasshouse Street • St. Peters • Newcastle upon Tyne • NE6 1BS
Tel: +44 191 265 7411 • Fax: +44 191 265 0581
E-Mail: cmp@cmp-products.co.uk • Web: www.cmp-products.com
Company Number:
DUBAI • HOUSTON • NEWCASTLE • SINGAPORE • SHANGHAI • PUSAN • PERTH
www.cmp-products.com
Cable Gland
Size
Entry Threads
Min Thread
Length
Diameter of Cable
Across
Flats
Across
Corners
Nominal
Protrusio
n Length
Ordering Reference
(Brass Metric)
PVC Shroud
Ref*
Cable Gland
Weight (Kgs)
Standard Option
Metric NPT NPT Min Max Max Max
16 M16 1/2” 3/4” 15.0 3.2 8.1 22.0 23.8 18.0 16A21RA PVC02 0.051
20S/16 M20 1/2” 3/4” 15.0 3.2 8.7 24.0 25.9 21.0 20S16A21RA PVC04 0.054
20S M20 1/2” 3/4” 15.0 6.1 11.7 24.0 25.9 21.0 20SA21RA PVC04 0.054
20 M20 1/2” 3/4” 15.0 6.5 14.0 27.0 29.2 24.0 20A21RA PVC05 0.059
25 M25 3/4” 1” 15.0 11.1 20.0 36.0 38.9 26.0 25A21RA PVC09 0.112
32 M32 1” 1-1/4” 15.0 17.0 26.3 41.0 44.3 27.0 32A21RA PVC10 0.128
40 M40 1-1/4” 1-1/2” 15.0 23.5 32.2 50.0 54.0 28.0 40A21RA PVC13 0.168
50S M50 1-1/2” 2” 15.0 31.0 38.2 55.0 59.4 29.0 50SA21RA PVC14 0.224
50 M50 2” 2-1/2” 15.0 35.6 44.1 60.0 64.8 30.0 50A21RA PVC17 0.231
63S M63 2” 2-1/2” 15.0 41.5 50.0 70.0 75.6 30.0 63SA21RA PVC20 0.360
63 M63 2-1/2” 3” 15.0 47.2 56.0 75.0 81.0 30.0 63A21RA PVC22 0.344
75S M75 2-1/2” 3” 15.0 54.0 62.0 79.0 85.3 32.0 75SA21RA PVC24 0.466
75 M75 3” 3-1/2” 15.0 61.1 68.0 84.0 90.7 32.0 75A21RA PVC26 0.395
90 M90 3” 3-1/2” 15.0 61.6 80.0 108.0 116.6 44.0 90A21RA PVC31 1.346
100 M100 4” - 15.0 76.0 91.0 122.0 131.8 48.0 100A21RA 150/50HST 1.575
115 M115 - - 15.0 86.0 98.0 138.0 149.0 55.0 115A21RA 180/60HST 2.322
130 M130 - - 15.0 97.0 115.0 154.0 166.3 62.0 130A21RA 180/60HST 3.400
All dimensions in millimeters
Cable Gland Selection Table
CMP PRODUCTS
CABLE
CABLE
GLAND
GLAND
TYPE
TYPE
A2
A2
NOTE: *CMP SOLO LSF Halogen Free Shrouds also available on request.
TECHNICAL DATA
CABLE GLAND TYPE : A2
INGRESS PROTECTION : IP66, NEMA 4X
PROCESS CONTROL SYSTEM : BS EN ISO 9001
CLASSIFICATION
CSA CERTIFICATION No : 1211841
CSA CERTIFICATION CODE : CSA Enclosure Type 4X
INSTALLATION INSTRUCTIONS
Installation should only be performed by a competent person using the correct tools. Read all instructions before beginning installation.
ACCESSORIES
The following accessories are available from CMP Products, as optional extras, to assist with fixing, sealing and earthing :-
Locknut | Earth Tag | Serrated Washer | Entry Thread (I.P.) Sealing Washer | Shroud*