mAI085MB Actuator Interface Technical Manual Document No. 10856 Revision B July 2007 1997-98-99, 2000 CMC Industrial Electronics Ltd. Distributive Intelligence CMC INDUSTRIAL ELECTRONICS LTD Phone: (604) 421-4425 Toll-Free: (888) 421-4425 Fax: (604) 421-7734 info@cmciel.com www.cmciel.
mAI085-MB Actuator Interface Technical Manual /i Table of Contents 1. 2. 3. Overview..............................................................................................................................1 Description of the Keypad and Indicators.............................................................................3 External Connections...........................................................................................................5 3.1 Power and Communications .....................
mAI085-MB Actuator Interface Technical Manual /ii Table of Figures Figure 1 - Keypad and Indicators ................................................................................................3 Figure 2 - Terminal Blocks and Connectors ................................................................................5 Figure 3 - Recommended Network and Power Connections.......................................................6 Figure 4 - Extended Data Network ...............................................
mAI085-MB Actuator Interface Technical Manual /1 1. Overview The mAI085-MB Actuator Interface is an interface between the control room operator and a network of Actuator Controllers. The interface is capable of controlling up to 100 actuators, either on a single network of up to 31 controllers or through a series of network drops utilizing RS485 repeaters. The interface allows for the pre-setting of setpoints for each of the actuators. An open key opens all of the actuators to their preset setpoints.
mAI085-MB Actuator Interface Technical Manual /2 This page intentionally left blank Distributive Intelligence CMC INDUSTRIAL ELECTRONICS LTD
mAI085-MB Actuator Interface Technical Manual /3 2. Description of the Keypad and Indicators CMC INDUSTRIAL ELECTRONICS 12 1 11 OL IDL POS 2 FLT MOV 10 SCAN OPN CLS 3 EMP PV 9 SV 4 8 5 OPEN CLOSE CLEAR SET ACTUATOR INTERFACE 7 6 Figure 1 - Keypad and Indicators ID Label Description of Operation 1 Upper Display Displays the name of the selected actuator. 2 Upper UP / DOWN Selects which actuator to view.
mAI085-MB Actuator Interface Technical Manual /4 ID Label Description of Operation 7 Clear key and lamp Clears all actuator setpoints. First press illuminates the lamp, the second press clears the setpoints and turns off the lamp. The lamp will turn off automatically after 10 seconds if the key is not pressed the second time and the setpoints will not be cleared.
mAI085-MB Actuator Interface Technical Manual /5 3. External Connections 1 2 3 4 5 7 6 8 9 13 10 V- D_L SH D_H V+ V- G V+ 11 12 Figure 2 - Terminal Blocks and Connectors ID Label Description 1 Output 1 Contact will close if in open mode or to start the conveying system. Maximum load 1A @24VDC, 0.5A@120VAC 2 Output 2 Contact will close if in close mode or to stop the conveying system. Maximum load 1A @24VDC, 0.5A@120VAC 3 Output 3 Contact will close if all setpoints are at zero.
mAI085-MB Actuator Interface Technical Manual /6 ID Label Description 9 Input Common Common connection for inputs. Inputs accept 8-32VDC of either polarity, maximum load is 20mA. 10 Modbus Port Modbus network port - see Appendix for connections details, wired DCE 11 Input Power Terminal V+ G V- 22 -26 VDC @ 2.0A Earth Ground VDC Common 12 Output Power and Network Connections V+ D_H SH D_L V- 24 VDC fused at 1.
mAI085-MB Actuator Interface Technical Manual /7 3.2 Optional Extended Data Network CMC INDUSTRIAL ELECTRONICS OL IDL POS FLT MOV 24VDC 1.
mAI085-MB Actuator Interface Technical Manual /8 This page intentionally left blank Distributive Intelligence CMC INDUSTRIAL ELECTRONICS LTD
mAI085-MB Actuator Interface Technical Manual /9 4. Using the Interface The controller has an easy to use keyboard for selecting and controlling the connected actuators. 4.1 Selecting an Actuator Controller Use the upper up or down keys to select the actuator. The right keys move between the actuator one at a time. The left keys skip actuators at a time. The upper display indicates which actuator is selected. The SCAN key allows the viewing of all connected actuators at one second intervals.
mAI085-MB Actuator Interface Technical Manual /10 4.5 Clearing the Setpoints The CLEAR key allows the clearing of all actuator setpoints. The first press of the CLEAR key illuminates the CLEAR lamp. The second press of the key clears all actuator setpoints to 0.
mAI085-MB Actuator Interface Technical Manual /11 5. Configuration The mAI085-MB Actuator Interface is configured using a menu driven interface. The operator keyboard changes function during configuration. This section will describe the configuration of the interface. The description will first define the keyboard functions, then describe the configuration menus used. 5.1 Overview of System Configuration Each actuator connected to the Interface has parameters that control its operation.
mAI085-MB Actuator Interface Technical Manual /12 Step Function Action at Interface Action at Actuator Controller 6 From the Controller Menu, use the GEt function to upload the calibrated parameters from controller 1.
mAI085-MB Actuator Interface Technical Manual /13 Step Function Action at Interface Action at Actuator Controller From the Main Menu perform a Snd function to send the previously saved parameters to the remaining controllers. no action Parameters for all active actuator controllers on the network are overwritten with values from the Interface 10. From the Controller Menu, set the iD for each of the remaining controllers.
mAI085-MB Actuator Interface Technical Manual /14 5.2 Configuration Keyboard Functions To enter configuration mode, press and hold the SCAN key for 10 seconds. The upper display will show LoC, indicating entry into configuration mode.
mAI085-MB Actuator Interface Technical Manual /15 For value entries, there is a flashing cursor indicating which digit is being advanced. The left up/down arrow keys move the cursor left and right. The right up/down arrow keys increase and decrease the value. 6 Set key Not used. 7 Clear key and lamp Not used . 8 Open / Close keys and indicators Not used. 9 Process Value Not used, off. 10 Status Indicators Not used, all off. 11 Fault Indicators Not used, all off.
mAI085-MB Actuator Interface Technical Manual /16 5.3.1 Main Menu The Main Menu allows the selection of several sub-menus and selection of the global parameter functions. All Main Menu items require YES/no responses. Display Function Response LoC Go to the local interface parameters menu. YES/no CtL Go to the configure actuator controllers menu. YES/no bUs Go to the configure ModBus RS232 interface menu.
mAI085-MB Actuator Interface Technical Manual /17 Display Function Response second YES response starts the operation. The upper display indicates the controller address and the lower display the result of the query. All addresses marked active are queried. Once complete, the lower display shows DonE. Should an active actuator controller not be found, the lower display will show FAiL. Each active address is tried 5 times.
mAI085-MB Actuator Interface Technical Manual /18 5.3.2 Local Menu The local menu allows the configuration of parameters specific to the mAI085-MB. Display Function Response oPn Selects the Open/Close mode at startup. Selecting YES will start the interface with the OPEN lamp on. Selecting no will start the interface with the CLOSE lamp on. The default value is no. YES/no oPL Selects the open relay output pulse timing. See “Controlling Conveying Systems” for details on output pulse timing.
mAI085-MB Actuator Interface Technical Manual /19 A menu selection allows the remote calibration of the field actuator controllers. This function sets the field controller into calibration mode and alerts the operator when the calibration is complete. Before this menu can be entered, the specific controller to be configured must be selected. When entering this menu the upper display will show C 0, indicating controller address 0. Use the upper arrow keys to select the controller to be configured.
mAI085-MB Actuator Interface Technical Manual /20 Display Function GEt Response Get the operational parameters from this controller. A YES response displays SUrE in the lower display. The second YES response starts the operation. Once complete, the lower display shows DonE. Should the controller not respond, the lower display will show FAiL.. YES/no ***************************** WARNING ******************************** This function will overwrite the Interface’s saved copy of the parameters.
mAI085-MB Actuator Interface Technical Manual /21 Display Function Response This function will modify the actuator controllers saved parameters. Verify that the calibration sequence completed successfully and that the actuator is operating properly before placing the field device into service. Actuator controllers that do not complete the calibration sequence revert automatically to the pre-calibration parameter table saved in the actuator controller.
mAI085-MB Actuator Interface Technical Manual /22 5.3.5 Factory Values Menu The Interface can be configured to a range of factory preset values. The menu items allow the selection of the actuator controller model, speed of actuator operation and actuator accuracy. When the save function from this menu is executed all of the controller ID’s will be reset to A1 – A100 and all of the controllers except controller 1 will be made inactive.
mAI085-MB Actuator Interface Technical Manual /23 5.3.6 Diagnostics Menu The mTI085 has a built in diagnostics system. This menu allows for the diagnosis of the input ports, communications ports and keyboard. Test connectors are required to test the communications port. Press the SETUP key to exit any of the diagnostic tests. Display Function io Response Tests the supervisory inputs and outputs. Once selected, energizing a supervisory input will close the corresponding supervisory output, i.e.
mAI085-MB Actuator Interface Technical Manual /24 This page intentionally left blank Distributive Intelligence CMC INDUSTRIAL ELECTRONICS LTD
mAI085-MB Actuator Interface Technical Manual /25 6. The Input / Output System The mAI085-MB Actuator Interface has 4 discrete inputs and 4 discrete outputs. Figure 2 and Table 2 detail the physical connections to the discrete signals. Each of the signals is described below: Name Description Input 1 Pin 1 Energizing this input will select Open mode and turn on the OPEN indicator on the front panel.
mAI085-MB Actuator Interface Technical Manual /26 Name Description Output 3 Pins 5 & 6 This output will be energized any time all of the actuator setpoints are 0. The output de-energizes whenever a non-zero setpoint is entered into any of the actuators. Output 4 Pins 7 & 8 This output is energized whenever an internal fault is detected in the mAI085-MB Actuator Interface. Possible faults are invalid parameter table (checksum verification failed during startup), corrupted firmware or damaged hardware.
mAI085-MB Actuator Interface Technical Manual /27 7. Controlling Conveying Systems The mAI085-MB Actuator Interface allows the direct control of simple conveying systems. The interface has several timers that facilitate this control. These timers in conjunction with the discrete output system control the conveying system. The following timers are used: ID Description Menu oPL Provides a pulsed output from Output 1 to start a conveying system.
mAI085-MB Actuator Interface Technical Manual /28 cPL Timer expires cDL Timer expires Actuator 3 cDL Timer expires Actuator 2 cDL Timer expires Actuator 1 cDL Timer expires Enters Closed mode Actuator 3 oDL Timer expires Actuator 2 oDL Timer expires Actuator 1 oDL Timer expires oDL Timer expires oPL Timer expires Enters Open mode Figure 6 details a typical start/stop sequence for a conveying system.
mAI085-MB Actuator Interface Technical Manual /29 8. Using the Modbus Network Interface The mAI085-MB incorporates a RTU Slave Mobus interface. This interface responds to only 3 Modbus slave commands. The commands are 3 - Read Holding Registers, 6 - Write One Holding Register and 16 - Write Multiple Holding Registers. The Modbus protocol allows a maximum of 125 Register Reads and 100 Register Writes in a single transaction. The following tables provide the register assignments for the Modbus interface.
mAI085-MB Actuator Interface Technical Manual /30 Register Function 40002 40003 40004 40005 40006 40007 ~ 40200 40201 Controller 1 Process value Controller 1 Status Controller 2 Process value Controller 2 Status Controller 3 Process value Controller 3 Status ~ Controller 100 Process value Controller 100 Status The controller process value is a 12 bit unsigned integer. The process value will occupy bits 0 11 of the process value word.
mAI085-MB Actuator Interface Technical Manual /31 8.2.2 Read-Write Registers Each controller has one register for the setpoint value. The setpoint value will occupy bits 0 11 of the setpoint value word. The factory set range of the setpoint value will be from 0 - 100, signifying 0 - 100%. Writing a setpoint to the setpoint register will cause the actuator controller to immediately position the actuator. The value in the setpoint register must change to initiate a move.
mAI085-MB Actuator Interface Technical Manual /32 7 8 9 10 11 12 13 14 15 mAI085-MB output 4, 0 = output off in open mode, 1 = yes setpoints all cleared, 1 = yes local keyboard disabled, 1 = yes always 0 RAM fault, 1 = yes mAI085-MB parameter corruption, 1 = yes mAI085-MB firmware fault, 1 = yes mAI085-MB in calibration, 1 = yes There are 4 command bits to control the interface. These command bits are active only on the 0 to 1 transition.
mAI085-MB Actuator Interface Technical Manual /33 9. Specifications Description Characteristic DC Supply Voltage 20 - 28VDC Current 2.0 @ 24VDC Supervisory Inputs Voltage 24VDC Current 20mA Supervisory Contacts Voltage 32VDC, 120VAC Current 1.0A @ 24VDC, 0.5A @ 120VAC Resistive Actuator Controller DC Supply Voltage 20 - 28VDC Current 1.5A @ 24VDC Actuator Controller Communications Standard RS485 differential Distance 500m (1640ft.
mAI085-MB Actuator Interface Technical Manual /34 This page intentionally left blank Distributive Intelligence CMC INDUSTRIAL ELECTRONICS LTD
mAI085-MB Actuator Interface Technical Manual /35 10. Appendix 1 - Editing Controller Setup Tables on a PC The mAI085 can download and upload the field actuator controller setup tables to a PC over a standard serial port. Using software supplied as part of the Windows operating system and spreadsheet software, such as Excel, the configuration tables can be conveniently edited and sorted. The download (dnl) and upload (UPL) functions are accessed from the main menu.
mAI085-MB Actuator Interface Technical Manual /36 4. Set the communications port settings as shown and then click OK. The settings are Bits per second - 9600, Data bits - 8, Parity - None, Stop bits -1, Flow control None; 5. On some computers it may be necessary to add a short delay to each transmitted character when uploading configurations to the mTI085. From the File menu in HyperTerminal, select Properties. On the next screen select the Settings tab. On the next screen click the ASCII Setup button.
mAI085-MB Actuator Interface Technical Manual /37 6. You will now be at the main HyperTerminal Screen. Select File and then Save and the screen below will appear. Click Save to save this configuration as Direct.ht. You can now open HyperTerminal from the Direct Icon anytime you require this connection. You are now ready to download the configuration file. 10.2 Downloading the Configuration to the PC 1. Select dnL from the Main Menu; 2. From HyperTerminals menu, click on Transfer and then Capture Text.
mAI085-MB Actuator Interface Technical Manual /38 4. From the HyperTerminal menu, select Transfer and then Capture Text, then Stop. You have now created a “.txt” file containing the configuration data. 5. Open Excel and select File and then Open. You will have to change the type of file to open in the highlighted dialog box as shown below. You want to open files of type “.txt”. Once you have selected file type “.txt”, select your data file and then click Open.
mAI085-MB Actuator Interface Technical Manual /39 6. Excel will display a data import dialog. The data from the mAI085MB is pre-formatted to be automatically imported into Excel. Just click Finish to import the data. 7. Adjust the width of the columns A so you can see the headings. Edit the data as required. A sample of an Excel spreadsheet is shown below. The columns correspond directly with the menu prompts from the CtL menu. There are 2 sections to the file.
mAI085-MB Actuator Interface Technical Manual /40 8. When finished, save the file as a “.txt” file. Excel will prompt you to change the type of file when you save or exit, as it defaults to the “.xls” file format. Always answer to not change format of the file. The screen sample below shows a typical dialog. Note you must click on Yes at this dialog to save your file as a “.txt” file. 10.3 Uploading the Configuration to the mAI085MB 1.
mAI085-MB Actuator Interface Technical Manual /41 3. On the mTI085 select YES, and then YES again to the SurE prompt. The lower display will show 128. Click on Open on the HyperTerminal dialog to start the transfer. The lower display will count down as the sensor data is received. 4. When the transfer is complete. The lower display will show donE. Select Sav from the Main menu of the mAI085MB to save your uploaded data.
mAI085-MB Actuator Interface Technical Manual /42 This page intentionally left blank Distributive Intelligence CMC INDUSTRIAL ELECTRONICS LTD
mAI085-MB Actuator Interface Technical Manual /43 11.
Distributive Intelligence 8 Shield Data + 24VDC Output 3 4 5 Set Open Set Close Clear Setpoints Force Closed Input Common 1 2 3 4 5 TB3 - DC Control Inputs 7 Data - 2 Fault All Setpoints Cleared In Close In Open 5 - Data Common 2 - TX Data Out 3 - RX Data In J2 - Modbus Network 5 - Data Common 7 - RTS Out 3 - TX Data Out 2 - RX Data In J1 - Controller Network Expansion and Download / Upload Port 6 1 4 3 DC Common 24VDC, 2A Input 3 2 5 Earth Ground 2 1 TB4 - Isolate
Distributive Intelligence D- Data - 24VDC Output Data + Shield Data - DC Common 24 D+ mAC185-MB Actuator Controller Shield DC Common P1 SHIELD mGP145-MB Gate Positioner 1. Data Wiring 2 or 3 pair shielded cable, up to 32 gates per network segment. 2. Force all closed permissive is a programmable option. Use 3 pair data cable if permissive is used. 3. Wire colors shown are for Belden multi-pair cabling.
mAI085-MB Actuator Interface Technical Manual /46 This page intentionally left blank Distributive Intelligence CMC INDUSTRIAL ELECTRONICS LTD