Specifications

kW Volts Phase
Amp Draw
Breaker or Fuse
Size
Copper Wire
Size Conduit Size
L1 L2 L3
36 208 1 173 173 -- 225 4/0 1-1/2″ (38 mm)
208 3 100 100 100 125 1 1-1/4″ (32 mm)
240 1 150 150 -- 200 3/0 1-1/2″ (38 mm)
240 3 86.7 86.7 86.7 125 1 1-1/4″ (32 mm)
380 3 54.7 54.7 54.7 70 4 1″ (25 mm)
480 3 43.3 43.3 43.3 60 6 3/4″ (19 mm)
600 3 34.7 34.7 34.7 50 8 1/2″ (13 mm)
39 208 1 187.5 187.5 -- 250 250 kcmil 2″ (51 mm)
208 3 108 108 108 150 1/0 1-1/4″ (32 mm)
240 1 163.5 163.5 -- 225 4/0 2″ (51 mm)
240 3 94 94 94 125 1 1-1/4″ (32 mm)
380 3 59.3 59.3 59.3 90 3 1″ (25 mm)
480 3 47 47 47 60 6 3/4″ (19 mm)
600 3 37.6 37.6 37.6 50 8 1/2″ (13 mm)
40
208 3 61.6 61.6 61.6 90 3 1″ (25 mm)
40.5 208 3 112.5 112.5 112.5 150 1/0 1-1/4″ (32 mm)
240 3 97.5 97.5 97.5 125 1 1-1/4″ (32 mm)
480 3 48.8 48.8 48.8 70 41″ (25 mm)
600 3 39 39 39 50 8 3/4″ (19 mm)
45 208 3 125 125 125 175 2/0 1-1/2″ (38 mm)
240 1 188 188 -- 250 250 kcmil 2″ (51 mm)
240 3 108 108 108 150 1/0 1-1/4″ (32 mm)
380 3 68.6 68.6 68.6 90 3 1″ (25 mm)
480 3 54 54 54 70 41(25 mm)
600 3 43.4 43.4 43.4 60 6 3/4″ (19 mm)
54 208 3 150 150 150 200 3/0 2″ (51 mm)
240 3 130 130 130 175 2/0 1-1/2″ (38 mm)
380 3 82 82 82 125 1 1-1/4″ (32 mm)
480 3 65 65 65 90 31(25 mm)
600 3 52 52 52 70 41(25 mm)
57 208 3 158.4 158.4 158.4 200 3/0 2″ (51 mm)
240 3 137.3 137.3 137.3 175 2/0 1-1/2″ (38 mm)
380 3 86.7 86.7 86.7 125 1 1-1/4″ (32 mm)
480 3 68.6 68.6 68.6 90 31″ (25 mm)
600 3 54.9 54.9 54.9 70 41(25 mm)
SPECIFICATIONS
Form No. EBOOSTERM-0712
8
Circuit Breaker and Fused Disconnect Switch Sizes — 36 to 57 kW
The shaded area contains electrical information for International models only.
Wire size is based on THHN wire for branch circuit protection at .91 derate factor. Circuit breakers and fused disconnects are to
be mounted remote and wired by contractor. Sizes are based on the 2002 NECtable 310-16. Conduit size based on conductors
plus ground wire sizing per Table C1 from Appendix C.
NOTE: 250 kcmil maximum wire size for terminal block.
ELECTRIC SHOCK HAZARD: Consult a licensed electrical
contractor for proper electrical installation conforming to
local electrical codes and the National Electrical Code
(N.E.C.).
WARNING