Specifications

kW Volts Phase
Amp Draw
Breaker or Fuse
Size
Copper Wire
Size Conduit Size
L1 L2 L3
13.5 208 1 65 65 -- 90 31(25 mm)
208 1 38 38 38 50 8 1/2″ (13 mm)
240 1 56.3 56.3 -- 90 31″ (25 mm)
240 1 33 33 33 50 8 1/2″ (13 mm)
480 1 16.3 16.3 16.3 30 10 1/2″ (13 mm)
600 1 13 13 13 20 12 1/2″ (13 mm)
15 208 1 72 72 -- 90 31(25 mm)
208 3 41.7 41.7 41.7 60 6 3/4″ (19 mm)
240 1 62.5 62.5 -- 90 31″ (25 mm)
240 3 36.1 36.1 36.1 50 8 1/2″ (13 mm)
380 3 23.0 23.0 23.0 30 10 1/2″ (13 mm)
480 3 18.1 18.1 18.1 30 10 1/2″ (13 mm)
600 3 14.5 14.5 14.5 20 12 1/2″ (13 mm)
17.25 208 3 47.9 47.9 47.9 60 6 3/4″ (19 mm)
18 208 1 86.5 86.5 -- 125 1 1-1/4″ (32 mm)
240 1 75 75 -- 100 31″ (25 mm)
240 3 43.4 43.4 43.4 60 6 3/4″ (19 mm)
380 3 27.3 27.3 27.3 40 8 1/2″ (13 mm)
480 3 21.7 21.7 21.7 30 10 1/2″ (13 mm)
600 3 17 17 17 30 10 1/2″ (13 mm)
24 208 1 115.4 115.4 -- 150 1/0 1-1/4″ (32 mm)
208 3 66.7 66.7 66.7 90 31″ (25 mm)
240 1 100 100 -- 125 1 1-1/4″ (32 mm)
240 3 57.8 57.8 57.8 90 3 1-1/4″ (32 mm)
380 3 38.0 38.0 38.0 50 8 1/2″ (13 mm)
480 3 29.9 29.9 29.9 40 8 1/2″ (13 mm)
600 3 23 23 23 30 10 1/2″ (13 mm)
27 208 1 129.8 129.8 -- 175 2/0 1-1/4″ (32 mm)
208 3 75 75 75 100 31(25 mm)
240 1 112.5 112.5 -- 150 1/0 1-1/4″ (32 mm)
240 3 65 65 65 90 31(25 mm)
380 3 38.1 38.1 38.1 50 8 1/2″ (13 mm)
480 3 32.5 32.5 32.5 50 8 1/2″ (13 mm)
600 3 26 26 26 40 8 1/2″ (13 mm)
30 208 1 144 144 -- 200 3/0 1-1/2″ (38 mm)
208 3 83.3 83.3 83.3 125 1 1-1/4″ (32 mm)
240 1 125 125 -- 175 2/0 1-1/2″ (38 mm)
240 3 72.3 72.3 72.3 100 31(25 mm)
380 3 45.7 45.7 45.7 60 6 3/4″ (19 mm)
480 3 36 36 36 50 8 1/2″ (13 mm)
600 3 28.9 28.9 28.9 40 8 1/2″ (13 mm)
SPECIFICATIONS
Form No. EBOOSTERM-0712
7
Wire size is based on THHN wire for branch circuit protection at .91 derate factor. Circuit breakers and fused disconnects are to
be mounted remote and wired by contractor. Sizes are based on the 2002 NECtable 310-16. Conduit size based on conductors
plus ground wire sizing per Table C1 from Appendix C.
Only 6, 7 and 9 kW models can be field converted to single or three phase (open delta on 3 phase). Check wiring diagram supplied
with the unit when converting the phase of the unit. Larger branch circuit required than for balanced 3 phase of equal kW. Balanced
3 phase available, consult factory.
Circuit Breaker and Fused Disconnect Switch Sizes — 13.5 to 30 kW