User guide

DCM-1 User Manual v1.0
Conguration
50
Extension Ports
The Extension Ports cannot be paralleled, but this is unlikely
to be a system requirement as the use of remote line
input plates (LE-1s and BE-1s) will be limited to the Zones
in which they are located. They will thus be wired to the
Extension Ports on the DCM-1 feeding those Zones, and not
to any other.
Mic Inputs
ME-1 remote mic input plates cannot be paralleled to
multiple DCM-1s, but their use will also be limited to the
Zones where they are installed. Any ME-1s in a system
should be connected to the Mic Inputs of the DCM-1
feeding the Zones where they are located.
Zone Outputs
Each DCM-1’s Zone outputs will feed a separate set of
power ampliers for those Zones. Thus in the example
shown, DCM‑1 #1’s outputs will feed the ampliers driving
the loudspeakers located in Zones 1 to 8, while DCM-1 #2’s
outputs will feed the ampliers driving the loudspeakers
located in Zones 9 to 16.
CDR-1s
Using more than one DCM-1 in a system does not greatly
compromise the exibility of CDR‑1 network wiring.
The Installation section of this manual gives examples of
the various wiring topologies which may be adopted (see
page 19); that used in any particular installation will be
dictated by building layout and wiring convenience.
The example above shows two chains of CDR-1s – called
‘network A’ and ‘network B’ for reference, connected to two
of the CDR-1 Ports on DCM-1 #1, one to PORT A, the
other PORT B. Only one CDR-1 interconnection is needed
between multiple DCM-1s. Either of DCM-1 #1’s two
remaining ports may be used to connect the CDR network
to DCM-1 #2, and any of DCM-1 #2’s four ports may be
used. In the diagram, the second PORT A socket on DCM-1
#1 is connected to one of the PORT A sockets on DCM-1
#2. In this case, the PORT A CDR-1 termination would be
set OFF in DCM-1 #1 and ON in DCM-1 #2. The PORT
B termination would be set ON in DCM-1 #1, and the
corresponding jumper setting in DCM-1 #2 is unimportant.
It is important to recognise that the CDR-1s on each of the
two chains in this example can be anywhere in the building,
in any Zones.
So that any CDR-1 in this system is assignable to any of
the 16 Zones, the CDR-1 Zone Offset function must be
set to +8 on DCM‑1 #2. This is set in the menu system; see
page 34 for full details. With this setting made and the two
DCM-1s interconnected as shown, all CDR-1s in the system
will offer all 16 Zones in their ASSIGN ZONE function when
CDR-1 Installer Mode is activated (see page 45).
The restriction placed on CDR-1 network wiring by multiple
DCM-1s results from the necessity of using one CDR-1 Port
on DCM-1 #1 to route the network through to DCM-1 #2.
In the example shown, the building network wiring would be
limited to six chains, three on each DCM-1.
It should be recognised that neither a CDR-1 network
interconnection between multiple DCM-1s, nor the use of
CDR Offsets may be necessary at all, if a network topology
can be installed which limits the CDR-1s on any one chain
to Zones which are being controlled by a single DCM-1.
Thus in the example, if the CDR-1s in Zones 1 to 8 were
on a single chain, and those in Zones 9 to 16 on another, the
rst could be connected only to DCM‑1 #1 and the second
to DCM-1 #2, providing a simpler wiring system.
When planning the CDR-1 network, the DC power supply
capability of each DCM-1 must also be taken into account.
As each DCM‑1 can only supply sufcient current to
operate 8 CDR-1s, it may be that an external PSU(s) will be
required at some position(s) in the chain(s) when multiple
DCM-1s are being used. Although interconnecting two
DCM-1s as shown in the example permits full access to all
zones in operation, it does not mean that 16 CDR‑1s can be
powered by using two DCM-1s. If the system in the example
was connected to a single chain of 16 CDR-1s (with Port B
being ignored), an external PSU would need to be added to
the chain at the CDR-1 #9, to power the “farthest” 8
CDR-1s.
CDPM
In order for a CDPM system to access all 16 Zones, the
two DCM-1s should be interconnected as shown, with the
CDPM THRU connector of DCM-1 #1 connected to the
CDPM IN of #2. The CDPM termination in CDM-1 #1
should be set OFF, and that in DCM-1 #2 should be set ON.
See also page 24.
3rd.-party paging system
The microphone of a 3rd.-party paging system will need to
address all Zones, so it must be connected to the Paging
Mic Input of both DCM-1s. Paralleling a microphone signal
is not recommended, and a microphone splitter, of either
active or passive type, should be used as shown.
Interfacing a 3rd.‑party paging system to a 16‑zone system
will require separate connections to the Paging Access
Connectors of the two DCM-1s. The paging commands
for Zones 1 to 8 should be wired to the Paging Access
Connector of DCM-1 #1, and those for Zones 9 to 16 to
that of DCM-1 #2. The general wiring procedures described
at page 26 should be followed.
Music Mute Input
The Music Mute Inputs on the two DCM-1s can be
paralleled together, though this is not ideal. A preferred
solution, if available, is to use a separate set of emergency
system contacts for each DCM-1 making up the system.
RS232 Control
If the DCM-1s are to be controlled via RS232 by an
external control system, the two DCM-1s should be
treated independently. Connect each DCM-1’s RS232 port
to a separate RS232 port on the system controller. The
controller should be programmed to address each unit
independently.