User guide
DCM-1 User Manual v1.0
Conguration
50
Extension Ports
The Extension Ports cannot be paralleled, but this is unlikely
to be a system requirement as the use of remote line
input plates (LE-1s and BE-1s) will be limited to the Zones
in which they are located. They will thus be wired to the
Extension Ports on the DCM-1 feeding those Zones, and not
to any other.
Mic Inputs
ME-1 remote mic input plates cannot be paralleled to
multiple DCM-1s, but their use will also be limited to the
Zones where they are installed. Any ME-1s in a system
should be connected to the Mic Inputs of the DCM-1
feeding the Zones where they are located.
Zone Outputs
Each DCM-1’s Zone outputs will feed a separate set of
power ampliers for those Zones. Thus in the example
shown, DCM‑1 #1’s outputs will feed the ampliers driving
the loudspeakers located in Zones 1 to 8, while DCM-1 #2’s
outputs will feed the ampliers driving the loudspeakers
located in Zones 9 to 16.
CDR-1s
Using more than one DCM-1 in a system does not greatly
compromise the exibility of CDR‑1 network wiring.
The Installation section of this manual gives examples of
the various wiring topologies which may be adopted (see
page 19); that used in any particular installation will be
dictated by building layout and wiring convenience.
The example above shows two chains of CDR-1s – called
‘network A’ and ‘network B’ for reference, connected to two
of the CDR-1 Ports on DCM-1 #1, one to PORT A, the
other PORT B. Only one CDR-1 interconnection is needed
between multiple DCM-1s. Either of DCM-1 #1’s two
remaining ports may be used to connect the CDR network
to DCM-1 #2, and any of DCM-1 #2’s four ports may be
used. In the diagram, the second PORT A socket on DCM-1
#1 is connected to one of the PORT A sockets on DCM-1
#2. In this case, the PORT A CDR-1 termination would be
set OFF in DCM-1 #1 and ON in DCM-1 #2. The PORT
B termination would be set ON in DCM-1 #1, and the
corresponding jumper setting in DCM-1 #2 is unimportant.
It is important to recognise that the CDR-1s on each of the
two chains in this example can be anywhere in the building,
in any Zones.
So that any CDR-1 in this system is assignable to any of
the 16 Zones, the CDR-1 Zone Offset function must be
set to +8 on DCM‑1 #2. This is set in the menu system; see
page 34 for full details. With this setting made and the two
DCM-1s interconnected as shown, all CDR-1s in the system
will offer all 16 Zones in their ASSIGN ZONE function when
CDR-1 Installer Mode is activated (see page 45).
The restriction placed on CDR-1 network wiring by multiple
DCM-1s results from the necessity of using one CDR-1 Port
on DCM-1 #1 to route the network through to DCM-1 #2.
In the example shown, the building network wiring would be
limited to six chains, three on each DCM-1.
It should be recognised that neither a CDR-1 network
interconnection between multiple DCM-1s, nor the use of
CDR Offsets may be necessary at all, if a network topology
can be installed which limits the CDR-1s on any one chain
to Zones which are being controlled by a single DCM-1.
Thus in the example, if the CDR-1s in Zones 1 to 8 were
on a single chain, and those in Zones 9 to 16 on another, the
rst could be connected only to DCM‑1 #1 and the second
to DCM-1 #2, providing a simpler wiring system.
When planning the CDR-1 network, the DC power supply
capability of each DCM-1 must also be taken into account.
As each DCM‑1 can only supply sufcient current to
operate 8 CDR-1s, it may be that an external PSU(s) will be
required at some position(s) in the chain(s) when multiple
DCM-1s are being used. Although interconnecting two
DCM-1s as shown in the example permits full access to all
zones in operation, it does not mean that 16 CDR‑1s can be
powered by using two DCM-1s. If the system in the example
was connected to a single chain of 16 CDR-1s (with Port B
being ignored), an external PSU would need to be added to
the chain at the CDR-1 #9, to power the “farthest” 8
CDR-1s.
CDPM
In order for a CDPM system to access all 16 Zones, the
two DCM-1s should be interconnected as shown, with the
CDPM THRU connector of DCM-1 #1 connected to the
CDPM IN of #2. The CDPM termination in CDM-1 #1
should be set OFF, and that in DCM-1 #2 should be set ON.
See also page 24.
3rd.-party paging system
The microphone of a 3rd.-party paging system will need to
address all Zones, so it must be connected to the Paging
Mic Input of both DCM-1s. Paralleling a microphone signal
is not recommended, and a microphone splitter, of either
active or passive type, should be used as shown.
Interfacing a 3rd.‑party paging system to a 16‑zone system
will require separate connections to the Paging Access
Connectors of the two DCM-1s. The paging commands
for Zones 1 to 8 should be wired to the Paging Access
Connector of DCM-1 #1, and those for Zones 9 to 16 to
that of DCM-1 #2. The general wiring procedures described
at page 26 should be followed.
Music Mute Input
The Music Mute Inputs on the two DCM-1s can be
paralleled together, though this is not ideal. A preferred
solution, if available, is to use a separate set of emergency
system contacts for each DCM-1 making up the system.
RS232 Control
If the DCM-1s are to be controlled via RS232 by an
external control system, the two DCM-1s should be
treated independently. Connect each DCM-1’s RS232 port
to a separate RS232 port on the system controller. The
controller should be programmed to address each unit
independently.










