Technical information

TECHNICAL INFORMATION
226
C-Bus Learn Units Quick Programming Guide
1. Entering Learn Mode
Hold down a toggle key on any output unit for 10 seconds. Unit and C-Bus indicators on Output Units will flash alternatively.
Note: These two indicators may initially flash together for up
to 20 seconds before flashing alternatively.
All loads and indicators will turn off except the one pressed
which will turn on.
All indicators
on Input Units
will turn off.
2. Choosing the Electrical Load to be Controlled
Press the toggle key switches on the Output Units which turn on the desired lights. Unit and C-Bus indicators continue to flash alternatively.
The selected lights and indicators are switched on.
3. Selecting the Key Input Switches to Control the Chosen Loads
3A. Setting Input Keys as On/O Switches
Press the Key Inputs
required to control the
selected loads.
The switches required to
control the loads will be
illuminated.
Exit Learn Mode by pressing any toggle switch on a Relay Output Unit for 2 seconds. C-Bus2 will now Learn the relationship and will return to normal operation.
Units and C-Bus indicators will stop flashing.