Specifications

C-Bus Wireless Gateway (433.92 MHz) Installation Instructions
LEAR
N
button
5800WCGA
C-Bus Wireless Gateway
C-Bus Supply: 15-36Vdc, 32mA
RF Frequency: 433.92MHz
Patent Pending
This unit must be
used with CLIPSAL C-Bus system
only.
WARNING:
LEARN
Made in Australia
C-Bus
Network
Address
C-Bus
Network
Address
Figure 3 — The LEARN button is on the base of the Gateway
4.2 Connecting to a Wired Network
To connect the Gateway to a C-Bus wired Cat-5 network:
1) Plug the Gateway into the wired C-Bus network as described in
section 3.2.
2) Use the C-Bus Toolkit software to configure the wired side of the
Gateway. Note the following points,
The Unit Address of the wired near side of the Gateway
(GATEWLSN) must match the Network Address of the C-Bus
Wireless network being linked to.
The Unit Address of the wireless far side of the Gateway
(WGATE5F) must match the Network Address of the C-Bus
wired network being linked to.
After using the “Scan Network” function in the Project Manager
“Units” view, the Gateway appears as a unit on the wired C-Bus
network. You can select the Gateway in this view and use the
“Make Network” function, to create and open the connected
C-Bus Wireless network.
8