Specifications
9 of 16
5502DAL C-Bus DALI Gateway Programming Guide
© 2011 Schneider Electric. All Rights Reserved.
4.0 Messages
When a C-Bus command is sent on the C-Bus network to turn off a mapped group
address this message will be transmitted by the DALI Gateway to the appropriate
load on the DALI network. The converse is also true; a message on the DALI
network can be translated and transmitted on the C-Bus network.
For example, if a key input unit is programmed to toggle Group Address $42 (66),
then DALI_1_GROUP2 will respond. Similarly, if something on the DALI network
were to command DALI_1_GROUP2 to change, then a message to do the same
thing appears on the C-Bus network for Group Address $42 (66). So, an Off
command on the DALI 1 Network to Group 2 makes the indicator on the key input
unit turn off. Pressing the key input unit sends an On command back to the DALI
network to Group 2.
Note: The values transmitted from the DALI Gateway are not stored anywhere in
the C-Bus Network unless a C-Bus unit is programmed to that Group Address.
5.0 Setup
The hybrid systems relevant to the DALI Gateway product necessarily involve both
DALI and C-Bus programming. The following sections touch upon the requirements.
5.1 DALI Setup
Initially, the DALI system will not contain any groups until they are programmed into
the DALI units. DALI programming and commissioning software is sourced from the
manufacturer of the ballasts being used.
The default behaviour of DALI units is to respond to Broadcast On and Broadcast
Off commands. The DALI network is split into two halves: DALI 1 Network and DALI
2 Network.
The Group Addresses $60 (96) and $61 (97) correspond to DALI_1_BROADCAST
and DALI_1_OFF. These addresses turn all the loads in DALI network A On and Off,
respectively. Similarly the Group Addresses $E0 (224) and $E1 (225) correspond to
DALI_2_BROADCAST and DALI_2_OFF.
To obtain finer control of the network, individual group addresses have to be applied
to the DALI units. Although each DALI unit can contain up to 16 DALI groups, the
simplest programming option is to provide only one group per unit.
This will provide 16 distinct lighting zones. For large commercial spaces this should
be adequate.