Specifications

6 of 16
5502DAL C-Bus DALI Gateway Programming Guide
© 2011 Schneider Electric. All Rights Reserved.
Group Addresses
Within the lighting applications, group addresses are used to emulate the function
of conventional wiring. The C-Bus addressing scheme allows you to have up to 255
groups. Each group is like a lighting circuit and can be controlled separately from
any other group.
A group association is programmed into both input units (key inputs and sensors)
and output units (relays and dimmers). Any message broadcast by the input units
for that group are read by the output units that share the same group address.
Loads are switched or dimmed as appropriate.
2.2 DALI
The DALI system uses both short addresses (analogous to unit addresses)
and group addresses (very similar to the C-Bus concept) to achieve a flexible
assignment of loads to inputs.
The main differences between DALI and C-Bus are in the actual implementation of
group addresses and the nature of the commands broadcast over the DALI network.
DALI Group Addresses
The DALI units may have up to 16 group addresses each. This means that if
a unit has groups numbered 1,2,3 and 4 associated with it then it will respond
to a message addressed to group 1,2,3 or 4. Note that in a C-Bus system by
comparison, a load can only have one group address.
DALI Lighting Commands
The DALI system supports many commands that turn a load on or off, ramp it or
perform other functions. The controlled lighting ballast has a level and fade rate
programmed into it. The level and fade rate apply to any ramp command received by
the ballast, until such time as the parameters are changed by the DALI configuration
software.
The level is not stored internally in the ballast, but the fade rate and fade time are.
Also stored in the ballast are parameters like power on level and mode level. The
current level is not stored, but is sent from C-Bus with each command.
There are two fade settings. The fade ‘rate’ and fade ‘time. The 5502DAL Gateway
uses the fade time setting.
In a C-Bus system each ramp command contains instructions for the level and fade
rate. A specified dimming ballast can generate the requested fade rate or level and
repeat the operation in rapid succession, each time at a different fade rate and level.