10.0 Power Surges and Short Circuit Conditions
The 5502DAL C-Bus DALI Gateway is not directly connected to the mains, however voltage
surges applied to the AC/DC input should be avoided. Each unit incorporates transient
protection circuitry, but additional external power surge protection devices should be used to
enhance system immunity to power surges. It is strongly recommended that overvoltage
equipment such as the Clipsal 970 be installed at the switchboard.
11.0 Megger Testing
Megger testing must never be performed on the C-Bus data cabling or terminals as it may
degrade the performance of the Network.
Megger testing of mains wiring of an electrical installation that has C-Bus Units connected will
not cause any damage to C-Bus Units. Since C-Bus Units contain electronic components, the
installer should interpret megger readings with due regard to the nature of the circuit
connection.
12.0 Important Warning
The use of any non C-Bus Software in conjunction with the hardware installation without the
consent of Clipsal Integrated Systems Pty Ltd. may void any warranties applicable to the
hardware.
13.0 Standards Complied
Standard/Directive
Title
AS/NZS 3548 Limits and Methods of Measurement of Radio Interference of
Information Technology Equipment
IEC 61000-6-3 General Emission
14.0 Product Specifications
Catalogue No. 5502DAL Series
C-Bus Input Voltage
15 – 36VDC
C-Bus Current Drawn
32 mA
C-Bus Side Terminal
RJ45 Connectors (2 off)
DALI Side Terminals
Screw terminals
Max Devices Connected to
C-Bus Network
50
Operating Temperature Range
0 - 45
0
C
Operating Humidity Range
10 - 95% RH
Weight
130g
Dimensions
72 x 85 x 65 (L x W x D in millimeters)
15.0 Mechanical Specifications
All dimensions are in millimeters.
No user serviceable parts inside.