Product specifications
Intelligent Building Series C-Bus DALI Gateway Installation Instructions
Note: Clipsal Integrated Systems Pty Ltd does not manufacture DALI
units, power supplies, commissioning software or any other product
or service associated with DALI aside from the DALI Gateway itself,
as described in this Installation Instruction. Check individual DA
component requirements.
LI
6.0 C-Bus System Clock
The DALI Gateway unit incorporates a software selectable C-Bus System Clock. The System
Clock is used to synchronise data communications waveforms on a C-Bus Network. At least
one active C-Bus System Clock is required on each C-Bus Network for successful
communications. No more than three units on any C-Bus Network should have Clock circuitry
enabled, so this option should normally be disabled using the C-Bus Installation Software.
If a System Clock is required, it can be enabled from the ‘Global Tab’ on the Graphical User
Interface (GUI) for the unit.
7.0 Connection to the C-Bus Network
Installation requires connection to the
unshielded twisted pair C-Bus Network Cable.
The illustration following, shows the
recommended technique for cable termination
giving the best electrical performance. It is
required that Category 5 data cable is used,
Clipsal catalogue number 5005C305B.
RJ Pin C-Bus Connection Colour
1 Remote ON * Green/White
2 Remote ON * Green
3 C-Bus Neg (-) Orange/White
4 C-Bus Pos (+) Blue
5 C-Bus Neg (-) Blue/White
6 C-Bus Pos (+) Orange
7 Remote OFF * Brown/White
8 Remote OFF * Brown
The DALI Gateway does have Remote Override (ON/OFF) functions. If both Remote ON wires
are shorted together then it causes 5502DAL C-Bus DALI Gateway to issue a global message
"Direct Arc Power 100%" to both DALI networks. If both Remote OFF wires are shorted together
then it causes 5502DAL C-Bus DALI Gateway to issue a global message "Indirect Arc Power
OFF" to both DALI networks. Remote ON has higher priority that Remote OFF, e.g. when both
signals are activated the last command to both DALI networks will be "Direct Arc Power 100%".
© Copyright 2004 Clipsal Integrated Systems Pty Ltd. Page 5