Product specifications

Intelligent Building Series C-Bus DALI Gateway Installation Instructions
4.2 C-Bus Indicator:
This indicator shows the status of the C-Bus Network at this unit. If sufficient network
voltage and a valid C-Bus Clock signal are present then the “OK” signal will be displayed
(steady on). If a network is connected which has more current load than the power supplies
can support, this indicator will flash to show a marginal network voltage. If there is no C-Bus
Network Clock present this indicator will not light.
Indicator Status Meaning
On C-Bus Network operational
Flashing Insufficient power to support network
Off No C-Bus Clock present or insufficient power to support
network or C-Bus not connected (check terminations).
5.0 Wiring Instructions
C-Bus Network
1
7
CAT 5
C-Bus Patch Cord RJ5CB300PL
5
4
Surface Box
SMRJ88A5/1
3
6
2
8
Category 5 Cable
5005C305B
C-Bus
DALI Gateway
C-Bus
2
DALIDALI
21
Mains
DALI
Power Supply
Power Supply
DALI
DALI 1 Network
DALI 2 Network
Ballast
Ballast
Supply
Supply
Mains
Mains
Mains
Lamp
Lamp
NOTE:
The mutual twist of solid and dotted conductors of opposing coloured conductors. This
ensures a good electrical termination, with favourable common mode noise
characteristics.
A maximum of 64 DALI devices (max.) can be connected on a single DALI output
channel.
A maximum of 50 DALI Gateways device can be connected on a single C-Bus Network
A maximum torque of 1.4Nm should be applied to the mains rated screw terminals.
Each DALI network must be interconnected with a maximum total wiring of 300m.
The wire used should be mains rated with double insulation and a minimum 1.5mmsq
cross section.
Rubber bungs are supplied (3 off) for unused RJ45 connectors, to stop foreign bodies
from entering the unit. Always ensure these bungs are installed when the unit is to be
mounted inside a mains rated enclosure.
© Copyright 2004 Clipsal Integrated Systems Pty Ltd. Page 4