C-Bus DALI Gateway Installation Instructions 5502DAL REGISTERED PATENT
Intelligent Building Series C-Bus DALI Gateway Installation Instructions Table of Contents Section ................................................................................................................. Page 1.0 Product Range....................................................................................................3 2.0 Description..........................................................................................................3 3.0 Capabilities .................................
Intelligent Building Series C-Bus DALI Gateway Installation Instructions 1.0 Product Range 5502DAL C-Bus DALI Gateway 2.0 Description The 5502DAL C-Bus DALI Gateway unit is a C-Bus system support device designed to provide an isolated communications path between a C-Bus Network and two DALI Networks. For ease of installation the unit is DIN rail mounted, measuring 4M wide (1M = 17.5 +0.5/-0.0 mm). 3.
Intelligent Building Series C-Bus DALI Gateway Installation Instructions 4.2 C-Bus Indicator: This indicator shows the status of the C-Bus Network at this unit. If sufficient network voltage and a valid C-Bus Clock signal are present then the “OK” signal will be displayed (steady on). If a network is connected which has more current load than the power supplies can support, this indicator will flash to show a marginal network voltage.
Intelligent Building Series C-Bus DALI Gateway Installation Instructions Note: Clipsal Integrated Systems Pty Ltd does not manufacture DALI units, power supplies, commissioning software or any other product or service associated with DALI aside from the DALI Gateway itself, as described in this Installation Instruction. Check individual DALI component requirements. 6.0 C-Bus System Clock The DALI Gateway unit incorporates a software selectable C-Bus System Clock.
Intelligent Building Series C-Bus DALI Gateway Installation Instructions 8.0 Network Burden The DALI Gateway product incorporates a software selectable Network Burden. The Network Burden can be enabled using the C-Bus Installation Software. A Network Burden may or may not be required to ensure correct operation of the C-Bus Network. If in doubt, consult the C-Bus Calculator (Network Design Verification Software Utility) before proceeding with the hardware installation.
Intelligent Building Series 10.0 C-Bus DALI Gateway Installation Instructions Power Surges and Short Circuit Conditions The 5502DAL C-Bus DALI Gateway is not directly connected to the mains, however voltage surges applied to the AC/DC input should be avoided. Each unit incorporates transient protection circuitry, but additional external power surge protection devices should be used to enhance system immunity to power surges.
Further Information For further information about configuring this product and other C-Bus devices, please consult the documentation supplied. Further assistance can be obtained as follows: • C-Bus Manuals The 5000M/2 C-Bus Technical Manual provides a comprehensive and definitive guide to Clipsal C-Bus. Includes hardware and software specifications, product datasheets, system design and installation guides, and software overview with fully worked programming examples.