C-Bus Network Interface Installation Instructions 5500CN Series
© Copyright Clipsal Australia Pty Ltd 2008. All rights reserved. This material is copyright under Australian and international laws. Except as permitted under the relevant law, no part of this work may be reproduced by any process without prior written permission of and acknowledgement to Clipsal Australia Pty Ltd. Clipsal, C-Bus and Schedule Plus are registered trademarks and HomeGate is a trademark of Clipsal Australia Pty Ltd.
Contents 1.0 Product Range 5 2.0 Important Notes 5 3.0 4.0 Description Wiring Instructions 5 6 5.0 C-Bus Network Connection 7 6.0 Status Indicators 9 6.1 Ethernet 9 6.2 C-Bus/Unit/Comms 9 7.0 C-Bus System Clock 10 8.0 C-Bus Network Burden 10 9.0 C-Bus Power Requirements 10 10.0 Power Surges 10 11.0 Megger Testing 11 12.0 Configuration 11 13.0 12.1 C-Bus Programming 11 12.2 Ethernet Setup 11 Factory Default Ethernet Settings 15 13.
C-Bus Network Interface 4 Installation Instructions
C-Bus Network Interface 1.0 Installation Instructions Product Range 5500CN C-Bus Network Interface (with 12 V DC, 500 mA AU plug pack) E5500CN C-Bus Network Interface (no plug pack included) 2.0 • • Important Notes Both Ethernet and C-Bus connections are made via RJ45 sockets. Ensure you make each connection to the correct socket.
C-Bus Network Interface 4.0 Installation Instructions Wiring Instructions The 5500CN and E5500CN are powered by a 12 V AC or DC plug pack (supplied with the 5500CN). Power connection is non-polarised and made via screw terminals. Ethernet and C-Bus connections are made via RJ45 sockets. Ethernet may be connected to a network via a switch or hub, or directly to a PC (using a crossover cable). Refer to Figure 1 and Figure 2.
C-Bus Network Interface 5.0 Installation Instructions C-Bus Network Connection Connection to the C-Bus network is made via one of the RJ45 sockets. Use Cat-5 Unshielded Twisted Pair (UTP) C-Bus cable, and an appropriately wired RJ45 plug. Pinouts and cable conductor assignments are provided in Figure 3 and Table 1. The RJ45 sockets are internally connected. The Clipsal catalogue number for the C-Bus Cat-5 UTP cable is 5005C305B.
C-Bus Network Interface Pin Installation Instructions C-Bus Connection Colour 1 Remote ON green & white 2 Remote ON green 3 C-Bus Negative (-) orange & white 4 C-Bus Positive (+) blue 5 C-Bus Negative (-) blue & white 6 C-Bus Positive (+) orange 7 Remote OFF brown & white 8 Remote OFF brown 87654321 87654321 Table 1 — RJ45 sockets and C-Bus pinouts 8
C-Bus Network Interface Installation Instructions 6.0 Status Indicators 6.1 Ethernet The “Ethernet” indicator shows the status of the Ethernet interface. The indicator is orange when the communication link is good (flashing green with active data transfer), and red with a problematic or non-existent link. Refer to Table 2.
C-Bus Network Interface 7.0 Installation Instructions C-Bus System Clock The 5500CN Series C-Bus Network Interface (CNI) incorporates a software selectable C-Bus system clock. The system clock is used to synchronise data communication on a C-Bus network. At least one active C-Bus system clock is required on each C-Bus network for successful communication. No more than three units on a C-Bus network should have their clock enabled, so this option is normally disabled using the C-Bus Toolkit software.
C-Bus Network Interface Installation Instructions 11.0 Megger Testing Important points when megger testing an electrical installation: • • Only megger test when mains cabling is disconnected from C-Bus output units. Do not megger test the C-Bus cable. 12.0 Configuration 12.1 C-Bus Programming The 5500CN Series C-Bus Network Interface (CNI) must be programmed with a unique identification address (Unit Address).
C-Bus Network Interface Installation Instructions The PC must be configured with an IP address; either static or dynamic/automatic (if a DHCP server is connected). If you are using a network/Internet firewall, you may need to disable it temporarily. If you use the telnet or web browser configuration method, you must first use your operating system's ARP utility to assign the CNI with a temporary IP address.
C-Bus Network Interface Installation Instructions Using Telnet to Configure the CNI In the instructions below, substitute cni_ip_addr for the temporary IP address you are using with the CNI. 1) Type the following from a command prompt/terminal session, then press Enter: telnet cni_ip_addr 1 You should get a response something like "Could not connect to host" or "Connection refused".
C-Bus Network Interface Installation Instructions Using a Web Browser to Configure the CNI If your web browser is set to use a proxy server, temporarily change it to access the Internet/network directly. In the instructions below, substitute cni_ip_addr for the temporary IP address you are using with the CNI. 1) Type the following into the Address/URL field of your browser, then press Enter: http://cni_ip_addr:1 You should get a response explaining that the page cannot be displayed.
C-Bus Network Interface Installation Instructions 13.0 Factory Default Ethernet Settings 13.1 Server Configuration Parameter Setting Parameter Setting IP address 0.0.0.0 Telnet password None Gateway IP address Not set DHCP device name Not set Netmask Default 13.
C-Bus Network Interface Installation Instructions 14.0 Electrical Specifications Parameter Description Supply voltage 12 V DC or AC @ 300 mA C-Bus input voltage 15 to 36 V DC. Does not draw current from the C-Bus network.
C-Bus Network Interface Installation Instructions 15.
C-Bus Network Interface Installation Instructions 16.
C-Bus Network Interface Installation Instructions 17.0 Warranty The 5500CN Series C-Bus Network Interface carries a two-year warranty against manufacturing defects.
Technical Support and Troubleshooting For further assistance in using this product, consult your nearest Clipsal Integrated Systems (CIS) Sales Representative or Technical Support Officer. Technical Support Contact Numbers Australia 1300 722 247 (CIS Technical Support Hotline) New Zealand 0800 888 219 (CIS Technical Support Hotline) Northern Asia +852 2484 4157 (Clipsal Hong Kong) South Africa 011 314 5200 (C-Bus Technical Support) Southern Asia +603 7665 3555 Ext.