C-Bus Network Interface Installation Instructions 5500CN Series us C-B AL IPS CL et ern Eth ms Ne C us N CO S ION CT NE C-B r two om it/C Un s/ -Bu ace erf t k In
Intelligent Building Series C-Bus Network Interface Installation Instructions Table of Contents 1. 2. 3. 4. 5. 6. 7. 8. 9. 10. 11. 12. 13. 14. 15. 16. 17. Product Range ..............................................................................................................3 Description .....................................................................................................3 Capability ......................................................................................................
Intelligent Building Series C-Bus Network Interface Installation Instructions 1.0 Product Range 5500CN C-Bus Network Interface 2.0 Description The Network Interface is a C-Bus system support device designed to provide an isolated communications path between an Ethernet 10BaseT Network and a C-Bus Network. For ease of installation the unit is DIN rail mounted measuring 4M wide (1M = 17.5 +0.5/-0.0mm) 3.
Intelligent Building Series C-Bus Network Interface Installation Instructions 6.0 Network Burden The software selectable Network Burden can only be enabled on a unit with an address of 001. The Burden can be enabled from the ‘Global Tab’ within the GUI for the Network Interface, which is the same as the PC Interface Module. Caution: The GUI software is designed to prevent accidental selection of the Burden. The following steps are required to correctly enable the Network Burden from the GUI: 1.
Intelligent Building Series C-Bus Network Interface Installation Instructions 8.0 Communications Protocol Start Bits Data Bits Stop Bits Parity Baud Rate 9.0 :1 :8 :1 : None : 9600 Default settings C-Bus Side Programming Requirements This Network Interface product incorporates a C-Bus PC Interface Module for communications to the C-Bus Network. Programming of the C-Bus side of the Network Interface can be done in the same manner as programming a standard PC Interface.
Intelligent Building Series C-Bus Network Interface Installation Instructions If the local machine is the only entry, ping another IP address on your network to build a new entry in the arp table; the IP address must be a host other than the machine on which you are working. Once there is at least one additional entry in the arp table, use the following command to arp an IP address to the Network Interface. arp -s 191.12.3.77 00-20-4a-xx-xx-xx Now open a Telnet connection on port 1.
Intelligent Building Series C-Bus Network Interface Installation Instructions 14.0 Standards Complied The units have been designed to meet Australian and European standards for EMC Compliance and Safety. AS/NZS3548:1992 Limits and Methods of Measurement of Radio Interference of Information Technology Equipment IEC61000-6-3:1996 Generic Emission 15.
Intelligent Building Series C-Bus Network Interface Installation Instructions Products of Clipsal Integrated Systems Pty Ltd ACN 089 444 931 ABN 15 089 444 931 Head Office 12 Park Terrace, Bowden South Australia 5007 PO Box 103 Hindmarsh South Australia 5007 Telephone International Facsimile International Internet clipsal.com/cis E-Mail cis@clipsal.com.