Instruction manual

C-Bus By Demand 3
Training Manual 16
2.1.2CBusNetworkExtender
TheremaybeinstancesinacommercialCBus i n stallation,whereoneofthefundamentalCBus
operatingparametersisexceeded.Theseparametersmaybe:
morethan100CBusunits
morethan2AmpsofCBusCurrent
morethan1kmofCBusCAT5cable
morethen255GroupAddresses.
Itiswhenoneoftheseparametersisexceeded,thatyouwillstill
needtoextendthenetwork.By
usingaNetworkBridgetocreateanothernetwork,youwillbeabletocreatetheappearancethat
thereisonelargeCBusnetworkfortheareainquestion.Thismeansthattotheaverageperson,
itwillappearthat:
thereismorethan100CBusunits
thereismorethan2AmpsofCBuscurrent
thereismorethan1km’
sofCBusCAT5Cable.
2.1.3CBusCommandFilter
OneofthelesserknownfeaturesoftheNetworkBridgeisthefilteringcapability.Inthe
NetworkBridgeprogramminginterface,youwillfindtheparametercalled‘Connect
Applications.’
ThisparametergivesyoutheoptionsofselectingoneoftwouniqueApplicationAddressesor
AllApplicationAddresses(whichisthedefaultsetting).TheAppl
icationAddressesthatare
selected,areallowedtoberoutedthroughtheNetworkBridge.ThebenefitoffilteringCBus
commandspresentsitself,onmultiplenetwork
installations,wheremanydifferentApplication
Addressesareused.
If all Group Addresses on all Application Addresses are being routed across the Network
Bridge, then there will be a lot of CBus traffic. By filtering Applications you can minimise the
amountofCBustraffictotheGroupAddresseson1or2ApplicationAddressesonly.