Specifications

49
OUTPUT UNITS |
12 Channel Professional Dimmers
The 12 channel Professional Dimmers are designed for commercial applications such as hotels, restaurants and
oce buildings.
The dimmers are C-Bus controlled, high power, multi phase control units, compatible with a wide range of load
types, including neon. Dimming is achieved through phase control techniques creating a highly ecient range of
dimmers.
The Professional Dimmers provide on-board MCB protection and thermal load protection, and contain modular
output channel cards of various ratings, allowing customisation to suite site needs.
A maintained active output is provided on each channel for emergency lighting. Each channel card has a bypass
switch which permits direct local override of the lighting circuit. In the event of an over-temperature condition,
such as one caused by excessive load, the dimmer channel reduces the output power.
The Professional Dimmer is designed and tested for a wide range of international markets with comprehensive
EMC and electrical safety testing and is fully ROHS compliant.
PRODUCT FEATURES
Soft start load turn-on protects lamp laments.
Voltage compensation to minimise load brightness variation if the AC
supply voltage drifts.
Mounting brackets included for ease of installation.
Suitable for single or three phase track lighting applications with
optional 3 phase MCB’s and RCD’s
Filtering to reduce supply voltage signalling eects.
After mains fail, dimmer returns to previous or preset values.
Linear output load power following input control.
C-Bus network burden and network clock generator.
Emergency lighting output for each channel.
On-board MCB and/or RCD protection.
Fan free operation, reduces maintenance requirements.
Manual dimmer bypass switch on all channels.
Local C-Bus override switches on front panel.
Generous mains supply terminals and load terminals.
Channel Status indicators on front control panel.
CE (European Community) compliant
TECHNICAL INFORMATION
Load terminal standby leakage current < 10 mA leading edge
AC supply voltage 240/415 V AC
AC supply frequency 47 to 53 Hz
Number of input phases 3 Phase
1 or 2 Phase (3 Amp model)
Minimum load/channel 20 W for incandescent
Compatible Loads Incandescent and low voltage lighting.
Ensure compatible leading edge electronic transformers
are used.
Dimming technology Leading Edge 3-5A Triac
Leading Edge 10-20A Dual SCR
Soft-start ramp time 0.5 sec
Load current rise time 200 s
Power control range 1.5% to 95%
Standby AC supply current 90 mA base current
75 mA each LE Channel
Short circuit withstand strength 6 kA
Rated insulation voltage 500 V
Dielectric test voltage 2500 V
*Note for 3A model installer must connect dimmer to mains with protection rated at 20A per phase 6kA short circuit withstand strength
Contact Schneider Electric on 0870 608 8 608 for more information.