Specifications
34
INPUT UNITS |
Clock Modules
PRODUCT FEATURES
• Programmable using the C-Bus conguration software
• Programmed variables are stored in non-volatile
memory and are retained in case of loss of mains or
C-Bus power
• Reserve power backup in case of loss of C-Bus supply
• CE (European Community) compliant
CATALOGUE NUMBER DESCRIPTION
*E50312TC7 Clock module 7day vertical
E50312TC7
The clock modules are surface mounted, input units used to provide basic timing functions and convenient control of
C-Bus output units.
The clock modules are 7-day timers, featuring 42 program storage locations for event programming. Events may be
programmed up to 6 days in advance and event durations may be up to 99 days.
The clock modules are powered from the two wire C-Bus connection, they feature a rechargeable power storage that
maintains the clock for up to 24 hours, in the event of loss of the C-Bus power supply.
The clock modules also feature a daylight saving option and random check generator from 5 to 60 minutes.
67
87 sq. 23
52
E50312TC7 illustrated
TECHNICAL INFORMATION
C-Bus Supply Voltage 15-36VDC @ 18mA
Timer 7 day
Number of Channels 2
Memory Locations 42
Accuracy 2.5 sec/day @ 20˚C
Timer Resolution 1 minute
Running Reserve 24 hours (without C-Bus power)
Reserve Charge Time 2 minutes
Daylight Saving Mode Yes
Random Event Generator 5 to 60 minutes
Display Iconic LCD display, grey scale
Maximum Number of Units on 100
a Single C-Bus Network
Status Indicator Programmable
Warm Up Time 5 seconds
C-Bus Termination Screw terminals
Standard Colours White
Operating Temperature 0˚C to 45˚C
Operating Humidity 0 - 95% RH, non condensing
*Ask for availability