Specifications
C-Touch Colour Touch Screen
12.0 Programming Requirements
Unit Address
The C-Touch Colour must be programmed with a unique identification
address (Unit Address). This is accomplished using the C-Bus Toolkit
software, available from the Downloads section of the Clipsal Integrated
Systems (CIS) web site (http://www.clipsal.com/cis). C-Bus Toolkit is also
used to enable the C-Bus System Clock and burden if required.
C-Touch Colour Project
The C-Touch Colour must be configured with a software project which has
been customised for a particular C-Bus installation. Such a project is
produced using the Programming Interface for C-Bus Embedded Devices
(PICED) software. The PICED software is available from the downloads
section of the CIS web site (http://www.clipsal.com/cis). Documentation
and help files are included with the software.
Once you have produced a project using the PICED software, use the
“Export to Archive” option to create a project archive. This option is
located in the Archive section of the PICED software File menu.
The C-Touch Colour Transfer Utility software is used to transfer an
archived project to the C-Touch Colour, via Ethernet. It is included with the
PICED software, and allows you to perform various configuration functions
such as setting the time.
Section 13.0 which follows explains how to use the Transfer Utility
software to configure the C-Touch Colour with a customised project.
Both the C-Touch Colour and C-Bus Toolkit project files should be saved to
disk and kept in an archive at your premises. It is also recommended to
give a copy to the customer.
26