10.0 Power Surges and Short Circuit Conditions
The mains voltage must be limited to the range specied for any C-Bus Unit which is
mains powered. Each unit incorporates transient protection circuitry, however external
power surge protection devices should be used to enhance system immunity to power
surges. It is strongly recommended that overvoltage equipment such as the Clipsal 970
is installed at the switchboard.
11.0 Megger Testing
Megger testing of an electrical installation that has C-Bus Units connected will not cause
any damage to C-Bus Units. Since C-Bus Units contain electronic components, the installer
should interpret megger readings with due regard to the nature of the circuit connection.
Megger testing must never be performed on the C-Bus data cabling or terminals as it
may degrade the performance of the Network.
12.0 Important Notes
An Electricians' Licence is not required to install C-Touch units.
Do not connect mains to C-Touch units.
13.0 Programming Requirements
The C-Touch Control Unit must be programmed to set a unique identication (Unit
Address) and the mode of operation on the C-Bus Network. The C-Bus Installation
Software can be used to congure the:
Unit Address
Clock
Burden
14.0 C-Touch Conguration Software
C-Touch Conguration Software is provided on CD-ROM with the C-Touch Unit. To install
the software, simply insert the CD into the CD Drive of your personal computer or laptop
and follow the on-screen prompts.
The CD-ROM also contains Online Documentation. Please refer to the C-Touch
Programming Reference for further information relating to the programming of the C-Touch.
Once the conguration of a customer installation is complete, the project should be written
to a disk and provided to the customer or archived at your premises for future reference.
15.0 Important Warning
The use of any non C-Bus Software in conjunction with the hardware installation without
the written consent of Clipsal Integrated Systems may void any warranties applicable to
the hardware.