Specifications
© Copyright 2003 Clipsal Integrated Systems Pty Ltd. Page 12
Intelligent Building Series C-Touch Installation Instructions
© Copyright 2003 Clipsal Integrated Systems Pty Ltd. Page 13
Intelligent Building Series C-Touch Installation Instructions
6.0 Wiring Details
Before proceeding please note: The RJ receptacle on the
back of the C-Touch unit must not be connected to C-Bus.
The connector is for the serial connection only.
6.1 C-Bus Network Connection
Installation of C-Touch on the C-Bus Network requires connection to the
unshielded twisted pair C-Bus Network Cable. Connection should be made using
Category 5 data cable, catalogue number 5005C305B.
The C-Bus Network Connection is polarity sensitive, and is clearly marked on the
rear of the C-Touch unit. Two loop-in / loop-out, removable terminal blocks are
provided for easy installation and maintenance.
C-Bus Connection Colour C-Touch
Remote ON Green/White Not Connected
Remote ON Green Not Connected
C-Bus Neg (-) Orange/White C-Bus Neg (-)
C-Bus Pos (+) Blue C-Bus Pos (+)
C-Bus Neg (-) Blue/White C-Bus Neg (-)
C-Bus Pos (+) Orange C-Bus Pos (+)
Remote OFF Brown/White Not Connected
Remote OFF Brown Not Connected
Blue + Orange, C-Bus Pos (+)
Blue/White + Orange/White, C-Bus Neg (-)
Brown + Brown/White, Remote OFF
Green + Green/White, Remote ON