User's Manual

5
Appendix(For developers only.)
Thermostat Cluster ID
Device ID: ZCL_HA_DEVICEID_THERMOSTAT 0x0301
Endpoint: 0x01
Server Side Client Side
Mandatory
Basic (0x0000)
Identify(0x0003)
Identify(0x0003)
HVAC THERMOSTAT (0x0201)
Optional
None None
Attribute of Basic Cluster Information
Identifier Name Type Range Access Default
Mandatory
/ Optional
0x0000
ZCLVersion
Unsigned
8-bit
integer
0x00 –0xff
Read
only
0x01 M
0x0001 ApplicationVersion
Unsigned
8-bit
integer
0x00 –0xff
Read
only
0x00 O
0x0003
HWVersion
Unsigned
8-bit
integer
0x00 –0xff
Read
only
0 O
0x0004
ManufacturerName
Character
String
0 – 32 bytes
Read
only
Climax
Technology
O
0x0005
ModelIdentifier
Character
String
0 – 32 bytes
Read
only
(Model Version) O
0x0006
DateCode
Character
String
0 – 16 bytes
Read
only
O
0x0007
PowerSource
8-bit 0x00 –0xff
Read
only
M
0x0010
LocationDescription
Character
String
0 – 32 bytes
Read /
Write
O
0x0011
PhysicalEnvironment
8-bit 0x00 –0xff
Read /
Write
0x00 O
0x0012
DeviceEnabled
Boolean 0x00 –0x01
Read /
Write
0x01 M
Attribute of Identify Cluster Information
Identifier Name Type Range Access Default
Mandatory
/ Optional
0x0000
IdentifyTime
Unsigned
16-bit integer
0x000xffff
Read /
Write
0x0000 M
Attribute of Thermostat Cluster Information
Identifier Name Type Range Access Default
Mandatory
/ Optional
0x0000
LOCAL_TEMPERATURE
16-bit
0x954d –
0x7fff
Read
only
0x0000 M
0x0003
MIN_HEAT_SETPOINT_LIMIT
16-bit
0x954d –
0x7fff
Read
only
0x01F4 O
0x0004
MAX_HEAT_SETPOINT_LIMIT
16-bit
0x954d –
0x7fff
Read
only
0x0DAC O
0x0005
MIN_COOL_SETPOINT_LIMIT
16-bit
0x954d –
0x7fff
Read
only
0x01F4 O
0x0006
MAX_COOL_SETPOINT_LIMIT
16-bit
0x954d –
0x7fff
Read
only
0x0DAC O
0x0011
OCCUPIED_COOLING_SETPOINT
16-bit
Min Cool
Setpoint Limit
Max Cool
Read /
Write
0x0A28 M