Specifications

ClimateMaster works continually to improve its products. As a result, the design and specications of each product at the time of order may be changed without notice and may not be as described herein. Please contact ClimateMaster's Customer
Service Department at 1-405-745-6000 for specic information on the current design and specications. Statements and other information contained herein are not express warranties and do not form the basis of any bargain between the parties,
but are merely ClimateMaster's opinion or commendation of its products. The latest version of this document is available at climatemaster.com.
LC377 - 7
TS Series 60Hz - HFC-410A Submittal Data Eng/I-P
Revised: 17 July, 2013
Page ______ of ______
TS Series Nomenclature
A0 2 4 CG 3 0 C L T
4 5 6 7
8
91011121314
Unit Size
Return Air
Voltage
Controls
Cabinet
A = Current Revision
Revision Level
Supply Air & Motor Option
TS
1 2
TS = Tranquility
®
20
Single Stage Scroll
(Rotary: Size 006-012)
Model Type
V
3
V = Vertical Upflow
Configuration
L = Left Return
R = Right Return
0 = None
Water Circuit Options
2 = HWG (Coil Only)
6 = HWG (Coil Only) w/Auto Flow Regulator 2.5 GPM/Ton
7 = HWG (Coil Only) w/Auto Flow Regulator 3.0 GPM/Ton
8 = Auto Flow Regulator 2.5 GPM/Ton
9 = Auto Flow Regulator 3.0 GPM/Ton
S
15
S = Standard
Standard
H = Horizontal
D = Vertical Downflow
5 = Secondary Circulating Pump
Option Supply ConfigurationMotor
T
D
B
Top
Down
Back
TSV
TSD
TSH
PSC
PSC
PSC
SStraight TSH PSC
VTSV PSC Hi Static
UTSD
YTSH
ZTSH
Top
Down
Back
Straight
K TSV ECM
N TSD ECM
P TSH ECM
W TSH ECM
Top
Down
Back
Straight
PSC Hi Static
PSC Hi Static
PSC Hi Static
Heat Exchanger Options
B = Size 018 Current Revision
CXM
DXM
CXM w/LON
DXM w/LON
CXM w/MPC
DXM w/MPC
Control w/o Disconnect w/ Disconnect
C
D
L
M
N
P
A
B
E
K
R
S
Standard
ClimaDry
®
Reheat
Non Coated Air Coil Tin Plated Air Coil
Copper Cupro-Nickel Copper Cupro-Nickel
C
E
N
P
A
D
J
F
Motorized Valve
TS
UW
G = 208-230/60/1
H = 208-230/60/3
E = 265/60/1
N = 575/60/3
F = 460/60/3
Rev.: 14 Jan, 2008D
AVAILABLE
VOLTAGES
006 - E,G
009 - E,G
012 - E,G
018 - E,G
024 - E,F,G,H
030 - E,F,G,H
036 - E,F,G,H
042 - F,G,H,N
048 - F,G,H,N
060 - F,G,H,N
070 - F,G,H,N
OPTION
1
A
J
K
2
C
L
M
3
E
N
P
1” FILTER
RAIL
RANGE
ULTRA
QUIET
2” FILTER
RAIL
1” FILTER
FRAME
2” FILTER
FRAME
4
G
R
S
NO
YES
NO
YES
YES
YES
YES
YES
NO
NO
NO
NO
NO
NO
YES
YES
YES
YES
NO
NO
NO
NO
NO
NO
YES
YES
YES
YES
NO
NO
NO
NO
NO
NO
YES
YES
YES
YES
NO
NO
NO
NO
NO
NO
ClimaDry
®
reheat coil not coated
ClimaDry
®
II Option Notes:
1. Unit must have DXM control option. 460 volt unit units require a four wire power supply with neutral.
2. ClimaDry
®
II may not be combined with motorized water valve, internal secondary circulating pump, or automatic ow regulator
options.
3. Unit minimum entering air temperature while in the dehumidication, cooling, or continuous fan modes is 70ºF DB/61ºF WB.
Operation below this minimum may result in nuisance faults.
4. A thermostat with dehumidication mode or thermostat and separate humidistat/dehumidistat is required for activation and
control of ClimaDry
®
II.
5. Downow and 575 volt units are not eligible for ClimaDry
®
II