Specifications

ClimateMaster works continually to improve its products. As a result, the design and specications of each product at the time of order may be changed without notice and may not be as described herein. Please contact ClimateMaster's Customer
Service Department at 1-405-745-6000 for specic information on the current design and specications. Statements and other information contained herein are not express warranties and do not form the basis of any bargain between the parties,
but are merely ClimateMaster's opinion or commendation of its products. The latest version of this document is available at climatemaster.com.
LC377 - 67
TS Series 60Hz - HFC-410A Submittal Data Eng/I-P
Revised: 17 July, 2013
Page ______ of ______
a. space temperature
b. leaving water temperature
c. discharge air temperature
d. command of space temperature setpoint
e. cooling status
f. heating status
g. low temperature sensor alarm
h. low pressure sensor alarm
i. high pressure switch alarm
j. condensate overow alarm
k. hi/low voltage alarm
l. fan “ON/AUTO” position of space thermostat as specied above
m. unoccupied / occupied command
n. cooling command
o. heating command
p. fan “ON/AUTO” command
q. fault reset command
r. itemized fault code revealing reason for specic shutdown fault (any one of 7)
This option also provides the upgraded 75VA control transformer with load side short circuit and overload protection via a built in
circuit breaker.
Warranty:
Climate Master shall warranty equipment for a period of 12 months from start up or 18 months from shipping (which ever occurs rst).
Option: Extended 4-year compressor warranty covers compressor for a total of 5 years.
Option: Extended 4-year refrigeration circuit warranty covers coils, reversing valve, expansion valve and compressor for a total of 5 years.
Option: Extended 4-year control board warranty covers the CXM/DXM control board for a total of 5 years.
FIELD INSTALLED OPTIONS
Hose Kits:
All units shall be connected with hoses. The hoses shall be 2 feet (61cm) long, braided stainless steel; re rated hoses complete with
adapters. Only re rated hoses will be accepted.
Valves:
The following valves are available and will be shipped loose:
a. Ball valve; bronze material, standard port full ow design, FPT connections.
b. Ball valve with memory stop and PT port.
c. “Y” strainer with blowdown valve; bronze material, FPT connections.
d. Motorized water valve; slow acting, 24v, FPT connections.
Hose Kit Assemblies:
The following assemblies ship with the valves already assembled to the hose described:
a. Supply and return hoses having ball valve with PT port.
b. Supply hose having ball valve with PT port; return hose having automatic ow regulator valve with PT ports, and ball valve.
c. Supply hose having “Y” strainer with blowdown valve, and ball valve with PT port; return hose having automatic ow regulator
with PT ports, and ball valve.
d. Supply hose having “Y” strainer with blowdown valve, and ball valve with PT port;
return hose having ball valve with PT port.
Tranquility
®
20 (TS) Series 60Hz
Engineering Specications – Page 6