Specifications
ClimateMaster works continually to improve its products. As a result, the design and specications of each product at the time of order may be changed without notice and may not be as described herein. Please contact ClimateMaster's Customer
Service Department at 1-405-745-6000 for specic information on the current design and specications. Statements and other information contained herein are not express warranties and do not form the basis of any bargain between the parties,
but are merely ClimateMaster's opinion or commendation of its products. The latest version of this document is available at climatemaster.com.
Revised: 17 July, 2013
LC377 - 52
TS Series 60Hz - HFC-410A Submittal Data Eng/I-P
Page ______ of ______
Electrical Data – ECM Motor & ClimaDry
®
All TS Units with ECM Fan Motor TS Units (ECM)
TS Units with ECM Fan Motor
and ClimaDry
®
Model
Voltage
Code
Rated
Voltage
Voltage
Min/Max
Compressor
Fan
Motor
FLA
Total
Unit
FLA
Min
Circuit
Amp
Max
Fuse/
HACR
Reheat
Pump
FLA
Total
Unit
FLA
Min
Circuit
Amp
Max
Fuse/
HACR
QTY RLA LRA
018
G 208-230/60/1 197/254 1 9.0 48.0 3.9 12.9 15.2 20 0.8 13.7 16.0 20
E 265/60/1 239/292 1 8.4 40.0 3.2 11.6 13.7 20 0.7 12.3 14.4 20
024
G 208-230/60/1 197/254 1 12.8 60.0 3.9 16.7 19.9 30 0.8 17.5 20.7 30
E 265/60/1 239/292 1 10.9 58.0 3.2 14.1 16.8 25 0.7 14.8 17.5 25
H 208-230/60/3 197/254 1 8.0 55.0 3.9 11.9 13.9 20 0.8 12.7 14.7 20
F* 460/60/3* 414/506 1 4.0 22.4 3.2 7.2 8.2 15 0.7 7.9 8.9 15
030
G 208-230/60/1 197/254 1 13.5 61.0 3.9 17.4 20.8 30 0.8 18.2 21.6 35
E 265/60/1 239/292 1 10.9 58.0 3.2 14.1 16.8 25 0.7 14.8 17.5 25
H 208-230/60/3 197/254 1 8.3 63.0 3.9 12.2 14.3 20 0.8 13.0 15.1 20
F* 460/60/3* 414/506 1 4.5 27.0 3.2 7.7 8.8 15 0.7 8.4 9.5 15
036
G 208-230/60/1 197/254 1 14.7 72.5 3.9 18.6 22.3 35 0.8 19.4 23.1 35
E 265/60/1 239/292 1 12.5 61.0 3.2 15.7 18.8 30 0.7 16.4 19.5 30
H 208-230/60/3 197/254 1 10.4 63.0 3.9 14.3 16.9 25 0.8 15.1 17.7 25
F* 460/60/3* 414/506 1 4.5 32.0 3.2 7.7 8.8 15 0.7 8.4 9.5 15
042
G 208-230/60/1 197/254 1 15.4 83.0 3.9 19.3 23.2 35 0.8 20.1 24.0 35
H 208-230/60/3 197/254 1 11.5 77.0 3.9 15.4 18.3 25 0.8 16.2 19.1 30
F* 460/60/3* 414/506 1 5.1 35.0 3.2 8.3 9.6 15 0.7 9.0 10.3 15
048
G 208-230/60/1 197/254 1 20.5 109.0 6.9 27.4 32.5 50 1.07 28.5 33.6 50
H 208-230/60/3 197/254 1 14.6 91.0 6.9 21.5 25.2 35 1.07 22.6 26.2 40
F* 460/60/3* 414/506 1 7.1 46.0 6.0 13.1 14.9 20 1.07 14.2 15.9 20
060
G 208-230/60/1 197/254 1 26.9 145.0 6.9 33.8 40.5 60 1.07 34.9 41.6 60
H 208-230/60/3 197/254 1 17.6 123.0 6.9 24.5 28.9 45 1.07 25.6 30.0 45
F* 460/60/3* 414/506 1 9.6 64.0 6.0 15.6 18.0 25 1.07 16.7 19.1 25
070
G 208-230/60/1 197/254 1 30.1 158.0 6.9 37.0 44.5 70 1.07 38.1 45.6 70
H 208-230/60/3 197/254 1 20.5 155.0 6.9 27.4 32.5 50 1.07 28.5 33.6 50
F* 460/60/3* 414/506 1 9.6 75.0 6.0 15.6 18.0 25 1.07 16.7 19.1 25
* NEUTRAL CONNECTION REQUIRED! All F Voltage (460 vac) units with ECM motors/ClimaDry
®
require a four wire power supply with neutral.
ECM motors/reheat pumps are rated 265 vac and are wired between one hot leg and neutral.