All TS Units with High Static PSC Fan Motor TS (H.S. PSC) Units
TS Units with H.S. PSC Fan Motor
and ClimaDry
®
Model
Voltage
Code
Rated
Voltage
Voltage
Min/Max
Compressor
Fan
Motor
FLA
Total
Unit
FLA
Min
Circuit
Amp
Max
Fuse/
HACR
Reheat
Pump
FLA
Total
Unit
FLA
Min
Circuit
Amp
Max
Fuse/
HACR
QTY RLA LRA
018
G 208-230/60/1 197/254 1 9.0 48.0 1.1 10.1 12.4 20 0.8 10.9 13.2 20
E 265/60/1 239/292 1 8.4 40.0 0.9 9.3 11.4 15 0.7 10.0 12.1 20
024
G 208-230/60/1 197/254 1 12.8 60.0 1.4 14.2 17.4 30 0.8 15.0 18.2 30
E 265/60/1 239/292 1 10.9 58.0 1.6 12.5 15.2 25 0.7 13.2 15.9 25
H 208-230/60/3 197/254 1 8.0 55.0 1.4 9.4 11.4 15 0.8 10.2 12.2 20
F* 460/60/3* 414/506 1 4.0 22.4 0.9 4.9 5.9 15 0.7 5.6 6.6 15
030
G 208-230/60/1 197/254 1 13.5 61.0 1.8 15.3 18.7 30 0.8 16.1 19.5 30
E 265/60/1 239/292 1 10.9 58.0 2.0 12.9 15.6 25 0.7 13.6 16.3 25
H 208-230/60/3 197/254 1 8.3 63.0 1.8 10.1 12.2 20 0.8 10.9 13.0 20
F* 460/60/3* 414/506 1 4.5 27.0 1.24 5.7 6.9 15 0.7 6.4 7.6 15
036
G 208-230/60/1 197/254 1 14.7 72.5 2.0 16.7 20.4 35 0.8 17.5 21.2 35
E 265/60/1 239/292 1 12.5 61.0 2.2 14.7 17.8 30 0.7 15.4 18.5 30
H 208-230/60/3 197/254 1 10.4 63.0 2.0 12.4 15.0 25 0.8 13.2 15.8 25
F* 460/60/3* 414/506 1 4.5 32.0 1.0 5.5 6.6 15 0.7 6.2 7.3 15
042
G 208-230/60/1 197/254 1 15.4 83.0 3.0 18.4 22.3 35 0.8 19.2 23.1 35
H 208-230/60/3 197/254 1 11.5 77.0 3.0 14.5 17.4 25 0.8 15.3 18.2 25
F* 460/60/3* 414/506 1 5.1 35.0 1.7 6.8 8.1 15 0.7 7.5 8.8 15
N 575/60/3 518/633 1 4.3 31.0 1.4 5.7 6.8 15 N/A N/A N/A N/A
048
G 208-230/60/1 197/254 1 20.5 109.0 3.4 23.9 29.0 45 1.07 25.0 30.1 50
H 208-230/60/3 197/254 1 14.6 91.0 3.4 18.0 21.7 35 1.07 19.1 22.7 35
F* 460/60/3* 414/506 1 7.1 46.0 1.8 8.9 10.7 15 1.07 10.0 11.7 15
N 575/60/3 518/633 1 5.1 34.1 1.4 6.5 7.8 15 N/A N/A N/A N/A
060
G 208-230/60/1 197/254 1 26.9 145.0 5.8 32.7 39.4 60 1.07 33.8 40.5 60
H 208-230/60/3 197/254 1 17.6
123.0 5.8 23.4 27.8 45 1.07 24.5 28.9 45
F* 460/60/3* 414/506 1 9.6 64.0 2.6 12.2 14.6 20 1.07 13.3 15.7 25
N 575/60/3 518/633 1 6.1 40.0 2.3 8.4 9.9 15 N/A N/A N/A N/A
* NEUTRAL CONNECTION REQUIRED! All F Voltage (460 vac) units with ClimaDry
®
require a four wire power supply with neutral.
Reheat pump is rated 265 vac and is wired between one hot leg and neutral.