Specifications
ClimateMaster works continually to improve its products. As a result, the design and specications of each product at the time of order may be changed without notice and may not be as described herein. Please contact ClimateMaster's Customer
Service Department at 1-405-745-6000 for specic information on the current design and specications. Statements and other information contained herein are not express warranties and do not form the basis of any bargain between the parties,
but are merely ClimateMaster's opinion or commendation of its products. The latest version of this document is available at climatemaster.com.
LC377 - 45
TS Series 60Hz - HFC-410A Submittal Data Eng/I-P
Revised: 17 July, 2013
Page ______ of ______
TS - Vertical Upow – Dimensional Data
Notes:
1. While clear access to all removable panels is not required,
installer should take care to comply with all building codes
and allow adequate clearance for future eld service.
2. Front & Side access is preferred for service access. However,
all components may be serviced from the front access panel
if side access is not available.
3. Discharge ange is eld installed.
4. Condensate is 3/4” FPT PVC and is switchable from front to
side.
Legend:
CAP = Control Access Panel
BSP = Blower Service Panel
CSP = Compressor Access Panel
ASP = Alternative Service Panel
Vertical
Upow
Model
Overall Cabinet
*A
Width
B
Depth
C
Height
006 -
012
in
cm
22.4
56.8
21.6
54.9
34.5
87.6
018
in
cm
22.4
56.8
25.6
65.1
44.6
113.3
024 -
030
in
cm
22.4
56.8
25.6
65.1
48.5
123.2
036
in
cm
25.4
64.5
30.6
77.8
50.5
128.3
042 -
048
in
cm
25.4
64.5
30.6
77.8
54.5
138.4
060 -
070
in
cm
25.4
64.5
30.6
77.8
58.5
148.6
Vertical
Upow
Model
Water Connections
1 2 3 4 5
Loop
In
D
Loop
Out
E
HWG
In
F
HWG
Out
G
H
Water
Loop
FPT
HWG
FPT
006 -
012
in
cm
3.7
9.4
9.7
24.6
N/A N/A
7.4
18.7
1/2” N/A
018
in
cm
2.1
5.2
10.0
25.4
13.9
35.2
16.9
42.9
7.8
19.8
3/4” 1/2”
024 -
030
in
cm
2.1
5.2
10.0
25.4
13.9
35.2
16.9
42.9
7.8
19.8
3/4” 1/2”
036
in
cm
3.4
8.6
10.8
27.5
15.6
39.7
18.9
47.9
7.8
19.8
3/4” 1/2”
042 -
048
in
cm
3.4
8.6
10.8
27.5
15.6
39.7
18.9
47.9
7.8
19.8
1” 1/2”
060 -
070
in
cm
3.4
8.6
10.8
27.5
15.6
39.7
18.9
47.9
7.8
19.8
1” 1/2”
Vertical
Upow
Model
Electrical Knockouts
J
1/2”
K
1/2”
L
3/4”
Low
Voltage
External
Pump
Power
Supply
006 -
012
in
cm
3.8
9.5
6.3
15.9
8.8
22.2
018
in
cm
3.6
9.2
6.1
15.6
8.6
21.9
024 -
030
in
cm
3.6
9.2
6.1
15.6
8.6
21.9
036
in
cm
3.6
9.2
6.1
15.6
8.6
21.9
042 -
048
in
cm
3.6
9.2
6.1
15.6
8.6
21.9
060 -
070
in
cm
3.6
9.2
6.1
15.6
8.6
21.9
*Does not include air lter supports. Add 2” (5.1cm)
when a 1” (25.4mm) lter is used, add 3” (7.6cm) when
a 2” (50.8mm) lter is used.
Recommended Minimum Installation Clearances for Vertical Units*
1”
Back of unit
Side opposite return air
6” Front if hard piped
Return Air Side
1”
Ducted return
- ‡ Add for duct width
- † Add 2” for 1” lter frame/rail or 3” for 2” lter frame/rail
Free (open) return - calculate required dimension for a maximum
velocity of 600 fpm
*Field installed accessories (hoses, air cleaners, etc.) may require additional space.
Air Coil Side
Front
‡
†
1”
1”
1”
6”