Service manual
41
climatemaster.com
Tranquility
®
22 Digital (TZ) Series IOM - 60Hz HFC-410A
Rev.: 17 Jan., 2013B
Unit Operating Conditions
Table 11: Water Temperature Change Through
Heat Exchanger
9 - 12
20 - 26
4 - 8
10 - 17
Antifreeze Type
Antifreeze
%
Cooling Heating
WPD
Corr. Fct.
EWT 30°F
EWT 90°F EWT 30°F
Total Cap Sens Cap Power Htg Cap Power
Water
0 1.000 1.000 1.000 1.000 1.000 1.000
Propylene Glycol
5 0.995 0.995 1.003 0.989 0.997 1.070
15 0.986 0.986 1.009 0.968 0.990 1.210
25 0.978 0.978 1.014 0.947 0.983 1.360
Methanol
5 0.997 0.997 1.002 0.989 0.997 1.070
15 0.990 0.990 1.007 0.968 0.990 1.160
25 0.982 0.982 1.012 0.949 0.984 1.220
Ethanol
5 0.998 0.998 1.002 0.981 0.994 1.140
15 0.994 0.994 1.005 0.944 0.983 1.300
25 0.986 0.986 1.009 0.917 0.974 1.360
Ethylene Glycol
5 0.998 0.998 1.002 0.993 0.998 1.040
15 0.994 0.994 1.004 0.980 0.994 1.120
25 0.988 0.988 1.008 0.966 0.990 1.200
Table 12: Antifreeze Correction
Model GPM
Pressure Drop (psi)
30°F* 50°F 70°F 90°F
024
Rev B
2.5
3.0
3.8
4.5
6.0
0.8
1.2
1.8
2.7
3.9
0.3
0.6
1.1
1.6
2.8
0.2
0.5
0.9
1.2
2.2
0.2
0.5
0.8
1.2
2.0
030
3.0
3.8
4.5
6.0
7.5
1.7
2.3
2.7
3.8
5.1
0.9
1.2
1.6
2.4
3.5
0.8
1.1
1.4
2.2
3.1
0.8
1.1
1.4
2.1
2.9
036
Rev B
4.0
6.0
6.8
8.0
9.0
0.6
1.8
2.3
3.2
4.0
0.1
1.0
1.5
2.2
2.9
0.1
0.7
1.1
1.8
2.4
0.1
0.7
1.1
1.7
2.3
042
3.8
5.3
7.5
7.9
10.5
1.7
2.7
4.5
4.8
7.4
1.0
1.8
3.1
3.4
5.4
0.9
1.6
2.8
3.1
4.9
0.9
1.5
2.6
2.9
4.7
048
4.5
6.0
6.8
9.0
12.0
1.4
2.0
2.5
4.0
6.5
1.1
1.7
2.1
3.4
5.5
0.9
1.4
1.8
3.0
4.9
0.8
1.3
1.7
2.7
4.5
060
Rev B
6.0
7.5
9.0
12.0
15.0
1.2
2.1
3.1
5.4
8.1
0.9
1.7
2.5
4.6
7.0
0.8
1.5
2.3
4.2
6.4
0.8
1.4
2.2
3.9
6.1
* Based on 15% methanol antifreeze solution
Table 10: TZ Coax Water Pressure Drop