Specifications

TY Series 60Hz - HFC-410A Submittal Data Eng/I-P
ClimateMaster works continually to improve its products. As a result, the design and speci cations of each product at the time of order may be changed without notice and may not be as described herein. Please contact ClimateMaster's Customer
Service Department at 1-405-745-6000 for speci c information on the current design and speci cations. Statements and other information contained herein are not express warranties and do not form the basis of any bargain between the parties,
but are merely ClimateMaster's opinion or commendation of its products. The latest version of this document is available at climatemaster.com.
Page ______ of ______Revised: 30 January, 2015LC992 - 35
Electrical Data
Standard Units
Model
Voltage
Code
Voltage
Min/Max
Voltage
Compressor Fan Motor
FLA
Total Unit
FLA
Min Circ
Amp
Max Fuse/
HACR
RLA LRA Qty
024
G 208/230/60/1 197/252 11.7 58.3 1 3.9 15.6 18.5 30
E 265/60/1 239/292 9.1 54.0 1 3.2 12.3 14.6 20
H 208/230/60/3 197/252 6.5 55.4 1 3.9 10.4 12.0 15
F* 460/60/3* 414/506 3.5 28.0 1 3.2 6.7 7.6 15
030
G 208/230/60/1 197/252 13.1 73.0 1 3.9 17.0 20.3 30
E 265/60/1 239/292 10.2 60.0 1 3.2 13.4 16.0 25
H 208/230/60/3 197/252 8.7 58.0 1 3.9 12.6 14.8 20
F* 460/60/3* 414/506 4.3 28.0 1 3.2 7.5 8.6 15
036
G 208/230/60/1 197/252 15.3 83.0 1 3.9 19.2 23.0 35
E 265/60/1 239/292 13.0 72.0 1 3.2 16.2 19.5 30
H 208/230/60/3 197/252 11.6 73.0 1 3.9 15.5 18.4 30
F* 460/60/3* 414/506 5.7 38.0 1 3.2 8.9 10.3 15
042
G 208/230/60/1 197/252 17.9 96.0 1 5.2 23.1 27.6 45
H 208/230/60/3 197/252 14.2 88.0 1 5.2 19.4 23.0 35
F* 460/60/3* 414/506 6.2 44.0 1 4.7 10.9 12.5 15
048
G 208/230/60/1 197/252 21.2 104.0 1 5.2 26.4 31.7 50
E 265/60/1 239/292 16.0 109.7 1 4.7 20.7 24.7 40
H 208/230/60/3 197/252 14.0 83.1 1 5.2 19.2 22.7 35
F* 460/60/3* 414/506 6.4 41.0 1 4.7 11.1 12.7 15
060
G 208/230/60/1 197/252 27.1 152.9 1 6.9 34.0 40.8 60
E 265/60/1 239/292 22.4 130.0 1 6.0 28.4 34.0 50
H 208/230/60/3 197/252 16.5 110.0 1 6.9 23.4 27.5 40
F* 460/60/3* 414/506 7.2 52.0 1 6.0 13.2 15.0 20
HACR circuit breaker in USA only
Wire length based on one way measurement with 2% voltage drop
Wire size based on 60°C copper conductor
All fuses Class RK-5
* NEUTRAL CONNECTION REQUIRED! All F Voltage (460 vac) units require a four wire power supply with neutral. ECM motor is rated
265 vac and is wired between one hot leg and neutral.