Page ______ of ______Revised: 30 January, 2015LC992 - 26
Antifreeze Correction Tables
Antifreeze Correction Table
Antifreeze Type
Antifreeze
%
Cooling Heating
WPD
Corr. Fct.
EWT 30°F
EWT 90°F EWT 30°F
Total Cap Sens Cap Power Htg Cap Power
Water
0 1.000 1.000 1.000 1.000 1.000 1.000
Propylene Glycol
5 0.995 0.995 1.003 0.989 0.997 1.070
15 0.986 0.986 1.009 0.968 0.990 1.210
25 0.978 0.978 1.014 0.947 0.983 1.360
Methanol
5 0.997 0.997 1.002 0.989 0.997 1.070
15 0.990 0.990 1.007 0.968 0.990 1.160
25 0.982 0.982 1.012 0.949 0.984 1.220
Ethanol
5 0.998 0.998 1.002 0.981 0.994 1.140
15 0.994 0.994 1.005 0.944 0.983 1.300
25 0.986 0.986 1.009 0.917 0.974 1.360
Ethylene Glycol
5 0.998 0.998 1.002 0.993 0.998 1.040
15 0.994 0.994 1.004 0.980 0.994 1.120
25 0.988 0.988 1.008 0.966 0.990 1.200
N/A N/A N/A