Specifications
TY Series 60Hz - HFC-410A Submittal Data Eng/I-P
ClimateMaster works continually to improve its products. As a result, the design and specifi cations of each product at the time of order may be changed without notice and may not be as described herein. Please contact ClimateMaster's Customer
Service Department at 1-405-745-6000 for specifi c information on the current design and specifi cations. Statements and other information contained herein are not express warranties and do not form the basis of any bargain between the parties,
but are merely ClimateMaster's opinion or commendation of its products. The latest version of this document is available at climatemaster.com.
Page ______ of ______Revised: 30 January, 2015LC992 - 11
Performance Data AHRI/ASHRAE/ISO 13256-1
Model
Water Loop Heat Pump Ground Water Heat Pump Ground Loop Heat Pump
Cooling 86°F Heating 68°F Cooling 59°F Heating 50°F
Full Cool 77°F
Part Cool 68°F
Full Heat 32°F
Part Heat 41°F
Capacity
Btuh
EER
Btuh/W
Capacity
Btuh
COP
Capacity
Btuh
EER
Btuh/W
Capacity
Btuh
COP
Capacity
Btuh
EER
Btuh/W
Capacity
Btuh
COP
TY*024
Part
18,100 16.1 20,600 5.2 20,300 27.2 16,700 4.4 19,400 22.2 14,700 4.0
TY*024
Full
23,700 14.3 28,000 4.6 26,500 21.7 23,000 4.1 24,600 16.0 17,800 3.6
TY*030
Part
21,900 15.2 26,300 5.0 24,900 24.8 22,000 4.3 24,200 20.9 19,400 3.9
TY*030
Full
28,500 14.0 35,800 4.6 32,300 20.7 30,000 4.2 29,900 15.7 23,800 3.6
TY*036
Part
25,800 17.2 29,900 5.3 29,000 29.4 24,900 4.6 27,300 23.4 21,500 4.0
TY*036
Full
34,300 15.1 42,000 4.6 38,200 22.3 35,100 4.3 35,200 16.7 27,300 3.6
TY*042
Part
31,000 15.8 36,800 5.1 35,200 26.4 30,500 4.3 34,000 22.0 26,900 3.8
TY*042
Full
41,100 14.3 50,200 4.6 46,300 21.3 42,300 4.1 43,100 16.1 33,300 3.4
TY*048
Part
34,100 15.2 39,500 5.5 39,200 26.8 32,600 4.6 37,600 21.2 29,200 4.1
TY*048
Full
45,900 14.0 53,800 4.9 51,800 20.9 45,000 4.4 48,100 15.5 35,600 3.7
TY*060
Part
45,500 17.7 49,000 5.3 50,400 28.9 39,800 4.5 48,600 23.7 34,800 4.0
TY*060
Full
61,700 15.7 67,500 4.8 68,000 22.7 55,400 4.3 63,200 17.3 43,700 3.6
Cooling capacities based upon 80.6°F DB, 66.2°F WB entering air temperature
Heating capacities based upon 68°F DB, 59°F WB entering air temperature
Ground Loop Heat Pump ratings based on 15% antifreeze solution
All ratings based upon operation at lower voltage of dual voltage rated models
Model
Water Loop Heat Pump Ground Water Heat Pump Ground Loop Heat Pump
Cooling 30°C Heating 20°C Cooling 15°C Heating 10°C
Full Cool 25°C
Part Cool 20°C
Full Heat 0°C
Part Heat 5°C
Capacity
kW
EER
Btuh/W
Capacity
kW
COP
Capacity
kW
EER
Btuh/W
Capacity
kW
COP
Capacity
kW
EER
Btuh/W
Capacity
kW
COP
TY*024
Part
5.30 4.7 6.04 5.2 5.95 8.0 4.89 4.4 5.68 6.5 4.31 4.0
TY*024
Full
6.94 4.2 8.20 4.6 7.76 6.4 6.74 4.1 7.21 4.7 5.22 3.6
TY*030
Part
6.42 4.5 7.71 5.0 7.30 7.3 6.45 4.3 7.09 6.1 5.69 3.9
TY*030
Full
8.35 4.1 10.49 4.6 9.47 6.1 8.79 4.2 8.76 4.6 6.98 3.6
TY*036
Part
7.56 5.0 8.76 5.3 8.50 8.6 7.30 4.6 8.00 6.9 6.30 4.0
TY*036
Full
10.05 4.4 12.31 4.6 11.19 6.5 10.28 4.3 10.31 4.9 8.00 3.6
TY*042
Part
9.09 4.6 10.79 5.1 10.32 7.7 8.94 4.3 9.96 6.4 7.88 3.8
TY*042
Full
12.05 4.2 14.71 4.6 13.57 6.2 12.40 4.1 12.63 4.7 9.76 3.4
TY*048
Part
9.99 4.5 11.58 5.5 11.49 7.9 9.55 4.6 11.02 6.2 8.56 4.1
TY*048
Full
13.45 4.1 15.77 4.9 15.18 6.1 13.19 4.4 14.10 4.5 10.43 3.7
TY*060
Part
13.3 5.2 14.36 5.1 14.77 8.5 11.66 4.3 14.24 6.9 10.20 3.9
TY*060
Full
18.1 4.6 19.78 4.5 19.93 6.7 16.24 4.0 18.52 5.1 12.80 3.5
Cooling capacities based upon 27°C DB, 19°C WB entering air temperature
Heating capacities based upon 20°C DB, 15°C WB entering air temperature
Ground Loop Heat Pump ratings based on 15% antifreeze solution
All ratings based upon operation at lower voltage of dual voltage rated models
ASHRAE/AHRI/ISO 13256-1. English (I-P) Units
ASHRAE/AHRI/ISO 13256-1. Metric (S-I) Units