Tranquility® 22 Two-Stage (TY) Series Submittal Data Models TYH/V 024 - 060 60Hz - HFC-410A SUBMITTAL DATA - I-P UNITS Unit Designation: English Language/I-P Units Job Name: Architect: Engineer: Contractor: PERFORMANCE DATA Cooling Capacity: Btuh EER: Heating Capacity: Btuh COP: Revised: 30 January, 2015 Ambient Air Temp: °F Entering Water Temp (Clg): °F Entering Air Temp (Clg): °F Entering Water Temp (Htg): °F Entering Air Temp (Htg): °F Airflow: CFM Fan Speed or Motor/RPM/Turns: Opera
Tranquility® 22 Two-Stage (TY) Series Submittal Data Models TYH/V 024 - 060 60Hz - HFC-410A SUBMITTAL DATA - S-I UNITS Unit Designation: English Language/S-I Units Job Name: Architect: Engineer: Contractor: PERFORMANCE DATA Cooling Capacity: kW EER: Heating Capacity: kW COP: Revised: 30 January, 2015 Ambient Air Temp: °C Entering Water Temp (Clg): °C Entering Air Temp (Clg): °C Entering Water Temp (Htg): °C Entering Air Temp (Htg): °C Airflow: l/s Fan Speed or Motor/RPM/Turns: Operating
TY Series 60Hz - HFC-410A Submittal Data Eng/I-P Table of Contents Unit Features . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . iGate™ Communicating Controls . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . Selection Procedure . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . TY Series Nomenclature . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . .
TY Series 60Hz - HFC-410A Submittal Data Eng/I-P Unit Features THE TRANQUILITY® 22 TWO-STAGE (TY) SERIES The TY comes with all the reliability features the ClimateMaster Tranquility® Series is known for. They include superb efficiency ratings, quiet operation and application flexibility. Tranquility® 22 units are available in vertical upflow and horizontal configurations in capacities of 24, 30, 36, 42, 48, and 60 Mbtuh.
TY Series 60Hz - HFC-410A Submittal Data Eng/I-P Unit Features UNIT FEATURES • Sizes 024 (2 ton, 7.0 kW) through 060 (5 tons, 17.6 kW) • EarthPure® (HFC-410A) refrigerant • Copeland UltraTech™ two-stage unloading scroll compressors • ECM variable speed fan motor with soft start • DXM2 two-way communicating controller • Exceeds ASHRAE 90.
TY Series 60Hz - HFC-410A Submittal Data Eng/I-P iGate™ Communicating Controls iGate™ Information gateway to monitor, control and diagnose your system Tranquility® 22 is equipped with industry-first, iGate™ – Information Gateway – 2-way communicating system that allows users to interact with their system in plain English iGate™ makes Tranquility® Series the easiest products to install and service.
TY Series 60Hz - HFC-410A Submittal Data Eng/I-P Selection Procedure Reference Calculations Heating Cooling HE LWT = EWT GPM x 500 LAT = EAT + HC CFM x1.08 HR LWT = EWT + GPM x 500 LAT (DB) = EAT (DB) - LC = TC - SC SC CFM x1.
TY Series 60Hz - HFC-410A Submittal Data Eng/I-P Performance Data – Selection Notes For operation in the shaded area when water is used in lieu of an antifreeze solution, the LWT (Leaving Water Temperature) must be calculated. Flow must be maintained to a level such that the LWT is maintained above 40°F [4.4°C] when the JW3 jumper is not clipped (see example below). Otherwise, appropriate levels of a proper antifreeze solution should be used in systems with leaving water temperatures of 40ºF [4.
TY Series 60Hz - HFC-410A Submittal Data Eng/I-P Selection Procedure Step 1 Determine the actual heating and cooling loads at the desired dry bulb and wet bulb conditions. Example Equipment Selection For Cooling Step 2 Obtain the following design parameters: Entering water temperature, water flow rate in GPM, air flow in CFM, water flow pressure drop and design wet and dry bulb temperatures. Air flow CFM should be between 300 and 450 CFM per ton.
TY Series 60Hz - HFC-410A Submittal Data Eng/I-P TY Series Nomenclature 1 2 3 4 5 6 7 TY V 024 A G D 3 8 9 10 11 12 13 14 15 0 B L T S STANDARD SERIES S = Standard TY = Tranquility® 22 Digital SUPPLY AIR FLOW & MOTOR CONFIGURATION CONFIGURATION V = Vertical Up H = Horizontal T B S UNIT SIZE 024 030 036 042 048 060 Supply Configuration Top TYV TYH Back TYH Straight Motor ECM ECM ECM RETURN AIR FLOW CONFIGURATION L = Left Return R = Right Return V = Left Return, Stainless Steel Drain
TY Series 60Hz - HFC-410A Submittal Data Eng/I-P Performance Data AHRI/ASHRAE/ISO 13256-1 ASHRAE/AHRI/ISO 13256-1. English (I-P) Units Water Loop Heat Pump Cooling 86°F Model Ground Water Heat Pump Heating 68°F Cooling 59°F Ground Loop Heat Pump Heating 50°F Part Cool 68°F Full Heat 32°F Part Heat 41°F Capacity EER Btuh Btuh/W Capacity COP Btuh Capacity Btuh EER Btuh/W Capacity Btuh COP Capacity Btuh EER Btuh/W 18,100 16.1 20,600 5.2 20,300 27.2 16,700 4.4 19,400 22.2 14,700 4.
TY Series 60Hz - HFC-410A Submittal Data Eng/I-P Performance Data – TY H/V 024 (Part Load) 600 CFM Nominal (Rated) Airflow Cooling,600 CFM Nominal (Rated) Airflow Heating EWT °F 20 30 40 50 60 70 80 90 100 110 120 GPM WPD Performance capacities shown in thousands of Btuh COOLING - EAT 80/67°F PSI FT 4.5 7.6 17.5 2.3 2.6 3.4 HEATING - EAT 68°F TC SC kW HR EER HC kW HE LAT COP 11.2 1.17 7.3 85.3 2.8 6.0 21.2 14.7 0.69 23.5 30.7 12.5 1.18 8.5 87.3 3.1 4.
TY Series 60Hz - HFC-410A Submittal Data Eng/I-P Performance Data – TY H/V 024 (Full Load) 750 CFM Nominal (Rated) Airflow Cooling, 750 CFM Nominal (Rated) Airflow Heating EWT °F 20 30 40 50 60 70 80 90 100 110 120 GPM WPD Performance capacities shown in thousands of Btuh COOLING - EAT 80/67°F PSI FT 6.0 11.1 25.7 3.0 3.7 4.5 HEATING - EAT 68°F TC SC kW HR EER HC kW HE LAT COP 8.5 28.1 18.6 1.11 31.9 25.4 15.7 1.49 10.6 87.3 3.1 17.4 1.53 12.2 89.5 6.
TY Series 60Hz - HFC-410A Submittal Data Eng/I-P Performance Data – TY H/V 030 (Part Load) 750 CFM Nominal (Rated) Airflow Cooling, 750 CFM Nominal (Rated) Airflow Heating EWT °F 20 30 40 50 60 70 80 90 100 110 120 GPM WPD Performance capacities shown in thousands of Btuh COOLING - EAT 80/67°F PSI FT 6.0 4.4 10.2 3.0 1.6 4.5 6.0 HEATING - EAT 68°F TC SC kW HR EER HC kW HE LAT COP 3.6 27.1 17.7 0.85 30.0 31.9 15.7 1.49 10.6 87.3 3.1 17.2 1.51 12.0 89.1 2.
TY Series 60Hz - HFC-410A Submittal Data Eng/I-P Performance Data – TY H/V 030 (Full Load) 900 CFM Nominal (Rated) Airflow Cooling, 900 CFM Nominal (Rated) Airflow Heating EWT °F 20 30 40 50 60 70 80 90 100 110 120 GPM WPD Performance capacities shown in thousands of Btuh COOLING - EAT 80/67°F PSI FT 7.5 5.8 13.5 3.8 2.0 5.6 HEATING - EAT 68°F TC SC kW HR EER HC kW HE LAT COP 4.7 35.3 21.8 1.40 40.1 25.3 21.8 1.93 15.2 89.2 3.3 23.5 1.99 16.7 90.9 3.3 7.
TY Series 60Hz - HFC-410A Submittal Data Eng/I-P Performance Data – TY H/V 036 (Part Load) 950 CFM Nominal (Rated) Airflow Cooling, 950 CFM Nominal (Rated) Airflow Heating EWT °F 20 30 40 50 60 70 80 90 100 110 120 GPM WPD Performance capacities shown in thousands of Btuh COOLING - EAT 80/67°F PSI FT 6.0 4.4 10.2 3.0 1.6 4.5 HEATING - EAT 68°F TC SC kW HR EER HC kW HE LAT COP 3.6 30.7 20.8 0.97 34.0 31.5 16.9 18.6 1.69 11.1 84.4 2.9 1.71 12.8 86.1 2.5 5.
TY Series 60Hz - HFC-410A Submittal Data Eng/I-P Performance Data – TY H/V 036 (Full Load) 1150 CFM Nominal (Rated) Airflow Cooling, 1150 CFM Nominal (Rated) Airflow Heating EWT °F 20 30 40 50 60 70 80 90 100 110 120 GPM WPD Performance capacities shown in thousands of Btuh COOLING - EAT 80/67°F PSI FT 9.0 7.5 17.2 4.5 2.5 6.8 HEATING - EAT 68°F TC SC kW HR EER HC kW HE LAT COP 5.8 40.6 27.3 1.69 46.4 24.0 25.3 2.32 17.3 88.3 3.2 27.5 2.39 19.3 90.1 4.
TY Series 60Hz - HFC-410A Submittal Data Eng/I-P Performance Data – TY H/V 042 (Part Load) 1100 CFM Nominal (Rated) Airflow Cooling, 1100 CFM Nominal (Rated) Airflow Heating EWT °F GPM 20 30 40 50 60 70 80 90 100 110 120 WPD Performance capacities shown in thousands of Btuh COOLING - EAT 80/67°F PSI FT 7.5 5.1 11.9 3.8 1.6 5.6 7.5 HEATING - EAT 68°F TC SC kW HR EER HC kW HE LAT COP 3.6 38.1 28.2 1.15 42.0 33.1 19.8 2.09 12.7 84.6 2.8 22.1 2.12 14.9 86.
TY Series 60Hz - HFC-410A Submittal Data Eng/I-P Performance Data – TY H/V 042 (Full Load) 1300 CFM Nominal (Rated) Airflow Cooling, 1300 CFM Nominal (Rated) Airflow Heating EWT °F 20 30 40 50 60 70 80 90 100 110 120 GPM WPD Performance capacities shown in thousands of Btuh COOLING - EAT 80/67°F PSI FT 10.5 8.3 19.3 5.3 2.5 7.9 HEATING - EAT 68°F TC SC kW HR EER HC kW HE LAT COP 5.8 50.4 36.7 1.94 57.0 25.9 29.6 2.83 19.9 89.0 3.1 32.4 2.89 22.5 91.0 4.
TY Series 60Hz - HFC-410A Submittal Data Eng/I-P Performance Data – TY H/V 048 (Part Load) 1250 CFM Nominal (Rated) Airflow Cooling, 1250 CFM Nominal (Rated) Airflow Heating EWT °F 20 30 40 50 60 70 80 90 100 110 120 GPM WPD Performance capacities shown in thousands of Btuh COOLING - EAT 80/67°F PSI FT 9.0 5.0 11.5 4.5 1.4 6.8 HEATING - EAT 68°F TC SC kW HR EER HC kW HE LAT COP 3.3 41.6 28.3 1.37 46.3 30.4 23.1 2.18 15.6 85.0 3.1 25.3 2.20 17.8 86.7 2.
TY Series 60Hz - HFC-410A Submittal Data Eng/I-P Performance Data – TY H/V 048 (Full Load) 1500 CFM Nominal (Rated) Airflow Cooling, 1500 CFM Nominal (Rated) Airflow Heating EWT °F 20 GPM WPD COOLING - EAT 80/67°F PSI FT 12.0 7.6 17.5 6.0 2.2 30 Performance capacities shown in thousands of Btuh HEATING - EAT 68°F TC SC kW HR EER 5.2 55.7 36.8 2.32 63.6 24.0 HC kW HE LAT COP 32.4 2.88 22.6 88.0 3.3 35.2 2.93 25.1 89.6 3.5 3.6 9.0 4.3 9.9 56.2 36.8 2.21 63.
TY Series 60Hz - HFC-410A Submittal Data Eng/I-P Performance Data – TY H/V 060 (Part Load) 1600 CFM Nominal (Rated) Airflow Cooling, 1600 CFM Nominal (Rated) Airflow Heating EWT °F 20 GPM WPD COOLING - EAT 80/67°F PSI FT 12.0 11.7 27.0 6.0 3.8 30 Performance capacities shown in thousands of Btuh HEATING - EAT 68°F TC SC kW HR EER 8.8 52.3 38.4 1.53 57.6 34.1 HC kW HE LAT COP 28.9 2.88 19.0 84.7 2.9 32.0 2.91 22.1 86.5 3.2 9.0 6.6 15.1 52.0 38.2 1.46 57.
TY Series 60Hz - HFC-410A Submittal Data Eng/I-P Performance Data – TY H/V 060 (Full Load) 1900 CFM Nominal (Rated) Airflow Cooling, 1900 CFM Nominal (Rated) Airflow Heating EWT °F GPM 20 30 40 50 60 70 80 90 100 110 120 WPD Performance capacities shown in thousands of Btuh COOLING - EAT 80/67°F PSI FT 14.0 14.6 33.7 7.0 4.6 10.5 HEATING - EAT 68°F TC SC kW HR EER HC kW HE LAT COP 10.7 69.4 48.5 2.81 79.0 24.7 41.2 3.90 28.0 88.1 3.1 45.0 3.99 31.4 89.
TY Series 60Hz - HFC-410A Submittal Data Eng/I-P Part Load Performance Data – Correction Tables Air Flow Correction Table Airflow Heating % of Rated Heating Capacity 80 85 Cooling Power Heat of Extraction Total Capacity Sensible Capacity S/T Power Heat of Rejection 0.979 1.035 0.965 0.980 0.917 0.936 0.955 0.975 0.984 1.021 0.975 0.986 0.939 0.953 0.964 0.982 90 0.990 1.011 0.984 0.992 0.961 0.969 0.975 0.988 95 0.995 1.004 0.993 0.996 0.981 0.985 0.986 0.
TY Series 60Hz - HFC-410A Submittal Data Eng/I-P Full Load Performance Data – Correction Tables Air Flow Correction Table Airflow Heating Cooling % of Rated Heating Capacity Power Heat of Extraction Total Capacity Sensible Capacity S/T Power Heat of Rejection 80 0.983 1.040 0.967 0.976 0.919 0.941 0.939 0.969 85 0.987 1.018 0.978 0.984 0.941 0.957 0.953 0.977 90 0.991 1.004 0.988 0.990 0.962 0.972 0.968 0.986 95 0.996 0.998 0.995 0.996 0.982 0.986 0.983 0.
TY Series 60Hz - HFC-410A Submittal Data Eng/I-P Antifreeze Correction Tables Antifreeze Correction Table Antifreeze Type Water Propylene Glycol Methanol Ethanol Ethylene Glycol Antifreeze % Cooling Heating EWT 90°F EWT 30°F WPD Corr. Fct. EWT 30°F Total Cap Sens Cap Power Htg Cap Power 0 1.000 1.000 1.000 1.000 N/A 1.000 N/A 1.000 N/A 5 0.995 0.995 1.003 0.989 0.997 1.070 15 0.986 0.986 1.009 0.968 0.990 1.210 25 0.978 0.978 1.014 0.947 0.983 1.360 5 0.
TY Series 60Hz - HFC-410A Submittal Data Eng/I-P ECM Blower Control The ECM fan is controlled directly by the DXM2 control board that converts thermostat inputs and CFM settings to signals used by the ECM motor controller. To take full advantage of the ECM motor features, a communicating multi-stage thermostat should be used (ATC32U**). The DXM2 control maintains a selectable operating airflow [CFM] for each heat pump operating mode. For each operating mode there are maximum and minimum airflow limits.
TY Series 60Hz - HFC-410A Submittal Data Eng/I-P Blower Performance Data Model 024 030 036 042 048 060 Max ESP (in wg) Fan Motor (hp) Range Default 750 575 650 500 750 575 350 750 0.75 1/2 Maximum 850 650 800 600 850 850 850 850 0.5 0.6 0.6 0.75 0.
TY Series 60Hz - HFC-410A Submittal Data Eng/I-P Physical Data Model 024 030 036 042 048 060 Compressor (1 Each) Scroll Scroll Scroll Scroll Scroll Scroll Factory Charge HFC-410A (oz) [kg] 49 48 48 70 80 84 ECM Fan Motor & Blower Fan Motor (hp) [W] 1/2 1/2 1/2 3/4 3/4 1 Blower Wheel Size (dia x w) - (in) [mm] 9X7 9X7 9X8 9X8 10X10 11X10 Water Connection Size FPT (in) 3/4" 3/4" 3/4" 3/4" 1" 1" Coax Volume (gallons) 0.323 0.323 0.738 0.89 0.738 0.
TY Series 60Hz - HFC-410A Submittal Data Eng/I-P TY - Horizontal Dimensional Data Horizontal Model Electrical Knockouts Overall Cabinet A Width B Length C Height Horizontal Model H 1/2” J 1/2” K 3/4” Low Voltage Low Voltage Power Supply 024 - 030 in cm 20.1 51.1 43.1 109.5 18.3 46.5 036 - 042 in cm 20.1 51.1 47.1 119.6 21.0 53.3 024 - 030 in cm 12.1 30.8 9.1 23.2 6.1 15.6 048 - 060 in cm 24.1 61.2 54.1 137.4 21.0 53.3 036 - 060 in cm 16.1 41.0 13.1 33.3 10.1 25.
TY Series 60Hz - HFC-410A Submittal Data Eng/I-P TY - Horizontal Dimensional Data LEFT RETURN RIGHT RETURN Optional 2' [61cm] CSP Service Access 2' [61cm] Service Access Front Power Supply 3 / 4" [19.1mm] Knockout Left Return 1 / 2" AA [12.7mm] Knockout 3.3" [83.8mm] Straight Discharge 3 K 2 J CSP AA 3.3" [83.8mm] F H E CAP 0.7" [17.8mm] BB D 1 0.7" [17.
TY Series 60Hz - HFC-410A Submittal Data Eng/I-P TY - Vertical Upflow Dimensional Data Overall Cabinet Vertical Upflow Model A Width B Depth C Height 024 - 030 in cm 21.5 54.6 21.5 54.6 40.0 101.6 036 - 042 in cm 21.5 54.6 26.0 66.0 45.0 114.3 048 - 060 in cm 24.0 61.0 32.5 82.6 46.0 116.8 Electrical Knockouts Water Connections - Standard Units 1 Vertical Upflow Model 2 3 Loop In D Loop In E Loop Out F Loop Out G 024 in cm 1.9 4.8 1.4 3.6 13.8 35.1 030 in cm 1.9 4.
TY Series 60Hz - HFC-410A Submittal Data Eng/I-P TY - Vertical Upflow Dimensional Data Discharge Connection Duct Flange Installed (+/- 0.10 in, +/- 2.5mm) Vertical Model Return Connection Using Return Air Opening M N O Supply Width P Supply Depth Q R S Return Depth T Return Height U 024 - 030 in cm 6.4 16.3 5.0 12.7 14.0 35.6 14.0 35.6 5.8 14.7 2.0 5.1 18.5 47.0 19.3 49.0 0.9 2.3 036 - 042 in cm 6.4 16.1 3.8 9.5 14.0 35.6 14.0 35.6 5.1 13.1 2.3 5.8 22.8 57.9 23.9 60.7 0.
TY Series 60Hz - HFC-410A Submittal Data Eng/I-P Corner Weights Corner Weights for TY Series Horizontal Units Model TYH024 TYH030 TYH036 TYH042 TYH048 TYH060 lbs Total Left-Front* Right-Front* Left-Back Right-Back 174 62 40 39 33 kg 79 28 18 18 15 lbs 182 67 41 40 34 kg 83 30 19 18 15 lbs 203 75 47 44 37 kg 92 34 21 20 17 lbs 218 81 50 48 39 kg 99 37 23 22 18 lbs 263 98 60 58 47 kg 119 44 27 26 21 lbs 303 103 64 61 75 kg 137 4
TY Series 60Hz - HFC-410A Submittal Data Eng/I-P Electrical Data Standard Units Model Voltage 024 030 036 042 048 060 Code G E H F* G E H F* G E H F* G H F* G E H F* G E H F* Voltage 208/230/60/1 265/60/1 208/230/60/3 460/60/3* 208/230/60/1 265/60/1 208/230/60/3 460/60/3* 208/230/60/1 265/60/1 208/230/60/3 460/60/3* 208/230/60/1 208/230/60/3 460/60/3* 208/230/60/1 265/60/1 208/230/60/3 460/60/3* 208/230/60/1 265/60/1 208/230/60/3 460/60/3* Min/Max Compressor Fan Motor Total Unit Min Circ Vo
TY Series 60Hz - HFC-410A Submittal Data Eng/I-P TY Series Wiring Diagram Matrix Only DXM 2 diagrams, with a representative diagram of LON and MPC Options are presented in this submittal. Other diagrams can be located online at climatemaster.com using the part numbers presented below.
TY Series 60Hz - HFC-410A Submittal Data Eng/I-P Typical Wiring Diagram – Single Phase TY Units with DXM2 Controller ClimateMaster works continually to improve its products. As a result, the design and specifications of each product at the time of order may be changed without notice and may not be as described herein. Please contact ClimateMaster's Customer Service Department at 1-405-745-6000 for specific information on the current design and specifications.
TY Series 60Hz - HFC-410A Submittal Data Eng/I-P Typical Wiring Diagram – Single Phase TY Units with DXM2 Controller and MPC ClimateMaster works continually to improve its products. As a result, the design and specifications of each product at the time of order may be changed without notice and may not be as described herein. Please contact ClimateMaster's Customer Service Department at 1-405-745-6000 for specific information on the current design and specifications.
TY Series 60Hz - HFC-410A Submittal Data Eng/I-P Typical Wiring Diagram – Three Phase 208/230V TY Units with DXM2 Controller ClimateMaster works continually to improve its products. As a result, the design and specifications of each product at the time of order may be changed without notice and may not be as described herein. Please contact ClimateMaster's Customer Service Department at 1-405-745-6000 for specific information on the current design and specifications.
TY Series 60Hz - HFC-410A Submittal Data Eng/I-P Typical Wiring Diagram – Three Phase 208/230V TY Units with DXM2 Controller and LON ClimateMaster works continually to improve its products. As a result, the design and specifications of each product at the time of order may be changed without notice and may not be as described herein. Please contact ClimateMaster's Customer Service Department at 1-405-745-6000 for specific information on the current design and specifications.
TY Series 60Hz - HFC-410A Submittal Data Eng/I-P Typical Wiring Diagram – Three Phase 460V TY Units with DXM2 Controller Note: 460V Units with ECM Motor Require A Neutral Wire. ClimateMaster works continually to improve its products. As a result, the design and specifications of each product at the time of order may be changed without notice and may not be as described herein.
TY Series 60Hz - HFC-410A Submittal Data Eng/I-P Tranquility® 22 (TY) Series 60Hz Engineering Specifications – Page 1 General: Furnish and install ClimateMaster Tranquility® “TY” Water Source Heat Pumps, as indicated on the plans. Equipment shall be completely assembled, piped, and internally wired. Capacities and characteristics as listed in the schedule and the specifications that follow.
TY Series 60Hz - HFC-410A Submittal Data Eng/I-P Tranquility® 22 (TY) Series 60Hz Engineering Specifications – Page 2 Option: The unit will be supplied with optional field or factory installed 2” air filter rails (typically used for free return installation) or 1” or 2” air filter frames with filter access door and return air duct flanges (typically used for ducted return installation). A corresponding 1” or 2” throwaway type glass fiber filter will ship with the factory installed filter rails or frame.
TY Series 60Hz - HFC-410A Submittal Data Eng/I-P Tranquility® 22 (TY) Series 60Hz Engineering Specifications – Page 3 must be HDPE (High Density Polyethylene) to avoid thermal cycling shock stress failure over the lifetime of the unit. Drain pan shall be fully insulated. Drain outlet shall be located at pan as to allow unobstructed drainage of condensate. Drain outlet for horizontal units shall be connected from pan directly to FPT fitting.
TY Series 60Hz - HFC-410A Submittal Data Eng/I-P Tranquility® 22 (TY) Series 60Hz Engineering Specifications – Page 4 Note: To achieve full benefit of the two-stage compressor and ECM fan, a 2 Heat/2 Cool thermostat (or a 3 Heat/2 Cool thermostat when electric backup heat is required) should be employed.
TY Series 60Hz - HFC-410A Submittal Data Eng/I-P Tranquility® 22 (TY) Series 60Hz Engineering Specifications – Page 5 c. d. e. f. g. h. i. j. k. l. m. n. o. p. q. r.
TY Series 60Hz - HFC-410A Submittal Data Eng/I-P Tranquility® 22 (TY) Series 60Hz Engineering Specifications – Page 6 stage of unit operation. The thermostat shall display system faults with probable cause and troubleshooting guidance.