Tranquility® Vertical Stack (TSM) Series Submittal Data Models TSM09 - 36 60Hz - HFC-410A English Language/I-P Units SUBMITTAL DATA - I-P UNITS Unit Designation: Job Name: Architect: Engineer: Contractor: PERFORMANCE DATA Cooling Capacity: Btuh EER: Heating Capacity: Btuh COP: Ambient Air Temp: °F Entering Water Temp (Clg): °F Entering Air Temp (Clg): °F Entering Water Temp (Htg): °F Entering Air Temp (Htg): °F Airflow: CFM Fan Speed or Motor/RPM/Turns: Revised: 16 December, 2014 Operati
Tranquility® Vertical Stack (TSM) Series Submittal Data Models TSM09 - 36 60Hz - HFC-410A English Language/S-I Units SUBMITTAL DATA - S-I UNITS Unit Designation: Job Name: Architect: Engineer: Contractor: PERFORMANCE DATA Cooling Capacity: kW EER: Heating Capacity: kW COP: Ambient Air Temp: °C Entering Water Temp (Clg): °C Entering Air Temp (Clg): °C Entering Water Temp (Htg): °C Entering Air Temp (Htg): °C Airflow: l/s Fan Speed or Motor/RPM/Turns: Revised: 16 December, 2014 Operating W
TSM Series 60Hz - HFC-410A Submittal Data Eng/I-P Table of Contents *Page Number Unit Features . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 4 iGate™ Communicating Controls . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 6 vFlow™ Internal Variable Water Flow Control . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 7 Selection Procedure . . . . . . . . . . . . . . . . . . .
TSM Series 60Hz - HFC-410A Submittal Data Eng/I-P Unit Features TRANQUILITY® VERTICAL STACK (TSM) SERIES WITH EARTHPURE® REFRIGERANT The Tranquility® Vertical Stack (TSM) Series offers an innovative, labor-saving solution for spaces where individual, quiet control of the heating and cooling system is important. TSM units’ consist of 2 major components - cabinet behind finished wall and slide in refrigeration chassis. Vertical risers running behind cabinet are especially ideal for multi-story buildings.
TSM Series 60Hz - HFC-410A Submittal Data Eng/I-P Unit Features vFlow™ systems provide reduced water pumping power compared to traditional fixed-speed pumping or fixed water flow systems and protects the unit against extreme operating conditions, extending the life of the compressor and air coil. Since vFlow™ is built inside the unit, it also saves on installation time and makes for a very clean and compact installation.
TSM Series 60Hz - HFC-410A Submittal Data Eng/I-P iGate™ Communicating Controls ECM Blower Motor iGate™ Information gateway to monitor, control and diagnose your system Tranquility® Vertical Stack Series is equipped with industry-first, iGate™ – Information Gateway – 2-way communicating system that allows users to interact with their water-source system in plain English AND delivers improved reliability and efficiency by precisely controlling smart variable speed components.
TSM Series 60Hz - HFC-410A Submittal Data Eng/I-P vFlow™ Internal Variable Water Flow Control vFlow™ Internal Variable Water Flow Industry-first, Built-in vFlow™ provide an ultra-highefficient, variable speed, internal water flow system. It saves installers time and labor by avoiding installing bulky external pumps, valves, or flow regulators. Multiunit installations are also much simpler with vFlow™ systems, as the units automatically adjust water flow across the system.
TSM Series 60Hz - HFC-410A Submittal Data Eng/I-P Selection Procedure Reference Calculations Heating Cooling HE LWT = EWT GPM x Constant LAT = EAT + HC CFM x1.08 LWT = EWT + HE GPM x Constant LAT (DB) = EAT (DB) - LC = TC - SC SC CFM x1.08 S/T = SC TC Constant = 500 for water, 485 for antifreeze.
TSM Series 60Hz - HFC-410A Submittal Data Eng/I-P Selection Procedure Step 1 Determine the actual heating and cooling loads at the desired dry bulb and wet bulb conditions. Step 2 Obtain the following design parameters: Entering water temperature, water flow rate in GPM, air flow in CFM, water flow pressure drop and design wet and dry bulb temperatures. Air flow CFM should be between 300 and 500 CFM per ton.
TSM Series 60Hz - HFC-410A Submittal Data Eng/I-P TSM Series Nomenclature Cabinet 1 2 3 C1 G 4 5 0 N 11 12 13 14 15 0 A 1 0 0 0 0 0 0 A 6 7 8 9 10 REVISION LEVEL CABINET SIZE A = CURRENT REVISION 1 = 09 2 = 12 3 = 15 4 = 18 5 = 24 6 = 30 7 = 36 STANDARD 0 = STANDARD A, B, C etc.... = SPECIAL 1, 2, 3 etc....
TSM Series 60Hz - HFC-410A Submittal Data Eng/I-P TSM Series Nomenclature Chassis 1 2 3 TSM 4 5 6 7 8 9 10 11 12 13 09 G S A S S C S S S A 15 14 Revision Level Series A = Current Revision Level TSM = TRANQUILITY® HIGH RISE CHASSIS Standard S = Standard A = Special #1 B = Special #2 Etc.....
TSM Series 60Hz - HFC-410A Submittal Data Eng/I-P TSM Series Nomenclature Return Air Panel 1 2 3 5 4 7 6 AVHS G 1 S 8 9 10 11 F S M S STANDARD ACCESSORY VHS RETURN AIR PANEL S = STANDARD DESCRIPTION TYPE “G” REVISION LEVEL Removable Fixed “A” M = CURRENT REVISION TSM (”G” PANEL) A = CURRENT REVISION TSM (”A” PANEL) UNIT SIZE OPTION 1 2 3 STYLE TSM/TSL 09, 12, 15, 18 N/A 24, 30, 36 A = DOOR w/ADA TSTAT MOUNTING B = DOOR w/ADA TSTAT MOUNTING & GRILLE C = DOOR w/ADA TSTAT MOUNTING & LO
TSM Series 60Hz - HFC-410A Submittal Data Eng/I-P Performance Data – AHRI/ASHRAE/ISO 13256-1 ASHRAE/AHRI/ISO 13256-1. English (I-P) Units Water Loop Heat Pump Model with ECM Motor Cooling 86°F Ground Water Heat Pump Heating 68°F Capacity Btuh EER Btuh/W Capacity Btuh 9,800 15.0 TSM12 11,600 TSM15 14,600 TSM18 Cooling 59°F COP Capacity Btuh EER Btuh/W Capacity Btuh 12,900 5.4 11,700 24.5 14.7 16,000 5.2 13,600 15.9 17,500 5.3 16,800 18,000 15.2 22,200 5.
TSM Series 60Hz - HFC-410A Submittal Data Eng/I-P Performance Data – Selection Notes For operation in the shaded area to determine if water can be used in lieu of an antifreeze solution, the Leaving Water Temperature (LWT) must be calculated. Flow must be maintained to a level such that the LWT is maintained above 42°F [5.6°C] when the CXM/DXM2 JW3 jumper is not clipped (see example below).
TSM Series 60Hz - HFC-410A Submittal Data Eng/I-P Performance Data – TSM09 with PSC Motor 400 CFM Nominal Airflow Heating, 350 CFM Nominal Airlfow Cooling *WPD Adder for Motorized Valve, TSM09 (Cv = 3.0, MOPD =200 psi) WPD Adder EWT °F 20 GPM PSI FT 1.5 0.3 0.6 2.3 0.6 1.3 3.0 1.0 30 2.
TSM Series 60Hz - HFC-410A Submittal Data Eng/I-P Performance Data – TSM12 with PSC Motor 500 CFM Nominal Airflow Heating, 400 CFM Nominal Airlfow Cooling WPD* EWT °F 20 30 40 50 60 70 80 90 100 110 120 GPM PSI FT 1.8 4.1 2.6 6.3 3.5 9.4 21.7 1.8 3.4 7.9 Performance capacities shown in thousands of Btuh Cooling - EAT 80/67°F TC SC Sens/Tot Ratio kW Heating - EAT 70°F HR EER HC kW HE LAT COP WPD Adder Operation not recommended 15.44 9.92 0.64 0.45 16.
TSM Series 60Hz - HFC-410A Submittal Data Eng/I-P Performance Data – TSM15 with PSC Motor 600 CFM Nominal (Rated) Airflow *WPD Adder for Motorized Valve, TSM15 (Cv = 4.7, MOPD = 200 psi) WPD Adder EWT °F 20 GPM PSI FT 2.3 0.2 0.5 3.4 0.5 1.2 4.5 0.9 2.1 30 40 50 60 70 80 90 100 110 120 Performance capacities shown in thousands of Btuh WPD* GPM PSI FT Cooling - EAT 80/67°F TC SC Sens/Tot Ratio kW Heating - EAT 70°F HR EER HC kW HE LAT COP 8.99 0.98 6.15 81.8 2.
TSM Series 60Hz - HFC-410A Submittal Data Eng/I-P Performance Data – TSM18 with PSC Motor 685 CFM Nominal (Rated) Airflow Performance capacities shown in thousands of Btuh WPD* EWT °F Cooling - EAT 80/67°F GPM 20 30 40 50 60 70 80 90 100 110 120 PSI FT TC SC Sens/Tot Ratio kW Heating - EAT 70°F HR 3.4 2.6 5.1 4.7 6.8 7.2 16.7 3.4 2.2 5.1 23.79 15.72 0.66 0.77 25.90 5.1 4.2 9.7 23.88 15.52 0.65 0.73 6.8 6.7 15.4 23.89 15.38 0.64 3.4 1.9 4.3 23.35 15.
TSM Series 60Hz - HFC-410A Submittal Data Eng/I-P Performance Data – TSM24 with PSC Motor 850 CFM Nominal (Rated) Airflow *WPD Adder for Motorized Valve, TSM24 (Cv = 7.4, MOPD = 200 psi) GPM WPD Adder PSI FT 4.0 0.3 0.7 6.0 0.7 1.5 8.0 1.2 2.7 Performance capacities shown in thousands of Btuh WPD* EWT °F 20 30 40 50 60 70 80 90 100 110 120 Cooling - EAT 80/67°F GPM PSI FT TC SC Sens/Tot Ratio Heating - EAT 70°F kW HR EER HC kW HE LAT COP 17.55 1.73 12.11 87.
TSM Series 60Hz - HFC-410A Submittal Data Eng/I-P Performance Data – TSM30 with PSC Motor 1000 CFM Nominal (Rated) Airflow Performance capacities shown in thousands of Btuh WPD* EWT °F Cooling - EAT 80/67°F GPM 20 30 40 50 60 70 80 90 100 110 120 PSI FT TC SC Sens/Tot Ratio kW Heating - EAT 70°F HR 4.0 1.2 6.0 2.5 8.0 5.2 12.1 4.0 0.9 2.1 33.05 22.48 0.68 1.30 36.75 6.0 2.3 5.3 32.29 21.97 0.68 1.23 35.77 8.0 5.0 11.4 31.79 21.64 0.68 1.20 4.0 0.7 1.
TSM Series 60Hz - HFC-410A Submittal Data Eng/I-P Performance Data – TSM36 with PSC Motor 1200 CFM Nominal (Rated) Airflow *WPD Adder for Motorized Valve, TSM36 (Cv = 7.4, MOPD = 200 psi) GPM WPD Adder PSI FT 4.5 0.4 0.9 6.8 0.8 1.9 9.0 1.5 3.4 Performance capacities shown in thousands of Btuh WPD* EWT °F 20 30 40 50 60 70 80 90 100 110 120 Cooling - EAT 80/67°F GPM PSI 4.5 3.7 6.0 5.0 9.0 8.
TSM Series 60Hz - HFC-410A Submittal Data Eng/I-P Performance Data – TSM09 with ECM Motor 400 CFM Nominal Airflow Heating, 350 CFM Nominal Airflow Cooling WPD EWT °F GPM 20 30 40 50 60 70 80 90 100 110 120 PSI FT Performance capacities shown in thousands of Btuh Cooling - EAT 80/67°F TC SC Sens/Tot Ratio Heating - EAT 70°F kW HR EER HC kW HE LAT COP 6.18 0.65 3.96 75.6 2.8 1.5 1.6 2.3 1.8 3.0 5.7 13.2 1.5 1.1 2.6 13.23 9.05 0.68 0.41 14.61 32.5 7.21 0.
TSM Series 60Hz - HFC-410A Submittal Data Eng/I-P Performance Data – TSM12 with ECM Motor 500 CFM Nominal Airflow Heating, 400 CFM Nominal Airflow Cooling *WPD Adder for Motorized Valve, TSM12 (Cv = 3.0, MOPD =200 psi) WPD EWT °F SC Sens/Tot Ratio kW HR EER HC kW HE LAT COP 4.1 6.3 FT 3.5 9.4 21.7 7.76 0.77 5.13 83.9 2.9 1.8 3.4 7.9 15.67 10.25 0.65 0.41 17.07 38.2 8.92 0.79 6.23 86.3 3.3 2.7 5.6 13.0 15.78 10.15 0.64 0.37 17.05 42.4 9.25 0.79 6.54 87.0 3.
TSM Series 60Hz - HFC-410A Submittal Data Eng/I-P Performance Data – TSM15 with ECM Motor 600 CFM Nominal (Rated) Airflow Performance capacities shown in thousands of Btuh WPD EWT °F 20 30 40 50 60 70 80 90 100 110 120 Cooling - EAT 80/67°F GPM PSI FT TC SC Sens/Tot Ratio kW Heating - EAT 70°F HR EER HC kW HE LAT COP 8.69 0.83 6.15 81.8 3.2 2.3 2.4 3.5 5.8 4.5 8.8 20.3 2.3 2.3 5.4 17.43 11.10 0.64 0.50 19.15 34.5 10.14 0.86 7.51 84.1 3.6 3.5 5.0 11.
TSM Series 60Hz - HFC-410A Submittal Data Eng/I-P Performance Data – TSM18 with ECM Motor 700 CFM Nominal (Rated) Airflow *WPD Adder for Motorized Valve, TSM18 (Cv =4.7, MOPD = 200 psi) WPD Adder WPD EWT °F 20 GPM PSI FT 3.4 0.5 1.2 5.1 1.2 2.7 6.8 2.1 4.8 Performance capacities shown in thousands of Btuh 30 40 50 60 70 80 90 100 110 120 Cooling - EAT 80/67°F GPM PSI FT TC SC Sens/Tot Ratio kW Heating - EAT 70°F HR EER HC kW HE LAT COP 10.67 1.03 7.16 82.1 3.
TSM Series 60Hz - HFC-410A Submittal Data Eng/I-P Performance Data – TSM24 with ECM Motor 850 CFM Nominal (Rated) Airflow Performance capacities shown in thousands of Btuh WPD EWT °F Cooling - EAT 80/67°F GPM 20 30 40 50 60 70 80 90 100 110 120 PSI FT TC SC Sens/Tot Ratio kW Heating - EAT 70°F HR EER HC kW HE LAT COP 17.55 1.60 12.11 87.1 3.2 4.0 6.0 3.9 2.5 8.0 5.2 12.1 4.0 0.9 2.1 33.57 21.59 0.64 0.92 36.72 36.4 19.10 1.59 13.69 88.8 3.5 6.0 2.
TSM Series 60Hz - HFC-410A Submittal Data Eng/I-P Performance Data – TSM30 with ECM Motor 1000 CFM Nominal (Rated) Airflow *WPD Adder for Motorized Valve, TSM30 (Cv = 7.4, MOPD = 200 psi) GPM WPD Adder PSI 0.3 0.7 6.0 0.7 1.5 8.0 1.2 2.7 Cooling - EAT 80/67°F EWT °F GPM 4.0 1.2 20 6.0 2.5 8.0 5.2 12.1 4.0 0.9 2.1 33.05 22.48 0.68 1.08 6.0 2.3 5.3 32.29 21.97 0.68 8.0 5.0 11.4 31.79 21.64 0.68 4.0 0.7 1.6 33.55 22.84 6.0 2.3 5.2 33.34 8.0 4.6 10.7 4.0 0.
TSM Series 60Hz - HFC-410A Submittal Data Eng/I-P Performance Data – TSM36 with ECM Motor 1200 CFM Nominal (Rated) Airflow Performance capacities shown in thousands of Btuh WPD EWT °F GPM PSI 4.5 20 30 40 50 60 70 80 90 100 110 120 Cooling - EAT 80/67°F FT TC SC Sens/Tot Ratio kW Heating - EAT 70°F HR EER HC kW HE LAT COP 23.28 2.22 15.72 85.9 3.1 3.7 6.0 5.0 9.0 8.6 19.8 4.5 2.8 6.4 46.26 30.11 0.65 1.53 51.50 30.2 26.08 2.26 18.36 88.1 3.4 6.0 3.8 8.
TSM Series 60Hz - HFC-410A Submittal Data Eng/I-P Performance Data – TSM09 with Modulating Valve or Variable Speed Pump 400 CFM Nominal Airflow Heating, 350 CFM Nominal Airflow Cooling EWT °F WPD Cooling - EAT 80/67°F WPD GPM PSI FT TC SC kW HR EER LWT 20 30 40 50 60 70 80 90 100 110 120 Heating - EAT 70ºF GPM PSI FT HC kW HE LAT COP LWT 3.0 5.7 13.2 6.18 0.65 3.96 75.6 2.8 17 1.0 0.7 1.6 13.10 9.16 0.45 14.62 29.4 60 1.5 1.1 2.5 7.21 0.66 4.95 76.
TSM Series 60Hz - HFC-410A Submittal Data Eng/I-P Performance Data – TSM12 with Modulating Valve or Variable Speed Pump 400 CFM Nominal Airflow Heating, 500 CFM Nominal Airflow Cooling EWT °F WPD Cooling - EAT 80/67°F WPD GPM PSI FT TC SC kW HR EER LWT PSI FT 1.1 1.1 2.6 15.10 9.86 0.51 16.85 29.6 60 3.5 9.4 21.7 7.76 0.77 5.13 83.9 2.9 17 1.8 3.4 7.9 8.92 0.79 6.23 86.3 3.3 23 1.1 1.1 2.6 15.10 9.86 0.51 16.85 29.6 60 1.1 1.1 2.6 15.10 9.86 0.
TSM Series 60Hz - HFC-410A Submittal Data Eng/I-P Performance Data – TSM15 with Modulating Valve or Variable Speed Pump 600 CFM Nominal Airflow Heating, 600 CFM Nominal Airflow Cooling EWT °F WPD Cooling - EAT 80/67°F WPD GPM PSI FT TC SC kW HR EER LWT PSI FT 1.3 1.8 4.2 17.75 11.82 0.58 19.74 30.5 60 4.5 8.8 20.3 8.99 0.83 6.15 81.8 3.2 17 2.3 2.3 5.3 10.14 0.86 7.51 84.1 3.6 23 1.3 1.8 4.2 17.75 11.82 0.58 19.74 30.5 60 3.5 1.3 1.8 4.2 17.75 11.
TSM Series 60Hz - HFC-410A Submittal Data Eng/I-P Performance Data – TSM18 with Modulating Valve or Variable Speed Pump 700 CFM Nominal Airflow Heating, 700 CFM Nominal Airflow Cooling EWT °F WPD Cooling - EAT 80/67°F WPD GPM PSI FT TC SC kW HR EER LWT PSI FT HC COP LWT 1.7 0.3 0.7 22.88 15.85 0.75 25.43 30.5 60 6.8 7.2 16.6 10.66 1.03 7.15 3.4 2.2 5.1 11.47 1.04 7.91 82.1 3.0 17.9 83.1 3.2 1.7 0.3 0.7 22.88 15.85 0.75 25.43 30.5 60 5.1 4.2 9.7 11.
TSM Series 60Hz - HFC-410A Submittal Data Eng/I-P Performance Data – TSM24 with Modulating Valve or Variable Speed Pump 850 CFM Nominal Airflow Heating, 850 CFM Nominal Airflow Cooling EWT °F WPD Cooling - EAT 80/67°F WPD GPM PSI FT TC SC kW HR EER LWT PSI FT COP LWT 2.4 0.5 1.2 32.76 21.27 1.01 36.21 32.3 60 8.0 5.2 12.0 13.86 1.73 7.94 4.0 0.9 2.1 17.35 1.67 11.67 83.1 2.3 18.0 86.9 3.1 2.4 0.5 1.2 32.76 21.27 1.01 36.21 32.3 60 6.0 2.3 5.3 18.
TSM Series 60Hz - HFC-410A Submittal Data Eng/I-P Performance Data – TSM30 with Modulating Valve or Variable Speed Pump 1000 CFM Nominal Airflow Heating, 1000 CFM Nominal Airflow Cooling EWT °F WPD Cooling - EAT 80/67°F WPD GPM PSI FT TC SC kW HR EER LWT PSI FT 2.5 0.5 1.1 33.42 22.73 1.22 37.56 27.5 60 8.0 5.2 12.0 17.82 1.72 11.96 84.5 3.0 17 4.0 0.9 2.1 18.94 1.74 13.02 85.5 3.2 20 2.5 0.5 1.1 33.42 22.73 1.22 37.56 27.5 60 6.0 2.3 5.3 18.94 1.
TSM Series 60Hz - HFC-410A Submittal Data Eng/I-P Performance Data – TSM36 with Modulating Valve or Variable Speed Pump 1200 CFM Nominal Airflow Heating, 1200 CFM Nominal Airflow Cooling EWT °F WPD Cooling - EAT 80/67°F WPD GPM PSI FT TC SC kW HR EER LWT PSI FT 3.4 0.9 2.0 45.94 30.11 1.63 51.51 28.2 60 9.0 8.6 19.9 23.28 2.22 15.72 85.9 3.1 17 4.5 2.8 6.5 26.08 2.26 18.36 88.1 3.4 22 3.4 0.9 2.0 45.94 30.11 1.63 51.51 28.2 60 6.0 3.4 0.9 2.0 45.
TSM Series 60Hz - HFC-410A Submittal Data Eng/I-P Performance Data Correction Tables Air Flow Correction Table Airflow Cooling % of Nominal (Rated) SCFM Total Capacity 70 75 Heating Sensible Capacity Power Heat of Rejection Heating Capacity Power Heat of Extraction 0.921 0.8 0.969 0.943 0.942 1.077 0.934 0.934 0.833 0.974 0.952 0.952 1.062 0.947 80 0.946 0.866 0.979 0.961 0.961 1.048 0.958 85 0.958 0.899 0.985 0.97 0.971 1.035 0.969 90 0.971 0.932 0.99 0.
TSM Series 60Hz - HFC-410A Submittal Data Eng/I-P vFlow™ - Modulating Valve and Variable Pump Tables Modulating Valve for Closed Loop Applications/Water Pressure Drop Adder Model CV 09 4.9 12 15 18 10.3 24 30 36 WPD Adders GPM PSI FT 1.5 2.3 3.0 1.8 2.6 3.5 2.3 3.4 4.5 3.4 5.1 6.8 4.0 6.0 8.0 4.0 6.0 8.0 4.5 6.8 9.0 0.09 0.21 0.37 0.13 0.28 0.51 0.05 0.11 0.19 0.11 0.25 0.44 0.15 0.34 0.6 0.15 0.34 0.6 0.19 0.43 0.76 0.22 0.49 0.87 0.29 0.65 1.18 0.11 0.25 0.44 0.25 0.57 1.01 0.35 0.78 1.
TSM Series 60Hz - HFC-410A Submittal Data Eng/I-P PSC Blower Performance Data TSM with PSC Motor Airflow in CFM with wet coil and clean 1" (25mm) fiberglass air filter. Size Fan Speed Rated CFM Min CFM High 09 Medium 400H/350C 284 Low 15 415 400 380 360 345 325 320 0.20Operation 0.25not recommended 0.30 0.35 360 330 320 300 * * 400 375 0.40 0.45 0.
TSM Series 60Hz - HFC-410A Submittal Data Eng/I-P ECM Blower Performance Data TSM Non Ducted ECM 88 and 80" Cabinets All data wet coil clean filter. Tranquility Model ESP Range (in wg) Constant Cooling Mode TSM12 TSM15 TSM18 TSM24 TSM30 TSM36 0 to 0.25 0 to 0.25 0 to 0.3 0 to 0.3 0 to 0.3 0 to 0.4 0 to 0.
TSM Series 60Hz - HFC-410A Submittal Data Eng/I-P Sound Data Free Standing Ductless Standard Construction Model TSM09 TSM12 TSM15 TSM18 TSM24 TSM30 TSM36 Mode Free Standing Ductless UltraQuiet Construction Octive Band Frequency, Hz Octive Band Frequency, Hz 125 250 500 1000 2000 4000 8000 125 250 500 1000 2000 4000 8000 Fan Only Low Speed Fan 53 45 46 37 30 30 34 53 45 46 37 30 30 34 Fan Only Med Speed Fan 55 49 49 41 35 34 35 55 49 49 41 35 34 35 Fa
TSM Series 60Hz - HFC-410A Submittal Data Eng/I-P Physical Data Model 09 12 Compressor (1 Each) Factory Charge HFC-410A (oz) [kg] 15 18 24 30 Rotary 36 Scroll 34 [.07] 34 [.97] 43 [1.22] 53 [1.51] 71 [2.01] 66 [1.87] 81 [2.29] 6.75 x 7.25 [174 x 184] 6.75 x 7.25 [174 x 184] 9.50 x 7.12 [241 x 181] 9.50 x 7.12 [241 x 181] 9.50 x 7.12 [241 x 181] 9.50 x 8.06 [241 x 205] 9.50 x 8.
TSM Series 60Hz - HFC-410A Submittal Data Eng/I-P Electrical Data - PSC Motor Model # TSM09G TSM12G TSM15G TSM18G TSM24G TSM30G TSM36G TSM09E TSM12E TSM15E TSM18E TSM24E TSM30E TSM36E Rated Voltage none 2.5 none 2.5 none 2.5 5 none 2.5 5 none 2.5 5 none 2.5 5 none 2.5 5 none 2.5 none 2.5 none 2.5 5 none 2.5 5 none 2.5 5 none 2.5 5 none 2.
TSM Series 60Hz - HFC-410A Submittal Data Eng/I-P Electrical Data - ECM Motor Model with ECM Motor TSM09G TSM12G TSM15G TSM18G TSM24G TSM30G TSM36G TSM09E TSM12E TSM15E TSM18E TSM24E TSM30E TSM36E none 2.5 none 2.5 none 2.5 5 none 2.5 5 none 2.5 5 none 2.5 5 none 2.5 5 none 2.5 none 2.5 none 2.5 5 none 2.5 5 none 2.5 5 none 2.5 5 none 2.
TSM Series 60Hz - HFC-410A Submittal Data Eng/I-P TSM Series Wiring Diagram Matrix All current diagrams can be located online at climatemaster.com. Click ‘Commercial’ (go to ‘Quick Links’ in the upper right) using the part numbers presented below.
TSM Series 60Hz - HFC-410A Submittal Data Eng/I-P Typical Wiring Diagram – TSM09 - 36 CXM with PSC Motor ClimateMaster works continually to improve its products. As a result, the design and specifications of each product at the time of order may be changed without notice and may not be as described herein. Please contact ClimateMaster's Customer Service Department at 1-405-745-6000 for specific information on the current design and specifications.
TSM Series 60Hz - HFC-410A Submittal Data Eng/I-P Typical Wiring Diagram – TSM09 - 36 DXM2 with PSC Motor ClimateMaster works continually to improve its products. As a result, the design and specifications of each product at the time of order may be changed without notice and may not be as described herein. Please contact ClimateMaster's Customer Service Department at 1-405-745-6000 for specific information on the current design and specifications.
TSM Series 60Hz - HFC-410A Submittal Data Eng/I-P Typical Wiring Diagram – TSM09 - 12 DXM2 with ECM Motor ClimateMaster works continually to improve its products. As a result, the design and specifications of each product at the time of order may be changed without notice and may not be as described herein. Please contact ClimateMaster's Customer Service Department at 1-405-745-6000 for specific information on the current design and specifications.
TSM Series 60Hz - HFC-410A Submittal Data Eng/I-P Typical Wiring Diagram – TSM15 - 36 DXM2 with ECM Motor ClimateMaster works continually to improve its products. As a result, the design and specifications of each product at the time of order may be changed without notice and may not be as described herein. Please contact ClimateMaster's Customer Service Department at 1-405-745-6000 for specific information on the current design and specifications.
TSM Series 60Hz - HFC-410A Submittal Data Eng/I-P Typical Wiring Diagram – Single Phase TSM Units with DXM2 Controller with Night Setback, Emergency Shutdown, & Pump Restart DXM 2 DXM 2 ClimateMaster works continually to improve its products. As a result, the design and specifications of each product at the time of order may be changed without notice and may not be as described herein.
TSM Series 60Hz - HFC-410A Submittal Data Eng/I-P Typical Unit - Exploded View Major Components 1. TSM Cabinet (Furred-in) A - floating condensate drain pan B - drain P trap C - supply air plenum D - optional surface mount thermostat 2 x 4 box horizontal E - optional disconnect / breaker location F - upper control box (high voltage terminal blocks optional MPC, Lon) G - blower assembly/motor H - risers (not shown) I - shutoffs (not shown) J - filter panel K - filter 2.
TSM Series 60Hz - HFC-410A Submittal Data Eng/I-P TSM – Standard Unit, Furred In Cabinet with Risers Top Supply Air KO Optional Remote T/Stat Conduit Power Conduit 2.00(51) Service Area 1.00 x 1.
TSM Series 60Hz - HFC-410A Submittal Data Eng/I-P TSM – Master Unit, Furred In Cabinet Top Supply Air KO Optional Remote T/Stat Conduit Power Conduit 2.00(51) Service Area 1.00 x 1.
TSM Series 60Hz - HFC-410A Submittal Data Eng/I-P TSM – Slave Unit, Furred In Cabinet, No Risers Top Supply Air KO Optional Remote T/Stat Conduit Power Conduit 2.00(51) Service Area 1.00 x 1.38 (25 x 35) Supply Air Angles Note 6 Note 7 24 (610) Thin Wall Conduit 3/4" (19) Supply Air K.O.
TSM Series 60Hz - HFC-410A Submittal Data Eng/I-P Master/Slave Cabinet Installation RA S R R S R S Note 4 Field connect hoses in both cabinets supply to supply and return to return (Cabinet supply is closest to corner, chassis supply is on left facing air coil) RA Field braze valve package (shut off with tubing) Field install P-Trap and clamp both ends 2” (50) Minimum extend copper if over 3” (75) Master (Style 3) Slave Notes: 1. Contractor must meet all fire code requirements. 2.
TSM Series 60Hz - HFC-410A Submittal Data Eng/I-P Cabinet Dimensions C 1.125 DIA (2) Holes (28.6) C 1.62 [41] 1.50 [38] 1.50 [38] C High Voltage Entrance C C 2.12 [54] D D D E F F 1.25 [32] 88.00 [2235] or 80.00 [2032] (Note 4) 66.75 [1695] OPENING FOR CHASSIS 2.50 x 12.00 [64 x 305] 5.00 [127] 5.00 [127] 2.75 [70] 2.88 [73] 57.00 [1259] 2.88 [73] 5.00 (127) 35.75 [908] Note 5 12.12 [308] 12.00 [305] 12.12 [308] 6.00 [152] L.H. SIDE 12.12 [308] 2.25 x 3.
TSM Series 60Hz - HFC-410A Submittal Data Eng/I-P Cabinet Slot Dimensions and Riser Arrangements TOP VIEWS 2.75” (70) 12.00” (305) A S S 5.00” (127) R 9.25” (235) 2.75” (70) STYLE 4 RA R B D D STYLE 4 STYLE 5 RA SIDE RA SIDE Model 09-18 24-36 A STYLE 5 RA STYLE 3 RA STYLE 2 RA STYLE 2 RA STYLE 3 RA B 19.25 [489] 24.25 [616] STYLE 4 RA STYLE 5 RA 19 [483] 24 [610] Note 8 2.88” (73) D R 2.
TSM Series 60Hz - HFC-410A Submittal Data Eng/I-P TSM Cabinet Configurations Cabinet Model Digits 11 and 12 Describe Air Flow Configuration 00 No Supply Air Openings 01 Right Side 02 Left Side 10 Back 11 Back & Right 12 Back & Left 20 Front 21 Front & Right 22 Front & Left 03 Left & Right Sides 23 Front, Left, & Right Notes: 1. Front is return air side and control box location. 2. Risers can be on any side without return or supply air openings.
TSM Series 60Hz - HFC-410A Submittal Data Eng/I-P Typical Cabinet Installation - Flush X C NOTICE! R.O. Seal between studs and cabinet flanges with weather tight foam material to prevent wall cavity air from infiltrating unit or room. A Supply air grille note 5 TSM CABINET FOR SURFACE MOUNTED THERMOSTAT flex boot (customer supplied) X X 2x4 nominal studs TOP VIEW Note 4 X OUTSIDE CORNER 5/8” (16) drywall 1 or 2 layers. Position studs accordingly.
TSM Series 60Hz - HFC-410A Submittal Data Eng/I-P Typical Cabinet Installation - Recessed X 6.00 (152) Note 8 ѥ NOTICE! ѥ Recessed cabinet requires frame kit. Seal Gap (4) Sides Frame Outside Drywall Outside air requires motorized damper. X G Style Return Air Panel Seal between the frame and cabinet with weather seal material to avoid air being pulled in from the wall cavity. Attach frame to studs not cabinet.
TSM Series 60Hz - HFC-410A Submittal Data Eng/I-P Hinged “G” Style Return Air Panel – AVHSG Series Inner Panel Pivots Open .625 (16) A 1.81 (46) 15 (380) Outer Panel 59.00 (1499) Hinged Inner Panel Locks 46.50 (1181) To Floor 4.
TSM Series 60Hz - HFC-410A Submittal Data Eng/I-P AHH Series – Stainless Steel Braided Hose Kit Specifications: • • • • • • • • • Designed for VHS water-source heat pump applications. Kevlar® reinforced EPDM core with ANSI 302/304 stainless steel outer braid. Fire rated materials per ASTM E 84-00 (NFPA 255, ANSI/UL 723 & UBC 8-1). MPT (External Pipe Thread) fitting at one end; swivel with NPSH thread connector (Internal Thread) at the other end (seals via fiber or EPDM washer, shipped inside connection).
TSM Series 60Hz - HFC-410A Submittal Data Eng/I-P Supply Air Openings and Grilles Standard cabinet openings and grille sizes. (W x H) 88" (2235) cabinet models 09-18 – front, back, or sides 12 x 12 (305 x 305) or 12 x 6 (305 x 152) and top 12 x 12 (305 x 305). 80" (2032) cabinet models 09-18 – front, back, or sides 12 x 6 (305 x 152) and top 12 x 12 (305 x 305). 88" (2235) cabinet models 24-36 – front, back, or sides 16 x 16 (406 x 406) or 16 x 8 (406 x 203) and top 16 x 16 (406 x 406).
TSM Series 60Hz - HFC-410A Submittal Data Eng/I-P Thermostats Two types of thermostats are available AT Series - require field to make wiring connections to screw terminals on thermostat. Cabinet construction for remote thermostat with field supplied whip (wires long enough to reach wall thermostat location) use AT Series. A91558 Series - are the AT Series thermostats with a wire harness factory assembled, 6” long wires terminating with 9 pin molex connector.
TSM Series 60Hz - HFC-410A Submittal Data Eng/I-P TSM Options Optional Cabinet Disconnect Switch (Non Fused) Located on control box access door. Can be accessed through slot in “G” Panel Frame. Classified as motor disconnect. See Cabinet decoder. Optional Cabinet Circuit Breaker Located on control box access door. Can be accessed through slot in “G” Panel Frame. All 208/230V and 265V 15 and 20 amp classified as HACR breaker. 265V 25 amp and higher classified as supplemental breaker. See Cabinet decoder.
TSM Series 60Hz - HFC-410A Submittal Data Eng/I-P ECM Blower Motor (Optional) The ECM blower motor (optional) for TSM09 - 36 is controlled directly by the DXM2 control board that converts thermostat inputs and CFM settings to signals used by the ECM motor controller. To take full advantage of the ECM motor features, a communicating multi-stage thermostat should be used (ATC32U**). The DXM2 control maintains a selectable operating airflow [CFM] for each heat pump operating mode.
TSM Series 60Hz - HFC-410A Submittal Data Eng/I-P Riser Definitions Swaged 3” Deep For A Dia. Riser From Above A Dia. A Dia. A A Dia. A Dia. Shutoff Valve Assembly A Dia. B Dia. 6.00 (152) MAX 3.00 (76) B Dia. Runout Into Cabinet Bottom of Cabinet Runout Into Cabinet Runout Into Cabinet 39.75 (1100) 3.00 (76) (Note 10) Drain Runout Into Cabinet Supply and Return Supply and Return Transition Up Straight Runout Into Cabinet C Dia. Supply and Return Transition Down 3.
TSM Series 60Hz - HFC-410A Submittal Data Eng/I-P Riser GPM Definitions and Sizing Riser GPM requirements and individual Unit GPM requirements are necessary to select the proper Riser Piping diameters. Refer to this page to determine GPM requirement, then refer to Riser Diameter Sizing Table to determine Riser Piping diameters. Example is for bottom supply (upward flow) - bottom return (downward flow) system feed loop, both supply and return will be same GPM.
TSM Series 60Hz - HFC-410A Submittal Data Eng/I-P Riser Diameter Sizing Refer to Riser GPM Definitions and Sizing for the prefix to this example. Each TSM Vertical Stack unit has three riser pipes: supply, return, and drain. The following example will be for Supply and Return riser pipe (from the top floor to the bottom floor), supply flow up and return flow down.
TSM Series 60Hz - HFC-410A Submittal Data Eng/I-P Riser Length Definitions and Sizing Total Riser Length (L) = FF of floor below + 2"(51) FF - (RRH + RT) + 4" (102). THIRD FLOOR Floor To Floor Height (FF): Distance from top of unit slab to top of above slab. Room Riser Height (RRH): Cabinet height + 3" (76). SECOND FLOOR FF=110 (2794) RRH=91 (2311) Riser Tail Piece (RT): Length of riser extending down from the cabinet. Riser tail piece must extend a minimum of 5" (127) below slab.
TSM Series 60Hz - HFC-410A Submittal Data Eng/I-P Riser Extension Definitions and Sizing Joint Overlap Riser Extension Length: Start with the floor to floor Dim. (FF) From this subtract the room riser height and tail piece length. Then add 4" (102) for the two joint overlaps. 2" (51) Unit "B" Riser Extension Length = FF - (RRH + RT) + 4" (102). Slab Thickness Riser Tail Piece (RT): Length of riser extending down from the cabinet. Riser tail piece must extend a minimum of 5" (127) below slab.
TSM Series 60Hz - HFC-410A Submittal Data Eng/I-P Setting Cabinet NOTICE! Before locating riser slab slot in floor, review plans and all information in this submittal regarding cabinet, risers, slab slot, rotation into slot, clear height and the relationship of all. To determine the slab slot size required for the risers and to determine if clear height is OK for unit installation, use the example 2 on riser length page and slab slot charts on the next page.
TSM Series 60Hz - HFC-410A Submittal Data Eng/I-P Slab Slot Chart - 3 Pipe 3 Pipe Standard 88" Cabinet Riser Stack Patterns Slab Slot Size Type of Installation Type 1 R S Type 2 D For Cabinet Styles 2 and 5 Type 3 or W D S R For Cabinet Styles 3 and 4 L 9¼ (235) WxL WxL WxL Clear Height is Floor to Ceiling Dimension Slab Slot for Cabinets with Risers Model 09-18 24-36 Type of Installing Cabinet Through Slot Clear Height Riser length in mm in mm Type 1 105 100 98 96 95 2667
TSM Series 60Hz - HFC-410A Submittal Data Eng/I-P Shipping Units Are Shipped FOB Factory TSM Chassis can be shipped 2 ways. 1. Upright in carton 4 per pallet, see figure 1. 2. Upright inside cabinet (risers shipped separate or customer supplied) 4 per pallet, see figure 1. TSM Cabinet without risers attached can ship upright 4 per pallet, see figure 1. TSM Cabinet with risers attached must be shipped horizontal and normally on dedicated open flat bed trailer either 3 or 6 per pallet, see figure 2 and 3.
TSM Series 60Hz - HFC-410A Submittal Data Eng/I-P Tranquility® Modular - TSM Series Engineering Specifications – Page 1 General: Furnish and install ClimateMaster Tranquility® “TSM Vertical Stack” Water Source Heat Pumps, as indicated on the plans with capacities and characteristics as listed in the schedule and the specifications that follow. Units shall be supplied completely factory built capable of operating over an entering water temperature range from 20° to 120°F (-6.7° to 48.9°C) as standard.
TSM Series 60Hz - HFC-410A Submittal Data Eng/I-P Tranquility® Modular - TSM Series Engineering Specifications – Page 2 Full-length supply, return, and insulated condensate water risers shall be type M copper. Supply and return risers have integral internal piping including ball valves (for shut off purposes at unit). Risers and piping shall be factory pressure tested to check for leaks. Field installed hose kits are required to connect the chassis piping to the cabinet ball valve.
TSM Series 60Hz - HFC-410A Submittal Data Eng/I-P Tranquility® Modular - TSM Series Engineering Specifications – Page 3 Refrigerant Circuit: All units shall contain an EarthPure® (HFC-410A) sealed refrigerant circuit including a high efficiency scroll or rotary compressor designed for heat pump operation, a thermostatic expansion valve for refrigerant metering, an enhanced corrugated aluminum lanced fin and rifled copper tube refrigerant to air heat exchanger, reversing valve, coaxial (tube in tube) refri
TSM Series 60Hz - HFC-410A Submittal Data Eng/I-P Tranquility® Modular - TSM Series Engineering Specifications – Page 4 Option: Stainless steel drain pan Electrical: A control compartment shall be located within the chassis and shall contain a 50VA transformer, 24 volt activated, 2 pole compressor contactor, relay and solid-state controller for complete unit operation. Reversing valve and fan motor wiring shall be routed through this electronic controller.
TSM Series 60Hz - HFC-410A Submittal Data Eng/I-P Tranquility® Modular - TSM Series Engineering Specifications – Page 5 Control shall have all of the above-mentioned features of the CXM control system along with the following expanded features: a. b. c. d. e. f. g. h. i. j. k. l. m. n. o. Removable thermostat connector. Night setback control. Random start on return from night setback.
TSM Series 60Hz - HFC-410A Submittal Data Eng/I-P Tranquility® Modular - TSM Series Engineering Specifications – Page 6 i. j. k. l. m. n. o. p. q. r.
TSM Series 60Hz - HFC-410A Submittal Data Eng/I-P Tranquility® Modular - TSM Series Engineering Specifications – Page 7 Option: Supply grille with double deflection style louvers. Option: Supply grille with double deflection style louvers with opposed damper. Warranty: ClimateMaster shall warranty equipment for a period of 12 months from start up or 18 months from shipping (which ever occurs first). Option: Extended 4-year compressor warranty covers compressor for a total of 5 years.
TSM Series 60Hz - HFC-410A Submittal Data Eng/I-P Tranquility® Modular - TSM Series Engineering Specifications – Page 8 d. Multistage Digital Automatic Changeover (ATA22U01) Thermostat shall be multi-stage (2H/2C), manual or automatic changeover with HEAT-OFF-COOL-AUTO-EM HEAT system settings and fan ON-AUTO settings. Thermostat shall have an LCD display with temperature, setpoint(s), mode, and status indication. The temperature indication shall be selectable for ºF or ºC.
TSM Series 60Hz - HFC-410A Submittal Data Eng/I-P Notes: ClimateMaster works continually to improve its products. As a result, the design and specifications of each product at the time of order may be changed without notice and may not be as described herein. Please contact ClimateMaster's Customer Service Department at 1-405-745-6000 for specific information on the current design and specifications.
TSM Series 60Hz - HFC-410A Submittal Data Eng/I-P Notes: ClimateMaster works continually to improve its products. As a result, the design and specifications of each product at the time of order may be changed without notice and may not be as described herein. Please contact ClimateMaster's Customer Service Department at 1-405-745-6000 for specific information on the current design and specifications.
TSM Series 60Hz - HFC-410A Submittal Data Eng/I-P Revision History Date: 12/16/14 Item: Action: Edits - page 59 Updated 12/12/14 Table - page 37 Updated 11/11/14 Added ATP21W02 Thermostat, Electric Heat, iGate Options, Misc. Changes. Removed ATP21U01 Thermostat.