changeover with HEAT-OFF-COOL-AUTO system settings and fan ON-AUTO settings. Thermostat shall have an LCD
display with temperature, set-point(s), mode, and status indication. The temperature indication shall be selectable for ºF or
ºC. The thermostat shall provide permanent memory of set-point(s) without batteries. Thermostat shall provide convenient
override feature to temporarily change set point.
h. Multistage Automatic or Manual Changeover Programmable 7 Day (ATP32U01)
Thermostat shall be 7 day programmable (with up to 4 set points per day), multi-stage (3H/2C), automatic or manual
changeover with HEAT-OFF-COOL-AUTO system settings and fan ON-AUTO settings. Thermostat shall have a blue
backlit dot matrix LCD display with temperature, set-points, mode, and status indication. The temperature indication shall
be selectable for ºF or ºC. Time display shall be selectable for 12 or 24 hour clock. Fault identifi cation shall be provided
(when used with ClimateMaster CXM or DXM controls) to simplify troubleshooting by providing specifi c unit fault at the
thermostat with red backlit LCD during unit lockout. The thermostat shall provide permanent memory of set-points without
batteries. Thermostat shall provide heating set-point range limit, cooling set-point range limit, temperature display offset,
keypad lockout, dead-band range setting, and inter-stage differential settings. Thermostat shall provide progressive
recovery to anticipate time required to bring space temperature to the next programmed event. Thermostat shall provide
an installer setup for confi guring options and for setup of servicing contractor name and contact information. Thermostat
shall allow the use of an accessory remote and/or outdoor temperature sensor (AST008). Thermostat navigation shall be
accomplished via fi ve buttons (up/down/right/left/select) with menu-driven selections for ease of use and programming.
i. Multistage Automatic or Manual Changeover Programmable 7 Day with Humidity Control (ATP32U02)
Thermostat shall be 7 day programmable (with up to 4 set points per day), multi-stage (3H/2C), automatic or manual
changeover with HEAT-OFF-COOL-AUTO system settings and fan ON-AUTO settings. Separate dehumidifi cation and
humidifi cation set points shall be confi gurable for discreet outputs to a dehumidifi cation option and/or an external
humidifi er. Installer confi guration mode shall allow thermostat dehumidifi cation mode to operate with ClimaDry reheat or
with ECM fan dehumidifi cation mode via settings changes. Thermostat shall have a blue backlit dot matrix LCD display
with temperature, relative humidity, set-points, mode, and status indication. The temperature indication shall be selectable
for ºF or ºC. Time display shall be selectable for 12 or 24 hour clock. Fault identifi cation shall be provided (when used
with ClimateMaster CXM or DXM controls) to simplify troubleshooting by providing specifi c unit fault at the thermostat
with red backlit LCD during unit lockout. The thermostat shall provide permanent memory of set-points without batteries.
Thermostat shall provide heating set-point range limit, cooling set-point range limit, temperature display offset, keypad
lockout, dead-band range setting, and inter-stage differential settings. Thermostat shall provide progressive recovery to
anticipate time required to bring space temperature to the next programmed event. Thermostat shall provide an installer
setup for confi guring options and for setup of servicing contractor name and contact information. Thermostat shall allow
the use of an accessory remote and/or outdoor temperature sensor (AST008). Thermostat navigation shall be accomplished
via fi ve buttons (up/down/right/left/select) with menu-driven selections for ease of use and programming.
DDC Sensors:
ClimateMaster wall mounted DDC sensor to monitor room temperature and interfaces with optional interface system described
above. Several types as described below:
a. Sensor only with no display (LON and MPC).
b. Sensor with override (LON only).
c. Sensor with setpoint and adjustment override (MPC only).
d. Sensor with setpoint and adjustment override, LCD display, status/fault indication (LON and MPC).