Specifications

39
The Smart Choice for Energy Efficiency
Th
he Smart Choice for Energ
Riser Defi nitions
Riser Tailpiece (length of riser that extends down from cabinet bottom) -
Dimension F on submittal drawing- Riser tailpiece sized for 2" (51) insertion into 3" (76) expanded section at top
of cabinet. Actual job t may be 1" (25) to 3" (76) insertion (built-in +1" (25) oor to oor tolerance). Riser tailpiece
should extend beneath bottom of slab a minimum of 5" (127) to facilitate brazing.
3" Expanded Section - Riser expanded at top of unit to accept a pipe diameter from unit above. (Top of riser
always 3" (76) above top of unit.)
Floor to Floor Height (FF dim.) - Dimension from top of
unit slab to top of slab above.
Slab Thickness (ST dim.) - Includes basic slab thickness
plus any material added to slab prior to setting cabinets.
Clear Height (Top of unit slab to bottom of slab above)
- This dimension is used to determine whether cabinet-
riser assembly will pivot through slab core without hitting
bottom of slab above unit. If selected cabinet-riser will
not pivot into position, special riser extension or shorter
cabinet will have to be considered, (Clear height = oor
to oor dimension less thickness of slab above unit.)
Room Riser Height (cabinet height + 3" (76) - Standard
cabinet height (88"(2235)) + 3" (76) = 91" (2311) -
Shorter than standard cabinet heights will have shorter
room riser heights.
Maximum Riser Height - Maximum length is 115" (2921).
Total Riser Height (dim. L on submittal) - Room riser
(RRH) height + riser tailpiece length (F) = total riser
length (115" (2921) max.).
Total Riser Height = Floor to Floor + 2" (51)
(115" (2921) max.).
Slab thickness (ST) (slab above)
3 " (76)
Slab thickness (ST) (slab below)
Clear
Height
Floor to
Floor
Height (FF)
Room Riser
Height
(RRH)
Cabinet
Height
Total Riser
Height (L)
(115” Max.)
(2921)
Riser Tailpiece (F)