Specifications
22
ClimateMaster Water-Source Heat Pumps
Tranquility Modular (TRM) Series
0.75 to 3 Ton Vertical Hi-Rise Units
Performance Data TRM-12
Performance capacities shown in thousands of Btuh445 CFM Nominal (Rated) Airfl ow
*WPD Adder for 
Motorized Valve, 
TRM12
(Cv = 4.9, 
MOPD = 125 psi)
GPM
WPD Adder
PSI FT
1.5 0.46 1.06
2.3 1.17 2.70
3.0 2.16 4.99
EWT
°F
GPM
WPD* Cooling - EAT 80/67°F Heating - EAT 70°F
PSI FT TC SC
Sens/Tot 
Ratio
kW HR EER HC kW HE LAT COP
20 3.0 6.2 14.3
Operation Not Recommended
7.7 0.83 4.9 85.9 2.70
30
1.5 1.4 3.2 15.1 9.4 0.62 0.53 16.8 28.5 8.6 0.86 5.8 88.0 2.96
2.3 3.2 7.3 15.2 9.4 0.62 0.49 16.8 31.0 9.1 0.87 6.1 88.8 3.07
3.0 5.8 13.4 15.2 9.4 0.62 0.47 16.8 32.2 9.3 0.87 6.4 89.3 3.13
40
1.5 1.2 2.8 14.7 9.2 0.63 0.59 16.7 24.8 10.2 0.89 7.2 91.2 3.35
2.3 2.9 6.6 15.0 9.4 0.62 0.55 16.8 27.5 10.7 0.90 7.7 92.3 3.49
3.0 5.3 12.1 15.1 9.4 0.62 0.52 16.8 28.8 11.0 0.91 8.0 93.0 3.56
50
1.5 1.2 2.7 14.1 9.0 0.64 0.66 16.4 21.3 11.8 0.92 8.7 94.5 3.74
2.3 2.8 6.4 14.6 9.2 0.63 0.61 16.6 23.8 12.4 0.94 9.3 95.9 3.90
3.0 5.1 11.8 14.8 9.3 0.63 0.59 16.7 25.2 12.8 0.94 9.6 96.7 3.98
60
1.5 1.1 2.6 13.4 8.7 0.65 0.74 15.9 18.1 13.4 0.95 10.1 97.8 4.11
2.3 2.6 6.1 13.9 8.9 0.64 0.69 16.2 20.3 14.2 0.97 10.9 99.5 4.29
3.0 4.8 11.2 14.2 9.0 0.64 0.66 16.4 21.6 14.6 0.98 11.3 100.4 4.38
70
1.5 1.1 2.4 12.6 8.3 0.66 0.83 15.4 15.2 15.0 0.98 11.6 101.1 4.46
2.3 2.5 5.7 13.2 8.6 0.65 0.77 15.8 17.1 15.8 1.00 12.4 102.9 4.64
3.0 4.6 10.7 13.4 8.7 0.65 0.74 15.9 18.2 16.3 1.01 12.9 103.9 4.74
80
1.5 1.0 2.3 11.6 7.9 0.68 0.91 14.7 12.7 16.5 1.01 13.1 104.3 4.78
2.3 2.3 5.4 12.3 8.2 0.67 0.85 15.2 14.3 17.4 1.03 13.9 106.2 4.96
3.0 4.4 10.1 12.6 8.3 0.66 0.82 15.4 15.2 17.9 1.04 14.3 107.2 5.06
85
1.5 1.0 2.2 11.1 7.7 0.69 0.96 14.4 11.6 17.2 1.02 13.7 105.8 4.92
2.3 2.3 5.3 11.8 8.0 0.68 0.90  14.8 13.1 18.1 1.04 14.6 107.7 5.10
3.0 4.3 9.9 12.1 8.1 0.67 0.87 15.0 13.9 18.6 1.05 15.0 108.6 5.19
90
1.5 0.9 2.1 10.6 7.5 0.71 1.01 14.0 10.6 17.9 1.04 14.4 107.3 5.06
2.3 2.2 5.2 11.3 7.8 0.69 0.95 14.5 11.9 18.8 1.05 15.2 109.1 5.23
3.0 4.2 9.7 11.6 7.9 0.68 0.92 14.7 12.6 19.2 1.06 15.6 110.1 5.32
100
1.5 0.9 2.1 9.6 7.1 0.74 1.10 13.3 8.7
Operation Not Recommended
2.3 2.2 5.1 10.2 7.3 0.72 1.04 13.8 9.8
3.0 4.2 9.6 10.5 7.5 0.71 1.01 14.0 10.4
110
1.5 0.9 2.0 8.5 6.6 0.77 1.20 12.6 7.1
2.3 2.1 4.9 9.1 6.9 0.75 1.14 13.0 8.0
3.0 4.0 9.3 9.4 7.0 0.74 1.11 13.2 8.5
120
1.5 0.9 2.0 7.4 6.1 0.82 1.30 11.9 5.7
2.3 2.1 4.8 8.0 6.4 0.79 1.24 12.3 6.4
3.0 4.0 9.2 8.3 6.5 0.78 1.22 12.5 6.8
Interpolation is permissible; extrapolation is not.
All entering air conditions are 80°F DB and 67°F WB in cooling, and 70°F DB in heating. ARI/ISO certifi ed conditions are 
80.6°F DB and 66.2°F WB in cooling and 68°F DB in heating.
Table does not refl ect fan or pump power corrections for ARI/ISO conditions.
All performance is based upon the lower voltage of dual voltage rated units.
Operation below 60°F EWT requires optional insulated water/refrigerant circuit.
See performance correction tables for operating conditions other than those listed above.
See Performance Data Selection Notes for operation in the shaded area.