Service manual
THE SMART SOLUTION FOR ENERGY EFFICIENCY
Vertical Stack
Rev.: 11/09/12
25
climatemaster.com
Start-Up Preparation
System Cleaning and Flushing - Cleaning and fl ushing 
the unit is the single most important step to ensure 
proper start-up and continued effi cient operation of the 
system. Follow the instructions below to properly clean 
and fl ush the system: Do not fl ush through chassis koax.
1.  Verify that electrical power to the unit is disconnected.
2.  Verify that supply and return riser service valves are 
closed at each unit.
3.  Fill the system with water, leaving the air vents open. 
Bleed all air from the system but do not allow the 
system to over fl ow. Check the system for leaks and 
make any required repairs. 
4.  Adjust the water and air level in the expansion tank.
5.  With strainers in place, (ClimateMaster recommends a 
strainer with a #20 stainlees steel wire mesh) start the 
pumps. Systematically check each vent to ensure that 
all of the air is bled from the system.
6.  Verify that make-up water is available and adjusted to 
properly replace any space remaining when all air is 
evacuated. Check the system for leaks and make any 
additional repairs required.
7.  Set the boiler to raise the loop temperature to 
approximately 85°F [29.4°C]. Open the drain at the 
lowest point in the system. Verify that make-up water 
replacement rate equals rate of bleed. Continue to 
bleed the system until the water appears clean or for 
at least three hours whichever is longer.
8.  Completely drain the system.
Flush risers as follows: (Refer to Figure 14).
1.  Close shut-off valves at each cabinet on the riser 
except the shut-off valve on the top fl oor. 
2.  At the top fl oor, install the hose kit and connect the 
ends of the hoses with the factory riser fl ush adapter 
from AFL5751. 
3.  Flush solution through supply riser. Note: The solution 
passes through the top fl oor connection down the 
return riser. 
4.  When the building has more than 10 fl oors, connect the 
supply and return runouts on the top two fl oors to divide 
the water fl ow and reduce pressure drop at the pump. 
5. Repeat fl ushing procedure for each set of risers in 
 the building.
6. Refi ll the system and add in a proportion of trisodium 
phosphate approximately one pound per 150 gallons 
[0.4kg per 500 liters] of water. Reset the boiler to raise 
the loop temperature to about 100°F [37.8°C].
7.  Circulate the solution for between 8 to 24 hours. At 
the end of this period, shut off the circulating pump 
and drain the solution. Repeat system cleaning if 
desired. 
8.  Open the supply and return riser service valves at each 
unit. Refi ll the system and bleed off all air.
9.  Test the system pH with litmus paper. The system 
water should have a pH of 6 to 8.5. Add chemicals as 
appropriate to maintain pH levels.
10.  When the system is successfully cleaned, fl ushed, 
refi lled, and bled, check the main system panels, 
safety cutouts, and alarms. Set controls to properly 
maintain loop temperature.
To 
Waste
Figure 14: Typical piping arrangement for fl ushing risers.
 WARNING! 
WARNING! To prevent injury or death due to electrical shock 
or contact with moving part, open unit disconnect before 
servicing unit.
 CAUTION! 
CAUTION! Do Not use "Stop-Leak" or any similar chemical 
agent in this system. Addition of these chemicals to the loop 
water can foul the system and can inhibit unit operation.
 CAUTION! 
CAUTION! To avoid possible damage to piping systems 
constructed of plastic piping, DO NOT allow loop temperature 
to exceed 110°F [43.3°C].










