Service manual

THE SMART SOLUTION FOR ENERGY EFFICIENCY
Vertical Stack
Rev.: 11/09/12
25
climatemaster.com
Start-Up Preparation
System Cleaning and Flushing - Cleaning and fl ushing
the unit is the single most important step to ensure
proper start-up and continued effi cient operation of the
system. Follow the instructions below to properly clean
and fl ush the system: Do not fl ush through chassis koax.
1. Verify that electrical power to the unit is disconnected.
2. Verify that supply and return riser service valves are
closed at each unit.
3. Fill the system with water, leaving the air vents open.
Bleed all air from the system but do not allow the
system to over fl ow. Check the system for leaks and
make any required repairs.
4. Adjust the water and air level in the expansion tank.
5. With strainers in place, (ClimateMaster recommends a
strainer with a #20 stainlees steel wire mesh) start the
pumps. Systematically check each vent to ensure that
all of the air is bled from the system.
6. Verify that make-up water is available and adjusted to
properly replace any space remaining when all air is
evacuated. Check the system for leaks and make any
additional repairs required.
7. Set the boiler to raise the loop temperature to
approximately 85°F [29.4°C]. Open the drain at the
lowest point in the system. Verify that make-up water
replacement rate equals rate of bleed. Continue to
bleed the system until the water appears clean or for
at least three hours whichever is longer.
8. Completely drain the system.
Flush risers as follows: (Refer to Figure 14).
1. Close shut-off valves at each cabinet on the riser
except the shut-off valve on the top fl oor.
2. At the top fl oor, install the hose kit and connect the
ends of the hoses with the factory riser fl ush adapter
from AFL5751.
3. Flush solution through supply riser. Note: The solution
passes through the top fl oor connection down the
return riser.
4. When the building has more than 10 fl oors, connect the
supply and return runouts on the top two fl oors to divide
the water fl ow and reduce pressure drop at the pump.
5. Repeat ushing procedure for each set of risers in
the building.
6. Refi ll the system and add in a proportion of trisodium
phosphate approximately one pound per 150 gallons
[0.4kg per 500 liters] of water. Reset the boiler to raise
the loop temperature to about 100°F [37.8°C].
7. Circulate the solution for between 8 to 24 hours. At
the end of this period, shut off the circulating pump
and drain the solution. Repeat system cleaning if
desired.
8. Open the supply and return riser service valves at each
unit. Refi ll the system and bleed off all air.
9. Test the system pH with litmus paper. The system
water should have a pH of 6 to 8.5. Add chemicals as
appropriate to maintain pH levels.
10. When the system is successfully cleaned, fl ushed,
refi lled, and bled, check the main system panels,
safety cutouts, and alarms. Set controls to properly
maintain loop temperature.
Figure 14: Typical piping arrangement for fl ushing risers.
WARNING!
WARNING! To prevent injury or death due to electrical shock
or contact with moving part, open unit disconnect before
servicing unit.
CAUTION!
CAUTION! Do Not use "Stop-Leak" or any similar chemical
agent in this system. Addition of these chemicals to the loop
water can foul the system and can inhibit unit operation.
CAUTION!
CAUTION! To avoid possible damage to piping systems
constructed of plastic piping, DO NOT allow loop temperature
to exceed 110°F [43.3°C].