Service manual
CLIMATEMASTER WATER-SOURCE HEAT PUMPS
Vertical Stack
Rev.: 11/09/12
22
ClimateMaster Water-Source Heat Pumps
Table 5: TRM with ECM-X Motor
Blower Performance Data
Model
Motor
TAP
Rated
Airfl ow
Min 
CFM
Airfl ow (cfm) at External Static Pressure (in. wg)
0.0 0.1 0.2 0.25 0.3 0.35 0.4 0.5 0.6 0.7 0.8
TRM15
HI
600 416
650 590
 MED HI 650 635 620 560
MED 650 640 630 615 600 595 590 520
MED LOW* 600 590 575 550 540 535 525 425
LOW 500 480 470 460 450 435 423
TRM18
HI
650 480
675 650 590
 MED HI 680 650 635 620 560
MED* 650 640 630 615 600 595 590 520
MED LOW 600 590 575 550 540 535 525
LOW 500 480 470 460 450 435 423
TRM24
HI
900 596
925 875 840 800 750
 MED HI 920 900 840 800 750 700
MED 925 900 880 850 815 750 700 620
MED LOW* 900 870 850 820 790 760 740 645
LOW 850 770 730 690 650 630 610
TRM30
HI
1150 798
1200 1150 1100 1050 1030 995 950 925 875 840
 MED HI 1,200 1120 1050 1010 975 950 920 880 830 800
MED* 1,150 1070 1020 990 950 920 880 800
MED LOW 1,000 950 910 880 860 840 800
LOW 900 850 800
TRM36
HI
1290 820
1310 1290 1260 1240 1170 1090 1025 920 840
 MED HI* 1290 1260 1230 1150 1120 1100 1070 1030 960 880 805
MED 1190 1160 1140 1038 1010 990 950 910 860 820
MED LOW 860 840 825 800
LOW 820
All units AHRI/ISO/ASHRAE 13256-1 rated on 
* speed motor TAP.
Airfl ow is rated at lowest Voltage if unit is dual Voltage rated, i.e. 208V for 208-230V units.
Unit must have DXM. Factory shipped on low and medium tap. Field select other taps if needed.