Service manual
CLIMATEMASTER WATER-SOURCE HEAT PUMPS
Vertical Stack
Rev.: 11/09/12
18
ClimateMaster Water-Source Heat Pumps
Flow Regulation - Flow regulation can be accomplished 
by two methods. One method of fl ow regulation involves 
simply adjusting the ball valve or water control valve 
on the discharge line. Measure the pressure drop 
through the unit heat exchanger, and determine fl ow 
rate from. Since the pressure is constantly varying, two 
pressure gauges may be needed. Adjust the valve until 
the desired fl ow of 1.5 to 2 gpm per ton [2.0 to 2.6 l/m 
per kW] is achieved. A second method of fl ow control 
requires a fl ow control device mounted on the outlet of 
the water control valve. The device is typically a brass 
fi tting with an orifi ce of rubber or plastic material that is 
designed to allow a specifi ed fl ow rate. On occasion, fl ow 
control devices may produce velocity noise that can be 
reduced by applying some back pressure from the ball 
valve located on the discharge line. Slightly closing the 
valve will spread the pressure drop over both devices, 
lessening the velocity noise.
Note: When EWT is 
below 50°F [10°C], 2 gpm per ton (2.6 l/m per kW) is 
required.
Water Coil Low Temperature Limit Setting - For all 
open loop systems the 30°F [-1.1°C] FP1 setting (factory 
setting-water) should be used to avoid freeze damage to 
the unit. See “Low Water Temperature Cutout Selection” 
in this manual for details on the low limit setting.
NOTICE! Ground-water applications for commercial 
buildings with more than 2-3 units should include 
a plate frame heat-exchanger to isolate the heat 
pumps from the ground-water and confi ne heat 
exchanger cleanings to one location and lessen 
maintenance. Direct use of ground-water may 
increase the frequency of heat pump maintenance 
and may shorten life expectancy. 










