Specifications

TRM
9
www.climatemaster.com
THE SMART SOLUTION FOR ENERGY EFFICIENCY
Tranquility Vertical Stack (TRM) Series
Rev.: 05/23/07D
Performance Data
ARI/ASHRAE/ISO 13256-1
Model
Water Loop Heat Pump Ground Water Heat Pump Ground Loop Heat Pump
Cooling 86°F Heating 68°F Cooling 59°F Heating 50°F Cooling 77°F Heating 32°F
Capacity
Btuh
EER
Btuh/W
Capacity
Btuh
COP
Capacity
Btuh
EER
Btuh/W
Capacity
Btuh
COP
Capacity
Btuh
EER
Btuh/W
Capacity
Btuh
COP
TRM09 8,800 13.0 12,500 4.6 10,100 19.5 9,800 3.8 9,300 14.7 7,200 3.1
TRM12 11,600 13.0 15,800 4.5 13,700 20.0 12,700 3.8 12,200 15.0 9,500 3.1
TRM15 13,800 13.0 19,600 4.7 16,500 20.0 15,500 3.9 15,200 14.6 11,500 3.1
TRM18 16,700 13.0 22,600 4.7 19,600 19.5 18,200 3.8 17,600 14.6 14,000 3.1
TRM24 22,100 13.0 29,400 4.5 26,400 20.0 23,100 3.8 23,600 14.8 18,000 3.1
TRM30 27,100 13.0 33,100 4.6 30,600 18.6 27,700 4.0 29,200 16.0 20,600 3.1
TRM36 32,000 12.5 39,500 4.6 36,700 18.8 32,000 3.8 33,000 14.3 25,000 3.1
Cooling capacities based upon 80.6°F DB, 66.2°F WB entering air temperature
Heating capacities based upon 68°F DB, 59°F WB entering air temperature
All air ow is rated on high speed
All ratings based upon operation at lower voltage of dual voltage rated models
ASHRAE/ARI/ISO 13256-1. English (IP) Units
Model
Water Loop Heat Pump Ground Water Heat Pump Ground Loop Heat Pump
Cooling 30°C Heating 20°C Cooling 15°C Heating 10°C Cooling 25°C Heating 0°C
Capacity
Watts
EER
W/W
Capacity
Watts
COP
Capacity
Watts
EER
W/W
Capacity
Watts
COP
Capacity
Watts
EER
W/W
Capacity
Watts
COP
TRM09 2,579 3.8 3,664 4.6 2,930 5.7 2,872 3.8 2,726 4.3 2,110 3.1
TRM12 3,400 3.8 4,631 4.5 4,015 5.9 3,722 3.8 3,576 4.4 2,784 3.1
TRM15 4,045 3.8 5,744 4.7 4,836 5.9 4,543 3.9 4,455 4.3 3,370 3.1
TRM18 4,894 3.8 6,624 4.7 5,744 5.7 5,334 3.8 5,158 4.3 4,103 3.1
TRM24 6,477 3.8 8,617 4.5 7,737 5.9 6,770 3.8 6,917 4.3 5,276 3.1
TRM30 7,943 3.8 9,701 4.6 8,969 5.5 8,118 4.0 8,558 4.7 6,038 3.1
TRM36 9,379 3.7 11,577 4.6 10,756 5.5 9,379 3.8 9,672 4.2 7,327 3.1
Cooling capacities based upon 27°C DB, 19°C WB entering air temperature
Heating capacities based upon 20°C DB, 15°C WB entering air temperature
All air ow is rated on high speed
All ratings based upon operation at lower voltage of dual voltage rated models
ASHRAE/ARI/ISO 13256-1. Metric (SI) Units